SITRANS F
Coriolis Flowmeters
MASS 2100 & FC300 (FCT030)
Operating Instructions
These Operating Instructions apply to Siemens
products
06/2017
A5E39789040-AA
Introduction
Safety notes
Description
Installing/mounting
Connecting
Commissioning
Operating MASS 2100/
FC300 with FCT030
Functions
Service and maintenance
Diagnosing and
troubleshooting
Technical data
Dimension drawings
Technical reference
Default settings
Certificates and support
HMI menu structure
1
2
3
4
5
6
7
8
9
10
11
12
A
B
C
D

Advertisement

Table of Contents
loading

Summary of Contents for Siemens MASS 2100

  • Page 1 Introduction Safety notes Description SITRANS F Installing/mounting Coriolis Flowmeters MASS 2100 & FC300 (FCT030) Connecting Commissioning Operating Instructions Operating MASS 2100/ FC300 with FCT030 Functions Service and maintenance Diagnosing and troubleshooting Technical data Dimension drawings Technical reference Default settings These Operating Instructions apply to Siemens...
  • Page 2 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 3: Table Of Contents

    Maximum temperature specifications for Ex use..............24 Description..............................27 Overview..........................27 System configuration......................27 Design............................28 3.3.1 Applications..........................28 3.3.2 Versions..........................29 Features..........................32 Applications..........................34 Approvals..........................34 Theory of operation........................34 Installing/mounting............................37 Basic safety notes........................37 4.1.1 Installation location requirements...................39 4.1.2 Proper mounting........................40 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 4 5.3.2 Signal wiring...........................82 5.3.3 Wiring.............................83 Device nameplates.........................84 5.4.1 Transmitter identification nameplate..................85 5.4.2 Sensor identification nameplate FC300.................89 Commissioning............................91 Basic safety notes........................91 6.1.1 Warnings..........................93 General requirements......................93 Local commissioning......................93 6.3.1 Power-up..........................93 6.3.2 Local display..........................93 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 5 Zero point adjustment......................97 6.3.4.4 Zero Point Adjustment wizard (menu item 1.2)..............99 6.3.4.5 Wizards..........................100 Commissioning with PDM....................110 6.4.1 Operating via SIMATIC PDM....................110 Operating MASS 2100/FC300 with FCT030....................111 Chapter overview Operating....................111 Operating instructions......................111 7.2.1 Local display (HMI)......................111 7.2.1.1 Display view structure......................113 7.2.1.2 Access control........................117...
  • Page 6 How do I update the firmware?....................213 10.4 Diagnosing with PDM......................213 Technical data............................215 11.1 Power...........................215 11.2 Performance.........................215 11.3 Interface..........................218 11.3.1 Modbus interface........................218 11.3.2 HART interface........................218 11.4 Inputs...........................219 11.4.1 Digital input..........................219 11.4.2 Process variables.........................219 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 7 Mounting bracket........................257 Technical reference..........................259 Sensor dimension dependent default settings..............259 A.1.1 Sensor dimension dependent default settings (Inputs/Outputs)..........269 Default settings............................271 Sensor..........................271 Process Values........................273 Standard volume flow......................276 Totalizer..........................284 Inputs and outputs........................291 Dosing..........................377 Date and time........................403 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 8 Menu item 3.9: Audit trail.....................511 D.18 Menu item 3.10: Self test.....................511 D.19 Menu item 3.11: Resets.......................512 D.20 Menu item 3.12: Firmware update..................512 D.21 Menu item 4: Communication....................512 D.22 Menu item 5: Security......................514 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 9 Table of contents Index.................................515 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 10 Table of contents MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 11: Introduction

    Introduction Note This manual applies to the Coriolis flowmeter SITRANS FC MASS 2100 / FC300 with transmitter FCT030, from firmware xx This document are standard delivered in electronic media with the device. Latest version can be downloaded at www.siemens.com (http://support.automation.siemens.com/WW/view/en/ 60666565/134200) These instructions contain all information required to commission and use the device.
  • Page 12: Product Compatibility

    ● descriptions of all functions that can be tors accessed via the local display (HMI) ● guide to setting parameters to obtain optimum operation of the device MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 13: Items Supplied

    Introduction 1.4 Items supplied Items supplied Flowsensors ● MASS 2100 DI 1.0, DI 1.5, DI 2.1 ● Sensorprom or SensorFlash ● Calibration report ● Calibration certificate ● MASS 2100 DI 3, DI 6, DI 15 ● Sensorprom or SensorFlash ● Calibration report ●...
  • Page 14 Note Scope of delivery may vary, depending on version and add-ons. Make sure the scope of delivery and the information on the nameplate correspond to your order and the delivery note. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 15: Checking The Consignment

    In order to protect plants, systems, machines and networks against cyber threats, it is necessary to implement – and continuously maintain – a holistic, state-of-the-art industrial security concept. Siemens’ products and solutions only form one element of such a concept. Customer is responsible to prevent unauthorized access to its plants, systems, machines and networks.
  • Page 16: Transportation And Storage

    The content reflects the technical status at the time of publishing. Siemens reserves the right to make technical changes in the course of further development.
  • Page 17: Safety Notes

    Observe the safety rules, provisions and laws applicable in your country during connection, assembly and operation. These include, for example: ● National Electrical Code (NEC - NFPA 70) (USA) ● Canadian Electrical Code (CEC) (Canada) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 18: Fcc Conformity

    Improper device modifications Danger to personnel, system and environment can result from improper modifications to the device. ● Changes or modifications not expressly approved by Siemens could void the user’s authority to operate the equipment. Note ● This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules.
  • Page 19: Requirements For Special Applications

    If you need additional information not covered by these instructions, contact your local Siemens office or company representative. Note Operation under special ambient conditions...
  • Page 20: Use In Hazardous Areas

    ● Connect the device with type of protection "Intrinsic safety" solely to an intrinsically safe circuit. ● Observe the specifications for the electrical data on the certificate and/or in Technical data (Page 215). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 21: Installation In Hazardous Areas

    FCT030 field mount transmitter (can be installed in Zone 1 for gas and Zone 21 for dust): Certificate: cCSAus 2508628 Ex db eb ia [ia Ga] IIC T6 Gb Ex tb [ia Da] IIIC T85°C Db MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 22 US Certifikate. UL E232147 Sitrans FC300 can be used in zone 0 and Class I Division 1. Class I Div. 1 Grp. A, B, C, D AEx ia IIC T6…T3 IIC Ga MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 23: Special Conditions For Safe Use

    Ex ia IIC T6…T3 Ga Ex ia IIIC T135°C…T180°C Da Canada Certificate. UL E232147 Sitrans FC MASS 2100 can be used in zone 0, 20 and Class I+II+III Division 1. Grp. A,B,C,D, E, F, G Class I+II+III Division 1. Grp. A,B,C,D, E, F, G.
  • Page 24: Maximum Temperature Specifications For Ex Use

    Additionally, the maximum surface temperature of the overall device shall be: ● For dust application, maximum surface temperature = 135°C ● For media temperature above 135°C surface temperature = media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 25 Safety notes 2.4 Use in hazardous areas For MASS 2100 compact with either FCT010 or FCT030 Ambient Maximum Process Temperature per Temperature Class (°C) Temperature Di15 50°C 45°C 40°C 35°C 30°C ● For dust application, maximum surface temperature = 135°C ●...
  • Page 26 Safety notes 2.4 Use in hazardous areas MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 27: Description

    The flowmeter can be used in a number of system configurations: ● as a field mounted transmitter and display supplied only with the necessary auxiliary power ● as part of a complex system environment, for example SIMATIC S7 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 28: Design

    ● Automotive: fuel injection nozzle & pump testing, filling of AC units, engine consumption, paint robots ● Oil & Gas: filling of gas bottles, furnace control, test separators, bore-hole plasticizer dosing, water-cut metering ● Water & Waste Water: dosing of chemicals for water treatment MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 29: Versions

    In the remote configuration, the sensor front end (DSL) is available in an aluminum enclosure with an ingress protection grade of IP67/NEMA 4X. For communication and power supply a 4- MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 30 The transmitter has a modular design with discrete, replaceable electronic modules and connection boards to maintain separation between functions and facilitate field service. All modules are fully traceable and their provenance is included in the transmitter setup. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 31 ⑨ ⑲ Transmitter cassette Terminal housing ⑩ ⑳ Heatsink cover for power supply module Sensor module (compact version) ⑪ ⑳ Cable entry Barrier module (remote version) Figure 3-4 Transmitter exploded view MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 32: Features

