6.6. Access to the PROFIdrive parameter

In the cyclic PROFINET communication, the parameter data is transferred via Telegram 100 or 101. If the
requirement is not executed, the cause is distinguished by octet 7 and 8.
PKW
(Parameter ID/value)
PKE
IND
Octet 1 Octet 2 Octet 3 Octet 4 Octet 5 Octet 6 Octet 7 Octet 8
PKE (Parameter ID)
15
14
13
12
AK
(Task ID/Response ID)
AK (Request from Master to this product)
Request ID
Function
0
No task
1
Request parameter value
2
Change parameter value (word)
6
Request parameter value (array)
7
Change parameter value (array)
AK (Response from this product to Master)
Response ID
Function
0
No response
1
Transfer parameter value (word)
4
Transfer parameter value (array)
7
Task can not be executed, followed by error number
11 = No parameter change rights
17 = Task cannot be executed due to operating status
18 = Other error
102 = Request not supported
SPM: always 0.
PWE
11
10
9
SPM
0 = Illegal parameter number
1 = Parameter value cannot be changed
2 = Lower or upper limit violated
3 = Erroneous sub index
(e.g. parameter is currently read-only)
PZD
Process data (cyclically)
PZD1
STW
ZSW
8
7
6
5
PNU
(Parameter number)
Note
for PNU access
for PNU access
for PNU access or inverter parameter access
for PNU access or inverter parameter access
- 50 -
E6582051
PZD2
HSW
HIW
4
3
2
1
0