ABB RELION REB500 Communication Protocol Manual

ABB RELION REB500 Communication Protocol Manual

Distributed busbar protection
Hide thumbs Also See for RELION REB500:

Advertisement

Quick Links

®
RELION
REB500
Distributed busbar protection REB500
Version 8.3 IEC
Communication protocol manual IEC 61850
/t1ain m1:nu
Events
Measu remen ts
Distu rbance records
Settings
10:5 3:.10
2013 -03- 30
joi,je ct name
j$sup erUs er
=
/Main menu
a
I
;
D
-
i!9?
t�, �
;;: ::
J
e
Setti rlgS
conf i� ation
rua,gr,o stics
rests
O•�
L¥19"39f�
; =
=
I D I
D
D

Advertisement

Table of Contents
loading

Summary of Contents for ABB RELION REB500

  • Page 1 ® RELION REB500 Distributed busbar protection REB500 Version 8.3 IEC Communication protocol manual IEC 61850 /t1ain m1:nu /Main menu i!9? Events t�, � ;;: :: Measu remen ts Distu rbance records Setti rlgS Settings conf i� ation rua,gr,o stics rests O•�...
  • Page 3 /t1ainm1:nu /Mainmenu i!9? Events J;;: :: t�,� Measuremen ts Disturbance records SettirlgS Settings confi� ation rua,gr,o stics rests O•� L¥19"39f� joi,ject name j$superUs er 3:.10 2013-03- 3010:5 I D I Document ID: 1MRK 511 450-UEN Issued: October 2020 Revision: C Product version: 8.3 ©...
  • Page 4 Toolkit (http://www.openssl.org/). This product includes cryptographic software written/ developed by: Eric Young (eay@cryptsoft.com) and Tim Hudson(tjh@cryptsoft.com). Trademarks ABB and Relion are registered trademarks of the ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
  • Page 5 Hitachi Power Grids be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment. ABB is a registered trademark of ABB Asea Brown Boveri Ltd. Manufactured by/for a Hitachi Power Grids company.
  • Page 6 (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB Power Grids in accordance with the product standard EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
  • Page 7: Table Of Contents

    1MRK 511 450-UEN Rev. C Table of contents Table of contents Section 1 Introduction....................3 This manual............................3 Intended audience........................3 Revision history..........................3 Product documentation......................3 Symbols and conventions......................4 1.5.1 Symbols............................4 1.5.2 Document conventions......................4 Section 2 Safety information..................5 Section 3 Interbay bus functions...................7 Introduction...........................
  • Page 9: Introduction

    1MRK 511 450-UEN Rev. C Section 1 Introduction Section 1 Introduction This manual GUID-FD38FA69-DDD6-40C9-9185-7AC9C894B6C6 v1 The communication protocol manual describes a communication protocol supported by the IED. The manual concentrates on vendor-specific implementations. Intended audience GUID-ACC7A898-5907-41E1-8DDD-DD8591298668 v1 This manual addresses the communication system engineer or system integrator responsible for pre-engineering and engineering for communication setup in a substation from an IED perspective.
  • Page 10: Symbols And Conventions

    Section 1 1MRK 511 450-UEN Rev. C Introduction Symbols and conventions 1.5.1 Symbols GUID-4F7DD10A-DEE5-4297-8697-B8AAB5E3262F v2 The electrical warning icon indicates the presence of a hazard which could result in electrical shock. The warning icon indicates the presence of a hazard which could result in personal injury.
  • Page 11: Safety Information

    1MRK 511 450-UEN Rev. C Section 2 Safety information Section 2 Safety information GUID-7CDA9FB7-5CD6-4BD5-A1D2-AAB8E7BF87A3 v3 Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been disconnected. Non-observance can result in death, personal injury or substantial property damage.
  • Page 13: Interbay Bus Functions

