■ Wiring
▼ The following steps must be performed before wiring.
(1) Turn off all input power to the inverter.
Mandatory
(2) Wait at least 15 minutes and check to make sure that the charge
(3) Use a tester that can measure
If these steps are not properly performed, the wiring will cause electric
shock.
▼ Tighten the screws on the terminal board to specified torque.
If the screws are not tightened to the specified torque, it may lead to fire.
*1) In case of 690V inverter, use a tester of DC voltage 1400VDC or more.
■ Operations
▼ Do not touch inverter and option unit terminals when electrical power is
applied to the inverter even if the motor is stopped.
Prohibited
Touching the inverter terminals while power is connected to it may result
in electric shock.
▼ Do not touch switches when hands are wet and do not try to clean the
inverter with a damp cloth. Such practices may result in electric shock.
▼ Do not pull the cable. This can result in damage or malfunction.
■ Disposal
▼ If you throw away this product, have it done by a specialist in industry
waste disposal*. If the collection, transport and disposal of industrial
Mandatory
waste is done by someone who is not licensed for that job, it is a
punishable violation of the law. (Laws in regard to cleaning and
processing of waste materials)
(*)Persons who specialize in the processing of waste and known as
"industrial waste product collectors and transporters" or "industrial waste
disposal persons".
lamp of the VF-AS1/PS1/AS3 is no longer lit.
check to make sure that the voltage to the DC main circuits (between
PA and PC) is 45V or less.
Warning
*1)
DC voltage 800VDC or more, and
Warning
Caution
E6581436