9.5
Information about electromagnetic compatibility (EMC) and cable
routing
9.5.1

General

Requirements to implement EMC are listed in EN 61000-6-2, EN 61000-6-4, EN 61800-3,
EN 60204-1 and in the EMC Design Directives - Order No. 6FC5297-☐AD30-0AP☐.
Conformance with the EMC Directive of the EC can be secured by following the measures
described in the EMC Design Directives.
When mounting components in cabinets, in order to fulfill the EMC directive, the following
conditions must be additionally observed:
● Connected to TN line supply systems with grounded neutral point
● SINAMICS line filter (optional for frame size FSA)
● Observance of information about cable shielding and equipotential bonding
● Only the recommended Siemens power and signal cables are used
● Only cables from Siemens must be used for DRIVE-CLiQ connections.
For MOTION-CONNECT cables refer to catalog D21.1 or D21.2
CAUTION
If couplings or cabinet glands are required for the DRIVE-CLiQ connections, then only the
DRIVE-CLiQ coupling and DRIVE-CLiQ cabinet gland, described in the Chapter
Accessories, may be used.
If the shielding procedures described and the specified cable lengths are not observed, the
machine may not operate properly.
AC Drive
Manual, (GH6), 07/2007 Edition, 6SL3097-2AL00-0BP2

9.5 Information about electromagnetic compatibility (EMC) and cable routing

DANGER
Cabinet Design and EMC for Components, Blocksize Format
301