    1MRK 511 450-UEN Rev. C Section 3 Interbay bus functions Section 3 Interbay bus functions GUID-FC8C1289-F943-4E92-A50E-BDA7281A5337 v1 Introduction GUID-7A41F2A2-F366-4D30-9D76-BB6279380110 v3 An interface is available for connecting the numerical busbar protection to a station automation system or station monitoring system (SCS/SMS). For an overview of REB500’s communication interfaces, see the Operation manual .
  • Page 14 Section 3 1MRK 511 450-UEN Rev. C Interbay bus functions Table 1: Configuration of IEC 61850-8-1 Setting Description Default setting IED Name 61850 Name of the REB500 IED REB500 RCB’s buffered 61850 report control blocks transfer None mode (for communication with third- party systems).
  • Page 15 1MRK 511 450-UEN Rev. C Section 3 Interbay bus functions Table 2: Configuration Ethernet communication Setting Description Default setting IP address IEC 61850-8-1 TCP/IP Address 0.0.0.0 Subnet mask IEC 61850-8-1 TCP/IP Subnet Mask 0.0.0.0 Gateway address IEC 61850-8-1 TCP/IP Gateway Address 0.0.0.0 The dialog box for configuring the communication is accessed by selecting Time in the HMI500 Setting menu.
  • Page 16: Configuring Iec 61850-8-1 Ibb

    Section 3 1MRK 511 450-UEN Rev. C Interbay bus functions 13000023-IEC18000607-1-en.vsdx IEC18000607 V1 EN-US Figure 5: Dialog box for configuring time synchronization Table 3: Configuration of IEC 61850-8-1 time synchronization Setting Description Default setting Time zone correction Time zone setting (hours/minutes) See Screenshot (h/m) Daylight saving time...
  • Page 17: Logical Node Ggio (Generic Process I/O) Configuration

    1MRK 511 450-UEN Rev. C Section 3 Interbay bus functions 13000024-IEC18000608-1-en.vsdx IEC18000608 V1 EN-US Figure 6: Configuring signals as events Diagnostic and system events are always available for transfer whichever protocol is in use and cannot be configured. The IEC 60870-5-103 section only appears when the protocol is configured. 3.3.2 Logical node GGIO (Generic process I/O) configuration GUID-49BCE444-5FF8-4226-800B-E1399532950B v3...
  • Page 18 Section 3 1MRK 511 450-UEN Rev. C Interbay bus functions 15000025-IEC18000609-1-en.vsdx IEC18000609 V1 EN-US Figure 7: Configuring I/Os as GGIO Leading and lagging edges shall be ticked. The IBB which is configured for IEC 61850-8-1 shall be ticked. The User defined text can be changed to identify the signal in the 61850 client tool. 15000026-IEC18000610-1-en.vsdx IEC18000610 V1 EN-US Figure 8:...
  • Page 19: Bay Protection Specific Signals

    1MRK 511 450-UEN Rev. C Section 3 Interbay bus functions Setting Description Default setting User defined text Bin_Out_Channel Bin_In_Channel Default text Send event to At least one event memory must be selected IBB x Events can be assigned to the event lists of interbay bus (IBB) 1 and/or 2 External MMC Events are stored in the CU memories...
  • Page 20 Section 3 1MRK 511 450-UEN Rev. C Interbay bus functions Table 5: Composing logical node name for bay protection Element Example for Field Comment OCINST Function no. IEEE Prefix Phase Lx / N0 Prefix Omitted if three phase protection Logical node name PTOC lnClass Time overcurrent function...
  • Page 21: Transfer Of Differential Current Values

    1MRK 511 450-UEN Rev. C Section 3 Interbay bus functions Transfer of differential current values 3.4.1 The delta/dead band algorithm GUID-85BE2C1A-DD67-4564-99E1-CF504CBD06D7 v1 To keep the load on the IBB as low as possible, the bus zone differential currents are checked cyclically, but only actually transferred via the bus if the value has changed.
  • Page 22 Section 3 1MRK 511 450-UEN Rev. C Interbay bus functions 12000190-IEC18000536-1-en.vsdx IEC18000536 V1 EN-US Figure 13: Settings/Communication/SCS Diff. Current Parameters Settings in this dialog box are made for each busbar section (bus zone) and can be changed after activating the respective field. The differential current parameters are as follows: Table 7: SCS differential current parameters Item...
  • Page 23: Iec 61850-8-1

