5 SETTINGS
a) SETTINGS
PATH: SETTINGS
SYSTEM SETUP
FLEXCURVE A
FlexCurves™ A through D have settings for entering times to reset/operate at the following pickup levels: 0.00 to 0.98 and
1.03 to 20.00. This data is converted into two continuous curves by linear interpolation between data points. To enter a cus-
tom FlexCurve™, enter the reset/operate time (using the VALUE keys) for each selected pickup point (using the MES-
SAGE UP/DOWN keys) for the desired protection curve (A, B, C, or D).
Table 5–3: FLEXCURVE™ TABLE
RESET
TIME
RESET
MS
0.00
0.68
0.05
0.70
0.10
0.72
0.15
0.74
0.20
0.76
0.25
0.78
0.30
0.80
0.35
0.82
0.40
0.84
0.45
0.86
0.48
0.88
0.50
0.90
0.52
0.91
0.54
0.92
0.56
0.93
0.58
0.94
0.60
0.95
0.62
0.96
0.64
0.97
0.66
0.98
The relay using a given FlexCurve™ applies linear approximation for times between the user-entered
points. Special care must be applied when setting the two points that are close to the multiple of pickup of
NOTE
1; that is, 0.98 pu and 1.03 pu. It is recommended to set the two times to a similar value; otherwise, the lin-
ear approximation may result in undesired behavior for the operating quantity that is close to 1.00 pu.
GE Multilin

FLEXCURVES

FLEXCURVE A(D)
FLEXCURVE A TIME AT
0.00 xPKP:
TIME
OPERATE
TIME
MS
MS
1.03
1.05
1.1
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
2.0
2.1
2.2
2.3
2.4
2.5
2.6
2.7
2.8
D30 Line Distance Relay
Range: 0 to 65535 ms in steps of 1
0 ms
OPERATE
TIME
OPERATE
MS
2.9
4.9
3.0
5.0
3.1
5.1
3.2
5.2
3.3
5.3
3.4
5.4
3.5
5.5
3.6
5.6
3.7
5.7
3.8
5.8
3.9
5.9
4.0
6.0
4.1
6.5
4.2
7.0
4.3
7.5
4.4
8.0
4.5
8.5
4.6
9.0
4.7
9.5
4.8
10.0
5.3 SYSTEM SETUP
5.3.5 FLEXCURVES™
TIME
OPERATE
TIME
MS
MS
10.5
11.0
11.5
12.0
12.5
13.0
13.5
14.0
14.5
15.0
15.5
16.0
16.5
17.0
17.5
18.0
18.5
19.0
19.5
20.0
5-59
5