Hitachi SJ300 Series Manual page 20

Sensorless vector contro
Hide thumbs Also See for SJ300 Series:
Table of Contents

Advertisement

●Terminal Description [
Symbol
L
Power Supply
H
O
Frequency Setting
O2
OI
AM
Monitor Output
AMI
Monitor Output
FM
P24
Power Supply
CM1
Run
FW
Command
1
[RS/RS]
2
[AT/AT]
3
[JG/JG]
4
[FRS/FRS]
Functions
5
Contact
[2CH/2CH]
Input
6
[CF2/USP]
7
[CF1/CF1]
8
[RV/RV]
Common
PLC
Terminal
11
[FA1/FA1]
12
[RUN/RUN]
13
Open
[OL/OL]
Collector
State
14
Output
[OTQ/OTQ]
15
[IP/IP]
CM2
Analog
Sensor
TH
Input
AL0
Relay
AL1
State/
Output
Alarm
AL2
[AL/AL]
]: Default setting (CE/UL)
Name
Common Terminal for Analog
Common terminal for H, O, O2, OI, AM, and AMI. Do not ground.
Power Source
Power Source for Frequency
Power supply for frequency command input
Setting
Maximum frequency is attained at DC 10V in DC 0 - 10V range. Set the
Frequency Command Terminal
voltage at A014 to command maximum frequency below DC 10V.
O2 signal is added to the frequency command of O or OI in DC
Frequency Command Extra
±
0 -
Terminal
can be input also at O2 terminal.
Maximum frequency is attained at DC 20mA in DC 4 - 20mA range.
Frequency Command Terminal
When the intelligent terminal configured as AT is on, OI signal is enabled.
Analog Output Monitor (Voltage)
Selection of one function from:
Output frequency, output current, torque, output voltage, input
power, electronic thermal load ratio, and LAD frequency.
Analog Output Monitor (Current)
[DC0-10V output (PWM output)] Selection of one function from:
Output frequency, output current, torque, output voltage, input
Digital Monitor (Voltage)
power, electronic thermal load ratio, and LAD frequency.
[Digital pulse output (Pulse voltage DC 0/10V)] Outputs the value
of output frequency as digital pulse (duty 50%)
Internal power supply for input terminals. In the case of source
Power Terminal for Interface
type logic, common terminal for contact input terminals.
Common terminal for P24, TH, and FM. In the case of sink type log-
Common Terminal for Interface
ic, common terminal for contact input terminals. Do not ground.
The motor runs forward when FW terminal is ON,
Forward Command Input
and stops when FW is OFF.
Intelligent Input Terminals
Assign 8 functions to terminals.
(Refer to the standard specifications for the functions.)
Select sink or source logic with the short-circuit bar on the control
Common Terminal for
terminals.
Intelligent Input Terminals,
Sink logic: Short P24 to PLC / Source logic: Short CM1 to PLC.
Common Terminal for
When applying external power source, remove the short-circuit bar
External Power Supply for
and connect PLC terminal to the external device.
PLCs, etc.
Assign 5 functions to open collector outputs.
When the alarm code is selected at C062, terminal 11
-
11
(Refer to the standard specifications for the functions.)
Intelligent Output Terminals
Both sink and source logic are always applicable between each
terminal and CM1.
Common Terminal for
Common terminal for intelligent output terminal 11
Intelligent Output Terminals
The inverter trips when the external thermistor detects abnormal
temperature. Common terminal is CM1.
[Recommended thermistor characteristics]
Thermistor Input Terminals
Allowable rated power: 100mW or over.
Impedance in the case of abnormal temperature: 3kΩ
Note: Thermal protection level can be set between 0 and 9999Ω.
In default setting, an alarm is activated when inverter output is
Alarm Output Terminals
turned off by a protective function.
Explanation of Terminals
10V range. By changing configuration, frequency command
14 are reserved for error codes of inverter trip.
Ratings
DC 10V, 20mA max.
Input impedance: 10kΩ, Allowable
input voltage range: DC - 0.3 - +12V
Input impedance:10kΩ, Allowable
input voltage range: DC 0 -
Input impedance: 100Ω, Allowable
input voltage range: DC 0 - 24mA
DC 0 - 10V, 2mA max.
DC 4 - 20mA, 250Ω max.
Digital output frequency
range: 0 - 3.6kHz, 1.2mA max.
DC 24V, 100mA max.
[Input ON condition]
Voltage between each terminal
and PLC: DC 18V min.
[Input OFF condition]
Voltage between each terminal
and PLC: DC 3V max.
Input impedance between each
terminal and PLC: 4.7Ω
Allowable maximum voltage
between each terminal and
PLC: DC 27V
Decrease in voltage between
-
13 or
each terminal and CM2:
4V max. during ON
Allowable maximum voltage:
DC 27V
Allowable maximum current:
50mA
-
15.
Allowable input voltage range
DC0 - 5V
Input Circuit
TH
Thermistor
CM1
Maximum capacity of relays
-
AL1
AL0:
AC 250V, 2A(R load)/0.2A(L load)
DC 30V, 8A(R load)/0.6A(L load)
-
AL2
AL0:
AC 250V, 1A(R load)/0.2A(L load)
DC 30V, 1A(R load)/0.2A(L load)
Minimum capacity of relays
-
-
AL1
AL0, AL2
AL0:
AC100V, 10mA DC5V, 100mA
±
12V
DC5V
10kΩ
1kΩ
20

Hide quick links: