CHAPTER 5: SETTINGS
Write the following FlexLogic equation (EnerVista example shown).
Set both timers (Timer 1 and Timer 2) to 20 ms pickup and 0 ms dropout.
Program the Latching Outputs by making the following changes in the
OUTPUTS  CONTACT OUTPUT H1a
: "VO1"
OUTPUT H1a OPERATE
: "VO4"
OUTPUT H1a RESET
: "VO2"
OUTPUT H1c OPERATE
: "VO3"
OUTPUT H1c RESET
Application example 4
A latching contact H1a is to be controlled from a single virtual output VO1. The contact is to remain closed as long as VO1
is high, and is to remain opened when VO1 is low. Program the relay as follows.
Write the following FlexLogic equation (EnerVista example shown).
Program the Latching Outputs by making the following changes in the
OUTPUTS  CONTACT OUTPUT H1a
: "VO1"
OUTPUT H1a OPERATE
: "VO2"
OUTPUT H1a RESET

5.9.4 Virtual outputs

SETTINGS  INPUTS/OUTPUTS  VIRTUAL OUTPUTS  VIRTUAL OUTPUT 1(96)
 VIRTUAL OUTPUT 1
C60 BREAKER PROTECTION SYSTEM – INSTRUCTION MANUAL
and
menus (assuming an H4L module):
CONTACT OUTPUT H1c
menu (assuming an H4L module):
VIRTUAL OUTPUT 1 ID
Virt Op 1
VIRTUAL OUTPUT 1
EVENTS: Disabled
SETTINGS  INPUTS/OUTPUTS  CONTACT
SETTINGS  INPUTS/OUTPUTS  CONTACT
Range: up to 12 alphanumeric characters
Range: Disabled, Enabled
INPUTS/OUTPUTS
5
5-267