12.6.2

Motor current settings

Motor current settings
3RW40 24-...
3RW40 26-...
3RW40 27-...
3RW40 28-...
3RW40 36-...
3RW40 37-...
3RW40 38-...
3RW40 46-...
3RW40 47-...
3RW40 55-...
3RW40 56-...
3RW40 73-...
3RW40 74-...
3RW40 75-...
3RW40 76-...
12.6.3

Motor protection acc. to ATEX

Refer to the information in chapter Motor protection / intrinsic device protection (3RW40 only)
[Page 32].
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01
I
[A]
I
[A]
e
min
12.5
5
25.3
10.3
32.2
17.2
38
23
45
22.5
63
25.5
72
34.5
80
42.5
106
46
134
59
162
87
230
80
280
130
356
131
432
207
12.6 Setting the motor protection function
I
[A]
I
[A]
max
max
CLASS 10
CLASS 15
12.5
11
25.3
23
32.2
30
38
34
45
42
63
50
72
56
80
70
106
84
134
134
162
152
230
210
280
250
356
341
432
402
Commissioning
I
[A]
max
CLASS 20
10
21
27
31
38
46
50
64
77
124
142
200
230
311
372