Rack installation instructions

Review the documentation that comes with the rack cabinet for safety and cabling information. Before
you install the server in a rack cabinet, review the following guidelines:
v Two or more people are required to install devices 2U or larger in a rack cabinet.
v One or more people are required to install devices 1U or larger in a rack cabinet.
v Make sure that the room air temperature is below 40°C (104°F).
v Do not block any air vents; usually 15 cm (6 in.) of space provides proper airflow.
v Do not leave open spaces above or below an installed server in your rack cabinet. To help prevent
damage to server components, always install a blank filler panel to cover the open space and to help
ensure proper air circulation.
v Install the server only in a rack cabinet with perforated doors.
v Plan the device installation starting from the bottom of the rack cabinet.
v Install the heaviest device in the bottom of the rack cabinet.
v Always install the tip plates on the rack.
v Do not extend more than one device out of the rack cabinet at the same time.
v Remove the rack doors and side panels to provide easier access during installation.
v Connect the server to a properly grounded outlet.
v Do not overload the power outlet when you install multiple devices in the rack cabinet.
v Install the server in a rack that meets the following requirements:
– Minimum depth of 70 mm (2.76 in.) between the front mounting flange and inside of the front door.
– Minimum depth of 157 mm (6.18 in.) between the rear mounting flange and inside of the rear door.
Use safe practices when lifting.
Do not place any objects on top of
rack-mounted devices.
Notes:
1. When you install a 2U server, be sure to install the rails in the bottom U of the 2U area in the rack.
2. Cage nuts and clip nuts may be required to install the server in a rack cabinet.
3. Your server might look different from the servers that are illustrated, and some parts of the rack
installation kit might not be used.
≥32 kg (70.5 lb)
≥18 kg (39.7 lb)
≥55 kg (121.2 lb)

Advertisement

loading

Summary of Contents for Lenovo 2U

  • Page 1: Rack Installation Instructions

    Notes: 1. When you install a 2U server, be sure to install the rails in the bottom U of the 2U area in the rack. 2. Cage nuts and clip nuts may be required to install the server in a rack cabinet.
  • Page 2 Countersunk head 10-32 screws for shipping brackets (right) M4 screws Adapters 10-32 screws 12-24 screws (L12)(2) M4 screws M5 screws M6 screws 10-32 screws Shipping (L8)(8) (L12)(2) brackets 2U shipping 2U shipping Cage nuts bracket bracket (left) (right) Front of rails...
  • Page 3 Installing a 2U server into the rack For rack with square-shaped or circle-shaped holes Square-shaped holes Square-shaped holes Rack Rear Rack Front Circle-shaped holes Circle-shaped holes Installing the rear end of the rails in a rack with Installing the front end of the rails in a rack with non-threaded holes.
  • Page 4 For rack with threaded-holes Before installing the rails in rack with threaded Installing the rails in a rack with threaded holes. holes, first install the adapters on the front and Align the pins on the rear of the rail and attached rear side of the rails.
  • Page 5 Installing the server on the rails. Tightening the front thumbscrews. Carefully hold the server and tilt it into position When you move the rack cabinet, or if you install over the rails, and then slowly lower the rear of the the rack cabinet in a vibration-prone area, tighten server on the rails 1 .
  • Page 6 When installing this the left side of the rail marked "2U". After knowing screw, make sure the thread in the hole matches the which hole to align with, insert the shipping specific screw that is needed.
  • Page 7 (For 2U server square-hole rack) Shipping bracket (For 2U server circle-hole rack) Securing the server in the rack with non-threaded holes for shipping (continued).
  • Page 8 Installing a 1U server into the rack For rack with square-shaped or circle-shaped holes Square-shaped holes Square-shaped holes Rack Rear Rack Front Circle-shaped holes Circle-shaped holes Installing the rear end of the rails in a rack with Installing the front end of the rails in a rack with non-threaded holes.
  • Page 9 For rack with threaded-holes For 1U Server Adapter M4 (L12 ) screw Installing the M4 (L12) screw into the adapter. Before installing the rails in rack with threaded holes, first install the adapters on the front and Insert the M4 (L12) screw into the holes on the rear side of the rails.
  • Page 10 Installing the rails with the attached adapters in a Removing the rack brackets from the server. rack with threaded holes. Note: If your server does not come with the rack Align the pins on the rear of the rail and attached brackets, go to step 5.
  • Page 11 Washers Rack Front Rack Front Installing the rack brackets. Installing the rack brackets (for racks with square-shaped holes on the front). Align the hole on the rack bracket with the middle hole on the front of the rack; then, install the screws Align the hole on the rack bracket with the middle to secure the rack bracket in the rack.
  • Page 12 Installing the server on the rails. Tightening the front thumbscrews (for specific models). Carefully hold the server and tilt it into position over the rails, and then slowly lower the rear of the Depending on your server model, thumbscrews are server on the rails 1 .
  • Page 13 Installing shipping brackets to 1U server for shipping (For 1U server Rack Rear threaded-hole rack) Shipping bracket Shipping bracket hooks Securing the server in the rack with threaded Securing the server in the rack with threaded holes for shipping. holes for shipping (continued). Note: If you install the server in a rack with threaded holes, you must remove the server from the rack before installing the shipping brackets.
  • Page 14 Circle-shaped holes Rack Rear (For 1U server square-hole rack) Shipping bracket (For 1U server Shipping circle-hole rack) bracket hooks Square-shaped holes Securing the server in the rack with non-threaded Securing the server in the rack with non-threaded holes for shipping. holes for shipping (continued).
  • Page 15 Removing a 2U server from the rack Square-shaped holes Rack Rear Circle-shaped holes Removing the server from the rack. Removing the rear end of the rails with non-threaded holes. To remove the server from the rack, disconnect the Notes: cables from the rear of the server. Loosen the thumbscrews and lift the handle on the front of the 1.
  • Page 16 Square-shaped holes Threaded-hole rack Rack Front Circle-shaped holes Removing the front end of the rails with Removing the rails with threaded holes. non-threaded holes. To remove the rails from a rack with threaded To remove the rails from the front of the rack, push holes, first remove the shipping bracket from the in the lower pin 1 and lift up slightly on the front rack by unscrewing the screw;...
  • Page 17 Removing a 1U server from the rack Removing the server that comes with latches from Removing the server that comes with front the rack. thumbscrews. Note: If your server comes with thumbscrews, refer To remove the server from the rack, disconnect the to the illustration on the right.
  • Page 18 Threaded-hole rack Rack Front Removing the rack brackets. Removing the rails from a rack with threaded holes. Loosen the screws and remove the rack brackets from the front end of the rails. To remove the rails from a rack with threaded holes, remove the screws from the front and rear of the rails;...
  • Page 19 Third Edition (November 2014) © Copyright Lenovo 2014. LIMITED AND RESTRICTED RIGHTS NOTICE: If data or software is delivered pursuant a General Services Administration “GSA” contract, use, reproduction, or disclosure is subject to restrictions set forth in Contract No. GS-35F-05925.