    All logical nodes are assigned to logical devices. All REB500 bay units, as well as the central unit are defined as a logical device. The designation of the logical device are based on the associated ABB reference for the bay or central unit and the REB500 Name.
  • Page 24 Section 4 1MRK 511 450-UEN Rev. C IEC 61850-8-1 REB500 signal Prefix Data Attribute 13761_BP Start BFP L1L2L3_5 GAPC Ind07 13770_BP Start BFP L1 GAPC Ind08 13775_BP Start BFP L2 GAPC Ind09 13780_BP Start BFP L3 GAPC Ind10 13785_BP Start BFP L1L2L3 GAPC Ind11 13790_BP External Start BFP...
  • Page 25 1MRK 511 450-UEN Rev. C Section 4 IEC 61850-8-1 REB500 signal Prefix Data Attribute 41505_Isolator alarm Swi_ CALH GrAlm 41815_Diff. current alarm BBP_ PDIF DifAlm 41820_Loss of supply voltage Bat_ CALH GrAlm 41830_Switch inhibit Swi_ CALH GrAlm 41840_PRP LineA ready LCCH ChLiv 41845_PRP LineB ready...
  • Page 26: Bay Protection Specific Signals

    Section 4 1MRK 511 450-UEN Rev. C IEC 61850-8-1 REB500 signal Prefix Data Attribute 56855_MemUsed RDRE MemUsed 56860_MemClsCommand RDRE MemClr.Oper 56865_MemRsCommand RDRE MemRs.Oper 56870_RCDMade RDRE RcdMade 56875_MemClsStVal RDRE MemClr.stval 56880_MemRsStVal RDRE MemRs.stval 59305_APC_Trip PTRC Tr.general 59810_APC_Faultloc_Ohm_Output RFLO FltZ 59815_APC_Faultloc_Km_Output RFLO FltDiskm To ensure that a signal is correctly transmitted via IEC 61850, it must be configured and allocated as an event to the IEC 61850 interface.
  • Page 27 1MRK 511 450-UEN Rev. C Section 4 IEC 61850-8-1 REB500 signal Prefix Data Attribute 211860_DIST Weak Infeed PDIS OpWeI.general 211865_DIST Power Swing PDIS OpPwS.general 211870_DIST VT Sup PDIS FuFail.stVal 211880_DIST Com Send PSCH TxTr.stVal 212105_OCDT TRIP F51 F51Lx PTOC F51N0 212705_OCDT Start F51 F51Lx PTOC...
  • Page 28: Differential Currents

    Section 4 1MRK 511 450-UEN Rev. C IEC 61850-8-1 REB500 signal Prefix Data Attribute 218605_AR Close CB RREC OpCls 218610_AR Close CB2 RREC OpCls2 218805_AR Ready RREC RdyRec 218810_AR In Progress RREC ActRec 218815_AR First AR 1P RREC PrgRec11 218820_AR First AR 3P RREC PrgRec31 218825_AR Second AR...
  • Page 29: Disturbance Recorder

    1MRK 511 450-UEN Rev. C Section 4 IEC 61850-8-1 Table 10: Differential currents REB500 data LN ABB designation Data Attribute Differential currents BusZone PDIF DifAClc.phsA.mag.f DifAClc.phsB.mag.f DifAClc.phsC.mag.f DifAClc.neut.mag.f Disturbance recorder GUID-3F1AB65C-D36F-4060-BD76-59DB3F0A8E14 v2 The logical node RDRE of each logical device provides a signal indicating of the disturbance recorder status and the commands for deleting the memory.
  • Page 30: Goose Supervision (Lgos)

    Section 4 1MRK 511 450-UEN Rev. C IEC 61850-8-1 GOOSE supervision (LGOS) GUID-69A7DC7A-AA20-41A2-962E-06B2CC4A3263 v1 The LGOS is used to monitor subscription states to GOOSE signals per sender control block instance at a receiver. They contain information like status of the subscription (active, not active) and other information, for example;...
  • Page 31 1MRK 511 450-UEN Rev. C Section 4 IEC 61850-8-1 Source system state LLN0.Health LPHD.PhyHealth Source signal All BUs connected F→A 41505_Isolator alarm T→A 41830_Switch inhibit T→A 41815_Diff. current alarm T→A Table 14: Source of BU health Source system state LLN0.Health LLPHD.PhyHealth Source signal BU disconnected...
  • Page 34 ABB Power Grids Sweden AB Grid Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 10 738 00 00 Scan this QR code to visit our website https://www.abb.com/protection-control © 2019 - 2020 Hitachi Power Grids. All rights reserved.