Selection And Ordering Data For Standard Applications And Normal Starting - Siemens SIRIUS 3RW30 Manual

Soft starters
Hide thumbs Also See for SIRIUS 3RW30:
Table of Contents

Advertisement

Technical data
13.1 3RW30
13.1.2

Selection and ordering data for standard applications and normal starting

Note
The rated motor current is extremely important when selecting a soft starter.
Refer to the information about selecting soft starters in chapter Configuration [Page 73].
Conditions for normal starting:
Max. ramp time 3 s, starting current 300 %, 20 starts / hour, ON time 30 %, standalone
assembly, max. installation altitude 1000 m / 3280 ft, ambient temperature kW 40 °C / 104 °F.
A larger model may need to be selected if other conditions and constraints apply or for a
higher starting frequency. We recommend using the "Win-Soft Starter" selection and
simulation software. For information about the rated currents for ambient temperatures > 40
°C, refer to chapter 3RW30..-.BB.. power electronics [Page 124].
122
SIRIUS 3RW30 / 3RW40
Manual, 01/2010, 535 1995-02 DS01