GE UR Series B30 Instruction Manual page 85

Bus differential system
Hide thumbs Also See for UR Series B30:
Table of Contents

Advertisement

3 HARDWARE
2.
Remove the module cover screw.
3.
Remove the top cover by sliding it towards the rear and then lift it upwards.
4.
Set the timing selection switches (channel 1, channel 2) to the desired timing modes.
5.
Replace the top cover and the cover screw.
6.
Re-insert the G.703 module. Take care to ensure that the correct module type is inserted into the correct slot position.
The ejector/inserter clips located at the top and at the bottom of each module must be in the disengaged position as
the module is smoothly inserted into the slot. Once the clips have cleared the raised edge of the chassis, engage the
clips simultaneously. When the clips have locked into position, the module will be fully inserted.
Table 3–5: G.703 TIMING SELECTIONS
SWITCHES
FUNCTION
OFF → octet timing disabled
S1
ON → octet timing 8 kHz
S5 and S6
S5 = OFF and S6 = OFF → loop timing mode
S5 = ON and S6 = OFF → internal timing mode
S5 = OFF and S6 = ON → minimum remote loopback mode
S5 = ON and S6 = ON → dual loopback mode
c) G.703 OCTET TIMING
If octet timing is enabled (on), this 8 kHz signal will be asserted during the violation of bit 8 (LSB) necessary for connecting
to higher order systems. When B30s are connected back to back, octet timing should be disabled (off).
d) G.703 TIMING MODES
There are two timing modes for the G.703 module: internal timing mode and loop timing mode (default).
Internal Timing Mode: The system clock is generated internally. Therefore, the G.703 timing selection should be in
the internal timing mode for back-to-back (UR-to-UR) connections. For back-to-back connections, set for octet timing
(S1 = OFF) and timing mode to internal timing (S5 = ON and S6 = OFF).
GE Multilin
Figure 3–36: G.703 TIMING SELECTION SWITCH SETTING
B30 Bus Differential System
3.3 DIRECT INPUT AND OUTPUT COMMUNICATIONS
3
3-33