    Description 3.4 Features Features ● The device can be used as HART slave in operation on SIEMENS SIMATIC S7/PCS7 or third party automation systems ● Available in compact and remote design ● Full graphical local display (HMI) ● SensorFlash (SD card) for memory backup and documentation storage (certificates etc.) ●...
  • Page 33 – Fraction B % – Sensor frame temperature ● Simulation of all outputs ● Simulation and suppression of alarms ● Comprehensive diagnostics (NAMUR or Siemens standard) for troubleshooting and sensor checking ● Firmware update ● Use in hazardous locations according to specification MASS 2100 &...
  • Page 34: Applications

    The SITRANS F C sensors are energized by an electromagnetic (voice coil) driver circuit which oscillates the pipes at their resonant frequency. Two pickups are placed symmetrically on either side of the driver to provide position signals for digital processing. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 35 The built-in noise filter is configurable and can be used for improving the performance of the flowmeter, in case the installation and application conditions are not ideal. Typical process noise such as gas bubbles (two-phase-flow) can be reduced through the filter functions. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 36 Description 3.7 Theory of operation MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 37: Installing/Mounting

    Refer to the information in Technical data (Page 215). Note Material compatibility Siemens can provide you with support concerning selection of sensor components wetted by process media. However, you are responsible for the selection of components. Siemens accepts no liability for faults or failures resulting from incompatible materials.
  • Page 38 Damage to device by severe external stresses and loads (e.g. thermal expansion or pipe tension). Process media can be released. ● Prevent severe external stresses and loads from acting on the device. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 39: Installation Location Requirements

    ● Install the device so that there is sufficient air supply in the room. ● Observe the maximum permissible ambient temperature. Refer to the information in the section Technical data (Page 215). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 40: Proper Mounting

    ● Avoid long drop lines downstream from the sensor to prevent process media separation causing air / vapor bubbles in the tube (min. back pressure: 0.2 bar). ● Avoid installing the flowmeter immediately upstream of a free discharge in a drop line. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 41: Orientation Of The Sensor

    The sensitivity and the accuracy of the sensor do not change with reverse flow. The indicated flow direction (positive/negative) is configurable. CAUTION Accurate measurement The sensor must always be completely filled with process media in order to measure accurately. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 42 Orienting the sensor The sensor operates in any orientation. The optimal orientation depends on the process fluid and the process conditions. Siemens recommends orienting the sensor in one of the following ways: MASS 2100 DI 1.0, DI 1.5 and DI 2.1...
  • Page 43 4.2 Installation instructions Gas applications Horizontal installation 2 Horizontal installation 1 Vertical installation 2 Vertical installation 1 Liquid applications Horizontal installation, correct Horizontal installation, wrong Vertical installation, correct Vertical installation, wrong MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 44 Installation in a dropline is only possible if a pipeline reduction or orifice with a smaller cross- section can be installed to prevent the sensor from being partially drained during the measurements. ① Orifice Pipe ② Valve Figure 4-3 Installation in drop line MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 45: Mounting The Sensor

    ● Make sure that any valves or pumps upstream of the sensor do not cavitate and do not send vibrations into the sensor. ● Decouple vibrating pipeline from the flow sensor using flexible tube or couplings. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 46 AvoNon-flexible pipes not recommended in vibrating environment Figure 4-6 Flexible pipes recommended in vibrating environment Avoid cross talk If operating more than one flowmeter in one or multiple interconnected pipelines there is a risk of cross talk. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 47: Hydrostatic Testing

    Pressure test of a completed flow system with piping and other components can be done at pressures no higher than 1.5 times the marked MAWP (PS) at 20 °C of the lowest rated system component. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 48: Process Pipe Connection

    After dismantling the sealing ring must be replaced with a new sealing ring. Pressure guards are not supplied with the sensor. Before removing the nipple from the sensor enclosure, please note the following: MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 49 The selection of pressure guard solution is the responsibility of the user, however Siemens recommends the following forms of pressure guard: ● A pressure switch screwed directly or piped into one of the purge ports and connected to an automatic shut-off valve will disable pressurized supply to the meter.
  • Page 50: Transmitter Installation

    The following installation steps must be carried out: 1. Install the mounting bracket on a wall or pipe. 2. Install the transmitter on the mounting bracket. 3. Turn the transmitter and/or turn the local display (optional). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 51: Remote Transmitter Mounting

    Note: U-bolts and other miscellaneous hardware are not supplied with the flowmeter. 2. Tighten nuts (torque: 10 Nm). Note Hygienic applications If the device is wall or pipe-mounted in a hygienic application, always use domed nuts. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 52 2. Loosen lock screw at transmitter pedestal using 5 mm Allen key. 3. Carefully rotate transmitter into desired position. 4. Firmly tighten lock screw (torque: 10 Nm). 5. Replace cap onto lock screw (torque: 10 Nm). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 53: Turning The Local Display

    2. Remove display cover. 3. Use a small screwdriver or blade to loosen the three retaining clips within the transmitter. 4. Carefully pull out local display. 5. Turn display into desired position. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 54: Wall Mount Housing Transmitter

    O-ring on both sides. Wind display cover further by one quarter of a turn to seal on the O-ring. 10.Reinstall and tighten lid lock screw. 4.2.2.3 Wall mount housing transmitter CAUTION Opening lid Care must be taken when opening the lid to avoid the lid falling. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 55 Mounting on wall 1. Prepare holes for the four screws (M6x100 or equivalent). Screw head diameter: max. 13.5 mm; screw shaft diameter: max. 6 mm. 2. Mount transmitter and tighten screws. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 56: Disassembly

    ● If the device contains hazardous media, it must be emptied prior to disassembly. Make sure that no environmentally hazardous media are released. ● Secure the remaining connections so that no damage can result if the process is started unintentionally. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 57: Connecting

    Damage to device through formation of condensation if the temperature difference between transportation or storage and the mounting location exceeds 20 °C (36 °F). ● Before taking the device into operation let the device adapt for several hours in the new environment. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 58 ● Ensure that the device is potentially equalized. Exception: It may be permissible to omit connection of the equipotential bonding for devices with type of protection "Intrinsic safety Ex i". MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 59 ● When connecting intrinsically safe and non‑intrinsically safe circuits ensure that isolation is carried out properly in accordance with local regulations for example IEC 60079-14. ● Ensure that you observe the device approvals applicable in your country. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 60 ● Keep device and cables at a distance from strong electromagnetic fields. ● Take account of the conditions for communication specified in the Technical data (Page 215). ● HART: Use shielded cables to guarantee the full specification according to HART. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 61: Energized Devices

    Observe the type examination certificates or the test certifications applicable in your country if you use transmitters as category 1/2 equipment. WARNING Commissioning Only apply power and commission the device after the device has been properly connected and, if required, closed. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 62: Lack Of Equipotential Bonding

    ● Step 3: Connecting the power supply (Page 75) ● Step 5: Finishing the transmitter connection (Page 81) See also Step 4b: Connecting the inputs and outputs (channels 2 to 4) (Page 78) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 63: Cable Requirements

    Cable specifications ● When installing sensor cable, use cable with at least same degree of protection as the sensors. It is recommended to use cables supplied by Siemens: – blue cables for installation of intrinsically safe circuits in hazardous areas –...
  • Page 64: Connecting The Multiple Plug To The Sensor

    Step 1: Connecting the DSL and the transmitter The following only applies to remote configurations. Wiring DSL (sensor) and transmitter (M12) The DSL is provided with a preformed cable terminated with M12 style stainless steel weather- proof plugs. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 65 4. Push cable through open gland; anchor cable with clamp bar. Ensure that the clamp does not earth the screen. Apply heat-shrink sleeve to make sure the screen is only earthed at the sensor end. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 66 5. Remove cap and ferrule from cable gland and slide onto cable. 6. Push cable through open gland; anchor cable screen and wires with clamp bar. 7. Remove terminal block from DSL cassette. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 67 18.Close and secure DSL lid including lock screw. Turn the lid until you can feel the friction of the O-ring. From this point turn the lid ¼ turn to be tight. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 68: Step 2: Preparing For The Transmitter Connections

    Current output/communication outputs (channel 1) 2. Remove lid lock screw for terminal connections lid. 3. Remove lid for terminal connections. A label showing the configuration is placed at the back of the terminal connections lid. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 69 Configuration label Terminal layout Field mount version Wall box version For configuration of the inputs/outputs, see table in section Step 4b: Connecting the inputs and outputs (channels 2 to 4) (Page 78). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 70: Connecting The Current Hart, Ch1

    2. Push cable through open gland and cable path. 3. Restore ferrule and tighten cap to lightly hold cable in place. 4. Signal cable screen is folded back over outer sheath and grounded beneath cable clamp. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 71 5. Connect wires to terminals using wiring tool, field mount transmitter Active current output Passive current output ⑤ ⑥ ④ ⑤ Functional Earth Functional Earth Active current output Passive current output MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 72 17.7 19.6 11.4 14.9 21.0 1000 14.8 19.2 21.6 2000 17.4 20.1 21.9 5000 19.4 20.4 22.2 10000 20.3 22.3 20000 20.4 22.4 50000 20.4 20.6 22.5 100000 20.6 20.7 22.6 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 73: Connecting The Modbus (Ch1)

    6. Connect wires to terminals using wiring tool, wall mount transmitter. Modbus ④ In + (B) ⑤ In - (A) ⑥ Out + (B) ⑦ Out - (A) 7. Tighten cable gland. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 74: Connecting The Profibus (Ch1)

    5. Connect wires to terminals using wiring tool, field mount transmitter PROFIBUS DP/PA ④ In + (B) ⑤ In - (A) ⑥ Out + (B) ⑦ Out - (A) Functional Earth MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 75: Step 3: Connecting The Power Supply

    2. Remove cap and ferrule from cable gland and slide onto cable. 3. Push cable through open gland and cable path. 4. Restore ferrule and tighten cap to lightly hold cable in place. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 76: Connecting The Power Supply (With Dsl)

    7. Tighten cable gland. 5.2.4.7 Connecting the power supply (with DSL) 1. Open enclosure lid, unscrew power supply terminal protection cover screw, and remove protection cover. 2. Remove blind plug and fit cable gland. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 77 ① ② ③ Protective Earth (PE) AC connection DC connection Power: 100 to 240 V AC, 47 to 63 Hz Power: 19.2 to 28.8 V DC MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 78: Step 4B: Connecting The Inputs And Outputs (Channels 2 To 4)

    IO[3]- (passive) ⑪ ⑫ IO[3]+ (active) IO[3] (common) Functional Earth Functional Earth Termination example for channel 3 6. Tighten cable gland. Note Active or passive current output is preselected at ordering. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 79 Start Dosing Stop Dosing Passive Reset Totalizer 1 ChX- Reset Totalizer 2 ChXC Reset Totalizer 3 Reset All Totalizers ChX+ Start Zero Point Adjust‐ ment Pause/Resume dosing Force Output Freeze Output MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 80 Signal output: < 500 Ω at 14 to 24 VDC (active), 14 to 30 VDC (passive) Relay output: 30 VAC/VDC, 100 mA Passive signal input: 15 to 30 VDC, 2 to 15 mA MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 81: Step 5: Finishing The Transmitter Connection

    6. Reinstate and tighten lid lock screw. 7. Ensure that moisture does not penetrate to inside of electronics housing by creating a drip loop (bend cables downward) immediately before cable glands. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 82: Ready For Commissioning

    ● No explosion hazard exists ● All connection leads are potential free 5.3.2 Signal wiring WARNING Signal wiring Input/output connections to the transmitter are required to be protected by intrinsic safe barriers at all times. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 83: Wiring

    Wiring tool Use the wiring tool for connecting the cables in the compact housing transmitter. The wiring tool is located in the application terminal compartment. Figure 5-6 Wiring tool location MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 84: Device Nameplates

    'Coriolis flowmeter SITRANS FCT010' or 'SITRANS FCT030' and sensors 'MASS2100 or 'FC300'. With remote versions, the transmitter is identified as 'SITRANS FCT030' or 'SITRANS FCT010' or 'SIFLOW' and the sensors as 'SITRANS FC MASS2100' or 'FC300'. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 85: Transmitter Identification Nameplate

    System revision numbers; firmware (FW) and hardware (HW) ⑪ Year of Manufacture Manufacturing year More detailed manufacturing date information is given in the serial number (see sensor identification nameplate above) ⑫ Enclosure IP Degree of protection MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 86 (http://support.automation.siemens.com/WW/view/en/60666565/134200). FCT030 transmitter approval nameplate ① QR code Product-specific QR code ② WEEE symbol, see Disposal (Page 173) ③ C✓ C-tick logo ④ FORCE OIML Custody Transfer evaluation certificate number MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 87 The flowmeter serial number is constructed as follows: PPPYMDDxxxxxx where PPP = Production factory (Siemens Flow Instruments: FDK) Y = Production year (for encryption, see below) M = Production month (for encryption, see below) DD = Production date (for encryption, see below)
  • Page 88 1969, 1989, 2009, 2029 Month (M) Code January February March April June July August September October November December Date (DD) Code Day 1 to 31 01 to 31 (corresponding to the actual date) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 89: Sensor Identification Nameplate Fc300

    Material of the pipe ⑤ Connection Process connector ⑥ Cal. factor Device specific calibration factor ⑦ PT / Year Test pressure and time stamp Figure 5-8 SITRANS FC300 identification nameplate example MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 90 Connecting 5.4 Device nameplates MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 91: Commissioning

    Damage to device if the enclosure is open or not properly closed. The type of protection specified on the nameplate or in Technical data (Page 215) is no longer guaranteed. ● Make sure that the device is securely closed. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 92 ● Check prior to commissioning that the cover, cover locks, and cable inlets are assembled in accordance with the directives. Exception: Devices having the type of protection "Intrinsic safety Ex i" may also be opened in energized state in hazardous areas. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 93: Warnings

    6.3.1 Power-up Power up the device. Devices with local display show a screen for initial startup. 6.3.2 Local display The device is commissioned/operated with the touch keypad on the local display. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 94: Initial Startup

    The first time the device is powered up, you will be prompted to set the language. The device always starts up showing "Language" in English. When the language has been set, you will be prompted to set the date and time. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 95: Commissioning Via Hmi

    In the wizard graphics below, the HMI view numbers are stated to the left. The first view in each wizard (About - view 1) is a description of what settings/actions can be performed using the specific wizard. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 96: Quick Commissioning Wizard (Menu Item 1.1)

    You configure parameters essential for your application by selecting the configuration path and subwizards appropriate for your application. See also Process Values wizard (menu item 1.3) (Page 102) Gas Application wizard (menu item 1.5) (Page 107) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 97: Zero Point Adjustment

    If the pressure can be increased by 1 to 2 bars with stopped flow, this should be applied. 3. Wait 1 to 2 minutes, for the system to settle, and then perform zero adjustment. Waiting longer can change the temperature. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 98 5. At the end of the zero adjustment, the outcome is displayed as an offset and a standard deviation. Note If you get an error message after the zero point adjustment, refer to Zero point adjustment (Page 138). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 99: Zero Point Adjustment Wizard (Menu Item 1.2)

    Ensure that the sensor has the same temperature as the process media. Perform at operating pressure or at least 0.2 barg. Clear Alarms View Text Options/Description Clear alarms "Clear Alarms" and alarm list are only shown if alarms are present. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 100: Wizards

    The purpose of the HMI wizards is to guide you through a quick set-up of various parameters. The following HMI wizards are available: ● Quick Commissioning ● Process Values ● Zero Point Adjustment ● Inputs/Outputs ● Gas Application ● Pulsating Flow ● Dosing Application MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 101 Confirm selection by pressing key again. When you reach the end of the wizard, e.g. "Process Values wizard is now finished", press key to go back to wizard list. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 102 The prioritizing of the process values automatically configures the measurement views on the display. The process value configured as 1st Process Value is set as first display view. View Text Options/Description Prioritize Prioritize the process values MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 103 The Current Output on Channel 1 is a 4 to 20 mA output with Profibus, Profinet, HART, Modbus, X-bus communication. Channel 1 can be used in Functional Safety applications if ordered with SIL option. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 104 Signal output - channels 2 to 4 The signal output can be configured to either current (0/4-20 mA), frequency, pulse, three- stage analog valve dosing control, discrete one or two-valve dosing control or alarm/status. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 105 Commissioning 6.3 Local commissioning MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 106 Status Mode Select the status output functionality Configuration Configure the alarm (only if Alarm Class or Individual alarms is se‐ lected) Output polarity and delay Set the output polarity and delay MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 107 Actual volume flow is difficult to use with low pressure; hence we recommend to use Corrected Volumeflow. View Text Options/Description Default Values Select whether or not to use the default values Configure Configure empty tube detection and limit Corr. Volumeflow Configure settings for corrected volumeflow MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 108 Noise Damping is set to 4 and the Low Flow Cut-Off value will be raised. View Text Options/Description Default Values Select whether or not to use the default values Configure Configure totalizer direction MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 109 The Dosing Application wizard will guide you through configuration of each recipe for dosing control including valve control (discrete/analog) and fault handling. The valve control is done using channels 2, 3 and 4. View Text Options/Description MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 110: Commissioning With Pdm

    For commissioning with SIMATIC PDM, see separate function manual for MODBUS, HART or PROFIBUS. 6.4.1 Operating via SIMATIC PDM SIMATIC PDM is a software package used to commission and maintain process devices. See also www.siemens.com/simatic-pdm (www.siemens.com/simatic-pdm) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 111: Operating Mass 2100/Fc300 With Fct030

    Operating MASS 2100/FC300 with FCT030 Chapter overview Operating A considerable amount of information regarding the operation and status of the flowmeter is available to the user via the local display (HMI ) and SIMATIC PDM. In this chapter you will find information on how to monitor and operate the device using the local display (HMI).
  • Page 112 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Note Recalibration of the keypad When the lid is mounted, all keys are recalibrated (approximately 40 seconds). During recalibration the LED is on and the keys cannot be operated. If one of the keys is pressed for more than 10 seconds, this key is recalibrated (duration less than 10 seconds).
  • Page 113: Display View Structure

    Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions 7.2.1.1 Display view structure There are three view types: ● Operation view The operator view shows up to six operation views (Page 118). The operation views are fully configurable to show different process values in different operation view types.
  • Page 114 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Table 7-3 Alarm view level 2 Function Enter alarm view level 1 Select the item above in the list; keep pressing the key to accelerate scrolling up the selection list Select the item below in the list; keep pressing the key to accelerate scrolling down the...
  • Page 115 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Function Go to the next menu in the operation view Enter the navigation view The following graphic shows an example of how to navigate between measurement views and alarm views with measurement views 1, 3, and 4 as well as alarm view 5 enabled.
  • Page 116 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Navigating the navigation view Browse the navigation view and menu items using the control buttons as follows: Table 7-8 Navigation view Function Enter the next higher level of the navigation view (for example from level 2 to level 1).
  • Page 117: Access Control

    The exact structure of the operating menu is explained in the HMI menu structure (Page 481). Note Lost PIN code If the PIN code is lost, provide Siemens customer support with the transmitter serial number (see nameplate). Siemens customer support will provide a code to be entered in Reset PINs (menu item 5.1.3).
  • Page 118: Operation View

    Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Auto Log Off function With the "Auto Log Off" function enabled (default), you will be prompted to enter the password if no keys have been pressed for ten minutes before operating the display again. With the "Auto Log Off"...
  • Page 119: Measurement Views

    Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions ① Long TAG Describes the measurement point and is shown in all operation views. Can be changed via the menu "Long TAG" (3.1.1). ② View number Shows the operation view number. The number refers to the view num‐...
  • Page 120 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Three values ① First process value The user-defined process value to be displayed is configured in menu "View" (1-6) located at "Setup" → "Display" ② Lower Limit Alarm The lower limit of the bar graph is defined by the lower alarm limit of the selected process value.
  • Page 121 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Note Bargraph The bargraph limits are defined as the lower and upper alarm values. One value and graph ① Process Value ② Graph ③ Instruction Press to freeze/unfreeze display Six values ①...
  • Page 122: Operating Views

    Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions 7.2.1.5 Operating views Operating Views Totalizer (level 1) ① Process value ② Graph ③ Instruction Press to enter the operation view. Totalizer (level 2) ① Process value ② Graph ③ Control Dosing (level 1) ①...
  • Page 123: Alarm Views

    Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Dosing (level 2) ① Dosed amount Actual dosed amount ② Amount Dosing progress ③ Count Number of dosings ④ Recipe Name of the selected recipe ⑤ Status Dosing status ⑥ Control Dosing control 7.2.1.6...
  • Page 124 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Alarm List (level 2) ① List of alarms List of all active alarms in device. Each Alarm can be selected for detailed information. ② Alarm icon Shows the alarm class, see Device status symbols (Page 185).
  • Page 125: Diagnostic Views

    Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Alarm acknowledgement There are two ways to have the alarms removed from the alarm list. ● Manual: The alarm remains in the alarm list until the alarm is manually acknowledged (ack.). The time of the acknowledgement is shown in the history log.
  • Page 126: Fixed Display Texts

    Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions 7.2.1.8 Fixed display texts Fixed display texts The following table lists the fixed display texts for the process value names available on the operation view. Table 7-11 Process values Fixed display text...
  • Page 127: Navigation View

    The navigation views present the menu structure of the device. All menu items are uniquely identified with menu item number. Level 1 of the navigation view (entered from the operation view) is standardized for all Siemens Process Instrumentation devices and covers the following groups: 1.
  • Page 128 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions 5. Security (menu): Contains parameters which describe all security settings of the device. 6. Language (parameter): Parameter for changing the language of the HMI. Regardless of the language setting, the term for this parameter is always the English term (Language).
  • Page 129: Parameter View

    Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Parameter item In navigation view parameters are shown without an arrow in the most right position except when the parameter is selected. When selected, the parameter is expanded into two lines; the second line shows the value of the parameter, a lock icon ( ) (only for read access level of the parameter), and an arrow in most right position.
  • Page 130 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Numeric parameters edit view Numeric parameters in edit view are displayed as shown here. ① Parameter name ② Parameter item number ③ Maximum value ④ Escape without saving (frame around ESC is only shown when cursor is in left-most position) ⑤...
  • Page 131 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions In order to change the resolution of the process value shown in the operation view (for example massflow), change the resolution of one configuration parameter for this process value (for example "Low Flow Cut-off" (menu item 2.2.1.2)). Any changes in resolution will change the resolution of all configuration parameters for this process value as well.
  • Page 132 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Parameter list edit view Lists of parameters in edit view are displayed as shown here. ① Parameter list ② Parameter name ③ Parameter item number ④ Help text describing the parameter function. The help text appears if no key is pressed for three seconds.
  • Page 133 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions Multiselection view It is possible to select/deselect multiple alarms to be suppressed. ① Parameter name ② Alarm list ③ Save settings (select and press right key to save settings) to scroll through the alarms. Use to select/deselect the alarm.
  • Page 134 Operating MASS 2100/FC300 with FCT030 7.2 Operating instructions MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 135: Functions

    ● Alarm Hysteresis The system reports a process alarm when the process value exceeds the Upper Limit Alarm or the Lower Limit Alarm. Likewise, the system reports a process warning when the process MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 136 - Fail Safe Mode is configure to react on a failure - Process Alarm occurs on a process value selected on the output The alarm behavior is described in detail below. Detail alarm behavior is described in Digital output (Page 229). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 137 Fraction calculations are naturally performed in the ratio provided, or in mass ratio when using the built-in tables. Volume or mass ratios derived from the fraction table are calculated through the composite media density. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 138: Zero Point Adjustment

    Zero Point Offset Value Average of N flow values is an instantaneous flow value sampled in ∑ the time domain N = Number of samples during zero point ad‐ ≡ justment MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 139 If the new zero point offset value is valid, it is automatically stored as the new zero point for the sensor. It remains stored in the case of a power failure. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 140: Low Flow Cut-Off

    Risk of unintentionally forcing flow values to zero, if the difference between the empty tube limit density value and the density of the process media is not sufficient. ● Ensure sufficient difference between the empty tube limit density value and the process media density MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 141: Process Noise Damping

    ● Cam pump (5: high) The default value is "Duplex pump". The damping affects all functions and outputs of the sensor. Figure 8-2 Centrifugal pump (1: low) Figure 8-3 Triplex pump (2) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 142 Duplex pump (3; default setting) Figure 8-5 Simplex pump (4) Figure 8-6 Cam pump (5: high) Note Increased reaction time The reaction time of the sensor increases when the process noise is damped. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 143: Inputs And Outputs

    Signal input ● Dosing control ● Totalizer reset ● Remote zero adjust ● Force or freeze output(s) Current input 8.6.1 Current output All four channels can be configured as current output. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 144 The accuracy specified for the analog output signal applies only within the range 4 to 20 mA. Lower limit (4 mA) and upper limit (20 mA) can be assigned to any specific flow values. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 145 In the alarms lists inSensor diagnostic events (Page 189) it is listed which alarms bring the output to fail safe current. Output scaling configuration Below are four examples describing configuration possibilities for a current output. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 146 ● Current Mode = 4-20 mA (maximum 25 mA) ● Upper Scaling = 100 kg/h ● Lower Scaling = 400 kg/h ● Fail Safe Mode = Maximum current ● Low-Flow Cut-Off = 25 kg/h MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 147 ● Current Mode = 4-20 mA NAMUR ● Upper Scaling = 400 kg/h ● Lower Scaling = -100 kg/h ● Fail Safe Mode = Maximum current ● Low-Flow Cut-Off = 25 kg/h MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 148 ● Current Mode = 4-20 mA US ● Upper Scaling = 400 kg/h ● Lower Scaling = -100 kg/h ● Fail Safe Mode = Minimum current ● Low-Flow Cut-Off = 25 kg/h MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 149: Pulse Output

    The pulse output function supplies pulses equivalent to a configured amount of accumulated volume or mass. The pulse width is configured and the pulse repetition is proportional to the selected flow rate. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 150: Frequency Output

    This example shows how to calculate the output frequency for any measured flowrate: Frequency output configuration: ● Operation Mode = Frequency Output (Channel 2 to 4) ● Process Value = Massflow MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 151: Redundancy Mode (Frequency)

    Channel 2 configured as positive direction and channel 3 set to redundancy mode 90° Figure 8-8 Positive flow - channel 3 leads by 90° Figure 8-9 Negative flow - channel 3 lags by 90° MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 152 Channel 2 configured as positive direction and channel 3 set to redundancy mode 90° Figure 8-12 Positive flow - channel 3 leads by 90° Figure 8-13 Negative flow - channel 3 lags by 90° MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 153: Digital Output

    Alarm class The alarm class options depend on the Alarm Mode setting, either NAMUR or Standard (Siemens Standard), selected in menu item 3.2.1. Both NAMUR and Siemens Standard alarms and their messages are described in more detail in Sensor diagnostic events (Page 189).
  • Page 154: Totalizers

    In case of failure in the system, the totalizer fail safe mode can be set to: - Hold (default): the totalizer holds the last value before the failure occurred - Run: the totalizer continues counting the actual measured value MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 155: Dosing

    ● dosing of mass flow, volume flow, standard volume flow or fraction flow (mass or volume) ● five independently configurable recipes ● flexible discrete or analog valve control ● fault handling – time and amount monitoring MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 156: Dosing Control Configuration

    Use one Signal output to control the Control valve. Assign the Operating Mode to Current Output. A Signal Input can be assigned to start the dosing. Process Values The following process values can be used for dosing control: ● Mass flow ● Volume flow MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 157: Valve Control Configuration

    2.4.6.27 "Status Mode" Primary Valve Dosing Relay output 2.4.4.1 "Status Mode" Primary Valve Dosing 2.4.7.1 "Status Mode" Primary Valve Dosing Two on/off valves Configuration of two valves (primary and secondary valves) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 158 2.4.6.1 "Operating Mode" Current Output 2.4.6.2 "Process Value" Control valve Note If the output channels including current output are configured for valve control, they cannot report alarm status or fault levels. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 159 - 2.5.5.6.2 Stage 1 Primary Open = 0 % - 2.5.5.6.3 Stage 1 Primary Close = 66 % - 2.5.5.6.4 Stage 2 Secondary Open = 33 % - 2.5.5.6.5 Stage 2 Secondary Close = 100 % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 160 - 2.5.5.6.2 Stage 1 Primary Open = 33 % - 2.5.5.6.3 Stage 1 Primary Close = 66 % - 2.5.5.6.4 Stage 2 Secondary Open = 0 % - 2.5.5.6.5 Stage 2 Secondary Close = 100 % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 161 The quantity or percent of amount at which the valve will transition Amount from partial to full flow Partially Closed 100.00 % of The quantity or percent of amount at which the valve will transition Amount from full flow to partial flow MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 162: Dosing Operation

    Dosing compensation In static applications the flowrate is constant. Thus, the dosing compensation, if required, is fixed. Use the fixed compensation by entering the amount in menu item 2.5.5.5.2 (Fixed Compensation). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 163: Fault Handling

    Each audit trail list can be cleared by the user. See also "Diagnostic log" (menu item 3.2.2) 8.10 Diagnostic log All unacknowledged diagnostic information are listed in the Diagnostic log menu item 3.2.2 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 164: Custom Unit

    Further is contains parameter backup files, firmware logs, alarm history log, parameter change log and data logging of process values and parameters. The Siemens SensorFlash memory unit offers a permanent database with backup of all parameter settings. The SensorFlash supports copy and transfer of user settings from one flowmeter to another to simplify commissioning.
  • Page 165: Datalogging On Sensorflash

    Inputs/outputs simulation HW configura‐ Channel 1 Channel 2 Channel 3 Channel 4 Simulation value tion Current output ● 4 to 20 mA Relay output ● ● 0 (low) or 1 (high) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 166: Maintenance

    Alarm simulation It is possible to simulate either specific alarms (ID numbers) or alarm classes. The alarm classes are either Siemens or NAMUR depending on the configuration of Alarm Mode, menu item 2.8.11. Any simulated alarms will be time-stamped 1900-01-01 00:00 if the alarms have not previously appeared as real alarms.
  • Page 167: Service And Maintenance

    ● Reliability of power supply, lightning protection, and grounds WARNING Impermissible repair of explosion protected devices Risk of explosion in hazardous areas ● Repair must be carried out by Siemens authorized personnel only. WARNING Dust layers above 5 mm Risk of explosion in hazardous areas.
  • Page 168: Recalibration

    ● Ensure that the atmosphere is explosion-free (hot work permit). Recalibration Siemens A/S, Flow Instruments offers to recalibrate the sensor at our works in Denmark. The following calibration types are offered as standard according to configuration (standard, density, °Brix/°Plato, fraction): ●...
  • Page 169: Cleaning

    ● Only use original accessories or original spare parts. ● Observe all relevant installation and safety instructions described in the instructions for the device or enclosed with the accessory or spare part. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 170 ● Before you open the enclosure or remove enclosure parts, de-energize the device. ● If maintenance measures in an energized state are necessary, observe the particular precautionary measures. Have maintenance work carried out by qualified personnel. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 171: Service Information

    ● Pickup 1 Amplitude ● Pickup 2 Amplitude ● Sensor Frequency ● Process Media Temperature ● Zero Point Adjustment Auto/Manual ● Zero Point Offset Value ● Manual Zero Point ● Zero Point Standard Deviation MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 172: Replacing The Device

    Check the item after it has been cleaned. Any devices/replacement parts returned without a decontamination declaration will be cleaned at your expense before further processing. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 173: Disposal

    Ensure that your ordering data is not outdated. The latest ordering data is always available on the Internet: Catalog process instrumentation (http://www.siemens.com/ processinstrumentation/catalogs) 9.8.2 Ex approved products WARNING Repair of Ex-approved products It is the customer's responsibility that repair of Ex-approved products fulfill national requirements. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 174: Replaceable Components

    For DSL, observe hazardous area ac‐ cess protocols! SITRANS FCT010/DSL A5E..Blind lid small (∅85 mm) Observe hazard‐ ous area access protocol SITRANS FCT010/DSL housing A5E03549313 Cable entry metric Painted aluminium MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 175 Mounting bracket kit for wall and pipe mounting SITRANS FCS400 A5E03906095 Remote version M12 option for DSL housing SITRANS FCT030 A5E03906104 Remote version Socket, M12 pedestal SITRANS FCT030 A5E03906130 Remote version Terminal house 1/2" NPT pedestal MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 176 For analog cable connection be‐ tween MASS2100/FC300 sensors and FCT010/030 transmitters. 5 x 2 x Ø0.34mm screened and twisted in pairs. Blue PVC insulation and sleeve. With two M20 connectors, female/ female. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 177 Service and maintenance 9.8 Spare parts/Accessories Component Order number Photo Hot swappable -20….+105⁰C (-4…..+221⁰F) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 178 I/O Cassette for firmware 4.0 A5E38006558 Ch2: Curent/Frequency/Pulse Ch3: Curent/Frequency/Pulse Ch4: None Non-Ex I/O Cassette for firmware 4.0 A5E38006598 Ch2: Curent/Frequency/Pulse Ch3: Curent/Frequency/Pulse Ch4: Curent/Frequency/Pulse Non-Ex I/O Cassette for firmware 4.0 A5E38006896 Ch2: Curent/Frequency/Pulse MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 179 Ch3: Relay Ch4: None Ex - Active I/O Cassette for firmware 4.0 A5E38012039 Ch2: Curent/Frequency/Pulse Ch3: None Ch4: None Ex - Passive I/O Cassette for firmware 4.0 A5E38012056 Ch2: Curent/Frequency/Pulse Ch3: Curent/Frequency/Pulse MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 180 Display and keypad assembly A5E39844261 For wall mount enclosure, Neutral version Power supply for wall mount A5E38263021 100 - 240 V AC, 47 - 63 Hz, 19,2 - 28,8 V DC MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 181 O-rings Metal Kit: PSU cover back pane for A5E38415145 Wall mount enclosure Power input cover plate for wall A5E38415205 mount enclosure 1. Components may be replaced while power is on MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 182: Field Enclosure Spareparts

    3,6,15 with MASS6000 compact to DSL/FCT030 Compact adapter for DSL/ or A5E42846760 FCT030 For upgrade from MASS2100 DI 3,6,15 with MASS6000 compact to DSL/FCT030 Non-Ex Wall bracket for FCT030 A5E42404426 For M20 analog cable connection MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 183 A5E41526318 For systems without DSL (HW version 3, FW 4.0) Sensor cassette (Remote). For systems with DSL (HW version 3, FW 4.0) 1. Components may be replaced while power is on MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 184 Service and maintenance 9.8 Spare parts/Accessories MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 185: Diagnosing And Troubleshooting

    Diagnostic log. The alarm history log can be reset in Reset log. Characteristics of messages The device provides two types of alarm formats, Siemens standard alarm classes and NAMUR status signals, selected in Status icons.
  • Page 186 ● Write access disabled ● Indicate read only parameters Data exchange ● Device is communicating Custody transfer enabled Memory card Capacity is 25 % used Memory card Capacity is 50 % used MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 187 Output signal invalid due to a param‐ Check device hardware tion error eter setting, an interconnection error configuration or parameter or a configuration error in HW. settings via HMI or engi‐ neering system. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 188: Fault Codes And Corrective Actions

    10.2 Fault codes and corrective actions Alarms and system messages support both Siemens standard alarm classes and NAMUR status signals. In the following tables the alarm IDs (identification numbers) are listed along with possible causes and directions for corrective action.
  • Page 189: Sensor Diagnostic Events

    Siemens representative Temperature measurement fault Turn off the power, wait 5 seconds and turn on the power again. If the failure continues then contact your local Siemens representative MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 190 Siemens representative Invalid calibration data Contact your local Siemens representative for recalibration Invalid compensation data Contact your local Siemens representative Malfunction in Pickup Amplitude Contact your local Siemens representative MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 191 10.2 Fault codes and corrective actions Diagnostic Action Comments Icons Malfunction in Pickup Amplitude Contact your local Siemens representative Malfunction in Pickup Amplitude Contact your local Siemens representative Malfunction in sensor driver Contact your local Siemens representative Malfunction in sensor driver...
  • Page 192 Comments Icons Fluid temp. below limit Increase the fluid temperature. If the failure con‐ tinues then contact your local Siemens repre‐ sentative Fluid temp. above limit Reduce the fluid temperature. If the failure con‐ tinues then contact your local Siemens repre‐...
  • Page 193 Contact your local Siemens representative Internal error in sensor Contact your local Siemens representative Unstable measurement condi‐ Check if air is present in the liquid and that the tion flowmeter is operated within its specifications. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 194: Transmitter Diagnostic Events

    Adjust parameter 'Lower alarm limit' Volume flow Value above alarm limit. Check process condi‐ tions or align limit to normal operation. Adjust parameter 'Upper alarm limit' MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 195 Adjust parameter 'Upper alarm limit' Medium temperature Value above warning limit. Check process con‐ ditions or align limit to normal operation. Adjust parameter 'Upper warning limit' MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 196 Value above warning limit. Check process con‐ ditions. Align Upper warning limit to normal process conditions Fraction B % Value below warning limit. Check process con‐ ditions. Align Lower warning limit to normal process conditions. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 197 Value below warning limit. Check process con‐ ditions. Align Lower warning limit to normal process conditions. Fraction B flow Value below alarm limit. Check process condi‐ tions. Align Lower alarm limit to normal process conditions. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 198 Adjust parameter 'Lower alarm limit' Totalizer 1 Value above alarm limit. Check process condi‐ tions or align limit to normal operation. Adjust parameter 'Upper alarm limit' MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 199 Adjust parameter 'Upper alarm limit' Totalizer 3 Value above warning limit. Check process con‐ ditions or align limit to normal operation. Adjust parameter 'Upper warning limit' MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 200 Sensor signal disrupted Turn off the power. Unplug and reconnect the sensor cable. Restore power. If the error still exists, contact your local Siemens representa‐ tive. SensorFlash Backup disabled. Another SensorFlash was in‐ serted. To acknowlege please copy the config‐...
  • Page 201 Functional safety Device detected an event in safe operation. Ac‐ knowledge the safety event in menu Functional Safety and repeat the safety commissioning. If the error still exists, contact your local Siemens representative. Cable break. Check current output cable con‐ nection Internal error Internal error in transmitter.
  • Page 202 FW invalid. A component does not have the ex‐ pected FW version. Start a product firmware update to update the component version or re‐ place the component. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 203 External failure. Connected sensor or output to If Operation mode is config‐ input channel is out of operation range. Please ured to Current input check connected sensor or output source. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 204 Dosing quantity overrun. Check installation. If ok, decrease 'Overrun Value' Dosing Invalid process value during dosing. Check in‐ stallation for abnormal operating conditions. If the error still exists, contact your local Siemens representative. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 205 Current output Adjust channel 3 parameter 'Upper range value' Cable break. Check channel 3 current output If Operation mode is config‐ cable connection ured to Current output MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 206 4 parameter 'Upper range value' Pulse overflow. Pulse output insufficient pulse If Operation mode is config‐ separation. Reduce pulses per amount, or re‐ ured to Pulse output duce pulse width, or increase amount MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 207 If Operation mode is config‐ cable connection. In passive mode check pow‐ ured to Current output er supply. Modbus Invalid register mapping. Source register allo‐ cated in duplicate. Check register mapping. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 208: Operation Troubleshooting

    3. Remove the SensorFlash from the destination device and insert the original SensorFlash. The device synchronizes the parameters to the SensorFlash and the alarm is cleared. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 209: Troubleshooting Sensor-Related Problems

    ● Gas application Ensure that the gas pressure/temperature conditions contain sufficient superheat to prevent dewing or precipitation. If the gas contains vapor or droplets then these may precipitate, causing instability. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 210 20 °C ± 2 °C (68 °F ± 3.6 °F) medium Temperature, 20 °C ± 2 °C (68 °F ± 3.6 °F) ambient Liquid pressure 2 ± 1 bar Density 0.997 g/cm3 Brix 40 °Brix MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 211 Vibrations in the pipe system are normally generated by pumps. Typically, cross talk is generated by two sensors of identical size and positioned in close proximity in the same pipe, or installed on the same rail or frame. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 212 If the solid particles in a liquid have a density higher than that of the liquid, they can precipitate inside the sensor and cause instability which leads to a measurement error. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 213: How Do I Update The Firmware

    Requirements The following procedure must be completed before diagnosing: ● Installation of PDM and PDM device driver ● Connection of communications or digital communications interface Refer to "Commissioning with PDM". MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 214 Diagnosing and troubleshooting 10.4 Diagnosing with PDM MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 215: Technical Data

    Technical data Note Device specifications Siemens makes every attempt to ensure the accuracy of these specifications but reserves the right to change them at any time. 11.1 Power Table 11-1 Power supply Description Specification Supply voltage ● 100 to 240 V AC, 47 to 63 Hz 30 VA ●...
  • Page 216 (DI 3.5) Media temperature ±0.5 ±0.5 ±0.5 ±0.5 ±0.5 ±0.5 ±0.5 ±0.5 ±0.5 accuracy [°C] Media temperature ±0.25 ±0.25 ±0.25 ±0.25 ±0.25 ±0.25 ±0.25 ±0.25 ±0.25 repeatability [°C] Brix error [°Brix] MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 217 Hastelloy C22 sen‐ (5294 (5076 (5946 (2900 sors [bar (psi)] PSI at 68 PSI at 68 (14503 PSI at 68 PSI at 68 °F) °F) psi) 20-180 °F °F) °C (68 °F-356 °F) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 218: Interface

    Table 11-9 HART communication Description Specification HART revision PROFIBUS interface Table 11-10 Profibus DP/PA Description Specification Profile version V4.0 - compatible with version 3 Default transmission rate Automatic baud rate detection MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 219: Inputs

    – When this function is activated, it will pause the dosing. When it is deactivated, the dosing will continue ● Stop dosing – Sets the digital output to "Off" and resets the dosing counter MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 220: Outputs

    0 to 24 V DC, 87 mA, short-circuit-protected Passive 3 to 30 V DC, 100 mA, short-circuit-protected Functions ● Pulse ● Frequency ● Alarm class / NAMUR status ● Individual alarms MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 221 Description Channels 2 to 4 Signal range 0/4 to 20 mA Resolution 0.4 μA Load ● Ex i: <470 Ω ● Non-Ex: <770 Ω Time constant (adjustable) 0.0 to 100 s MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 222: Current Output

    The accuracy specified for the analog output signal applies only within the range 4 to 20 mA. Lower limit (4 mA) and upper limit (20 mA) can be assigned to any specific flow values. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 223 In the alarms lists inFault codes and corrective actions (Page 188) it is listed which alarms bring the output to fail safe current. Output scaling configuration Below are four examples describing configuration possibilities for a current output. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 224 ● Current Mode = 4-20 mA (maximum 25 mA) ● Upper Scaling = 100 kg/h ● Lower Scaling = 400 kg/h ● Fail Safe Mode = Maximum current ● Low-Flow Cut-Off = 25 kg/h MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 225 ● Current Mode = 4-20 mA NAMUR ● Upper Scaling = 400 kg/h ● Lower Scaling = -100 kg/h ● Fail Safe Mode = Maximum current ● Low-Flow Cut-Off = 25 kg/h MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 226 ● Current Mode = 4-20 mA US ● Upper Scaling = 400 kg/h ● Lower Scaling = -100 kg/h ● Fail Safe Mode = Minimum current ● Low-Flow Cut-Off = 25 kg/h MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 227: Pulse Output

    The pulse output function supplies pulses equivalent to a configured amount of accumulated volume or mass. The pulse width is configured and the pulse repetition is proportional to the selected flow rate. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 228: Frequency Output

    This example shows how to calculate the output frequency for any measured flowrate: Frequency output configuration: ● Operation Mode = Frequency Output (Channel 2 to 4) ● Process Value = Massflow MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 229: Digital Output

    The alarm class options depend on the Alarm Mode setting, either NAMUR or Standard (Siemens Standard), selected in menu item 3.2.1. Both NAMUR and Siemens Standard alarms and their messages are described in more detail in Fault codes and corrective actions (Page 188).
  • Page 230: Construction

    Negative flow - channel 3 lags by 180° 11.6 Construction Table 11-17 Designated use Description Specification Measurement of process medium ● Fluid Group 1 (suitable for dangerous fluids) ● Aggregate state: Paste/light slurry, liquid and gas MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 231 Transmitter pedestal lock screw Compact version: Remote version: Pedestal lock screw cap Cable gland to housing (Siemens supplied, metric) Note NPT glands When using NPT glands, the user must take care to use the supplied NPT thread adaptors. MASS 2100 & FC300 (FCT030)
  • Page 232 Self-draining design Yes, when mounted in correct position (sensor type specific direction) DN4 self-draining not possible *: Pressure ratings depend on sensor material **: Pressure ratings depend on process connection dimension MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 233: Local Display (Hmi)

    Min. bending radius allowed Single 5 X ø Description Specification Number of conductors 10 (5x2) Square area [mm 0.35 Screen [m] Twisted and screened in pairs Outside color Blue External diameter [mm] Maximum length MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 234: Operating Conditions

    (Humidity max. 90 %) Transmitter without display -40 to +70 [-40 to +158] Transmitter with display -40 to +70 [-40 to +158] Climate class DIN 60721-3-4 Altitude Up to 2000 m (6560 ft) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 235: Process

    The pressure drop is dimension-dependent and influenced by process media viscosity and density. Sensors with undersized process connections experience higher pressure drop due to reduction in inlet/outlet dimensions. Note Pressure drop information Pressure drop information is available on request. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 236: Pressure Drop

    MASS2100 DI1.5 ∆ [bar] 0,01 Mass flow [kg/ht] Figure 11-6 MASS 2100 DI 1.5 / 1/16", pressure drop for density = 1000 kg/m 11.8.3 FC300 DN4 FC300 DN4, pressure drop for density = 1000 kg/m MASS 2100 & FC300 (FCT030)
  • Page 237: Mass2100 Di3, Di6 & Di15

    Technical data 11.8 Process 11.8.4 MASS2100 Di3, Di6 & Di15 Figure 11-7 MASS 2100 DI3 Viscosity [cSt] Figure 11-8 MASS 2100 DI 6 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 238: Bus Communication

    Number of device variables Number of process values, both measured and derived Physical layers supported Frequency Shift Keyed Loop-powered 4-wire device Note Always refer to nameplates on the device for device-specific approvals. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 239: Approvals

    Certifikate. UL E232147 Sitrans FC300 can be used in zone 0 and Class I Division 1. Class I Div. 1 Grp. A, B, C, DA AEx ia IIC T6…T3 IIC Ga MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 240: Sensorflash

    Description Specification MASS 2100 ATEX Certificate : DEMKO 03 ATEX 135252X Sitrans FC MASS 2100 can be used in zone 0, 20 Ex ia IIC T6…T3 Ga Ex ia IIIC T135°C…T180°C Da IECEx Certificate : IECEx ULD 17.0029 Sitrans FC MASS 2100 can be used in zone 0, 20 Ex ia IIC T6…T3 Ga...
  • Page 241: Ped

    This must be within the limits defined for the equipment. Division of media (liquid/gaseous) into the fluid groups Fluids are divided according to Article 9 into the following fluid groups: MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 242 R phrases: for example: 2, 3 (1, 4, 5, 6, 9, 16, 18, R phrases: for example: 26, 27, 28, 39 (32) 19, 44) Extremely flammable Toxic R phrases: for example: 12 (17) R phrases: for example: 23, 24, 25 (29, 31) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 243 The flowmeters are subjected to the conformity assessment procedure - Module H. Flowmeters according to Article 4 Paragraph 3 are designed and manufactured in accordance with sound engineering practice in Denmark. PED conformity reference is not affixed to the CE mark. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 244 ● Exception: liquids at temperatures > 350 °C belonging to Category II must be included in Category III. PS [bar] 1000 Article 3 Paragraph 3 PS = 0,5 2000 7000 1000 10000 Figure 11-11 Diagram 7 ● Liquids of fluid group 1 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 245: Pressure - Temperature Ratings

    Design rules for flange connections in both the EN1092-1 and ASME B16.5 standards dictate pressure derating with increasing temperature. The charts below show the effect of process medium temperature on the pressure ratings for the flanges within the product program. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 246: Pressure - Temperature Ratings (Stainless Steel Sensors)

    40.0 40.0 37.9 34.5 32.9 63.0 63.0 63.0 59.7 51.8 51.8 100.0 100.0 100.0 94.8 86.2 82.1 Table 11-31 ISO228-G and ASME B1.20.1 NPT [bar] Temperature TS (°C) -40 to +38 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 247 25 / 50-100 40 / 10-40 Note Test pressure Maximum allowable test pressure (MATP) for the flowmeter and process connection is 1.5 times the nominal pressure up to 150 bar (2176 psi). MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 248: Pressure - Temperature Ratings (Hastelloy Sensors)

    14.6 51.7 51.7 51.7 51.5 50.3 59.1 103.4 103.4 103.4 103.0 100.3 98.1 Table 11-39 DIN 11851 [bar] PN (bar) / DN Temperature TS (°C) 25 / 50-100 40 / 10-40 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 249: Dimension Drawings

    152 (5.98) 4 (0.16) 120 (4.72) NV21 G 9/16” Ø 9 (0.35) Ø18,8 (0.74) Ø24 (0.94) G 9/16” 18-UNF 100 (3.94) Figure 12-1 MASS2100 DI 1.0 only available with 9/16” 18-UNF connectors MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 250 Ø18,8 (0.74) Ø24 (0.94) Ø24 (0.94) 1/4” NPT G 1/4” ANSI/ASME ISO 228/1 B1.20.1-1983 100 (3.94) Figure 12-2 MASS 2100 DI 1.5 and DI 2.1, standard version, Dimensions in mm (inch) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 251 Ø 9 (0.35) Ø18,8 (0.74) Ø18,8 (0.74) Ø24 (0.94) Ø24 (0.94) 1/4” NPT G 1/4” ANSI/ASME ISO 228/1 B1.20.1-1983 100 (3.94) Figure 12-3 MASS 2100 DI 1.5, High-temperature version, Dimensions in mm (inch) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 252 Dimension drawings 12.1 Sensor dimensions FC300 DN4 Standard version FC300 DN4 HP only available with 9/16” 18UNF connectors Housing is not rated for pressure containment MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 253 Dimension drawings 12.1 Sensor dimensions FC300 DN4 high temperature version Housing is not rated for pressure containment MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 254: Mass2100 Di3, Di6 & Di15

    (15.75) (11.02) (2.97) (2.36) (0.84) (4.09) ISO 228/1 - G¼ (¼") Pipe PN 100 75.5 21.3 thread AN‐ (15.75) (11.02) (2.97) (2.36) (0.84) (4.09) SI/ASME B 1.20.1 - ¼" NPT (¼") MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 255 PN 40 75.5 21.3 connec‐ (23.07) (17.48) (2.97) (1.73) (0.79) (0.84) (5.08) tion DIN 11851 (DN15) Clamp PN 16 75.5 21.3 ISO 2852 (24.57) (17.48) (2.97) (1.73) (0.79) (0.84) (5.08) (25 mm) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 256: Transmitter Dimensions

    349 (13.7) 6 (¼) 62 (2.44) 72 (2.83) 277 (10.9) 349 (13.7) 15 (½) 75.5 (2.9) 86.5 (3.4) 287 (11.2) 373.5 (14.7) Remote version 307 (12) 200 (7.8) Dimensions in mm MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 257: Mounting Bracket

    Dimension drawings 12.4 Mounting bracket Weight: 4.8 kg (10.6 lbs) 12.4 Mounting bracket For compact housing Dimensions in mm Weight: 4.8 kg (10.6 lbs) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 258 Dimension drawings 12.4 Mounting bracket MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 259: Technical Reference

    DN 25 -6,136 DN 50 -24,54 DN 80 -62,83 DN 100 -180,56 DN 150 -298,61 MASS2100 -0,010 -0,022 -0,043 -0,088 FC300 DN4 HP -0,039 FC300 DN4 C22 -0,088 FC300 DN4 316 -0,120 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 260 2820 DN 150 1,269 4570 MASS2100 0,0000272 0,0980 0,0000542 0,195 0,000117 0,42 0,000250 0,90 FC300 DN4 HP 0,0000972 0,35 FC300 DN4 C22 0,000264 0,95 FC300 DN4 316 0,000389 MASS2100 0,00139 0,0106 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 261 DN 50 -0,250 DN 80 -0,641 DN 100 DN 150 -2,3 MASS2100 -0,0002 -0,00045 -0,00088 -0,0018 FC300 DN4 HP -0,00080 FC300 DN4 C22 -0,0018 FC300 DN4 316 -0,0025 MASS2100 -0,0072 -0,0451 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 262 0,001269444 4,57 MASS2100 2,72222E-08 0,000098 5,41667E-08 0,000195 1,16667E-07 0,00042 0,00000025 0,0009 FC300 DN4 HP 9,72222E-08 0,00035 FC300 DN4 C22 2,63889E-07 0,00095 FC300 DN4 316 3,88889E-07 0,0014 MASS2100 1,38889E-06 0,005 1,05556E-05 0,038 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 263 DN 50 -0,250 DN 80 0,641 DN 100 DN 150 -2,25 MASS2100 -0,0002 -0,00045 -0,00088 -0,0018 FC300 DN4 HP -0,0008 FC300 DN4 C22 -0,0018 FC300 DN4 316 -0,0025 MASS2100 -0,0072 -0,045 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 264 0,001269444 4,57 MASS2100 0,000000027 0,000098 0,000000054 0,000195 0,000000117 0,00042 0,000000250 0,0009 FC300 DN4 HP 0,000000097 0,00035 FC300 DN4 C22 0,000000264 0,00095 FC300 DN4 316 0,000000389 0,0014 MASS2100 0,000001389 0,005 0,000010556 0,038 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 265 Volume flow m 0,0018 FC300 DN4 316 Mass flow Kg/s 0,120 Volume flow m 0,0025 MASS2100 Mass flow Kg/s 0,353 Volume flow m 0,0072 Mass flow Kg/s 2,209 Volume flow m 0,0451 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 266 Volume flow m -0,0018 FC300 DN4 316 Mass flow Kg/s -0,120 Volume flow m -0,0025 MASS2100 Mass flow Kg/s -0,353 Volume flow m -0,0072 Mass flow Kg/s -2,209 Volume flow m -0,0451 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 267 DN 50 0,1444 DN 80 0,378 DN 100 0,783 DN 150 1,269 MASS2100 0,0000272 0,0000542 0,000117 0,000250 FC300 DN4 HP 0,0000972 FC300 DN4 C22 0,000264 FC300 DN4 316 0,000389 MASS2100 0,00139 0,0106 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 268 2820 DN 150 1,269 4570 MASS2100 0,0000272 0,0980 0,0000542 0,195 0,000117 0,42 0,000250 0,90 FC300 DN4 HP 0,0000972 0,35 FC300 DN4 C22 0,000264 0,95 FC300 DN4 316 0,000389 MASS2100 0,00139 0,0106 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 269: Sensor Dimension Dependent Default Settings (Inputs/Outputs)

    Standard volume flow 0.00003536 normal m³/s -0.005 to +0.005 DN 25 Mass flow kg/s -24.5 to +24.5 Volume flow 0.000098 -0.015 to +0.015 Standard volume flow 0.000098 normal m³/s -0.015 to +0.015 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 270 -0.059 to +0.059 Standard volume flow normal m³/s -0.059 to +0.059 DN 150 Mass flow kg/s - 251 to +251 Volume flow -0.249 to +0.249 Standard volume flow normal m³/s -0.249 to +0.249 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 271: Default Settings

    Selected zero-point adjustment Auto ● Auto method. Automatic zero point ● Manual adjustment is recommended. 2.1.3.2 Zero Point Adjustment Wizard 2.1.3.3 Duration Define zero-point adjustment du‐ 1 to 999 User ration. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 272: Auto Off

    [cycles] teresis band is exceeded. 2.1.4.8 Filter Iteration Set the number of times to re‐ 1 to 5 Expert peat the same filter. Increasing the number will increase the damping. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 273: Process Values

    Below limit flow output is forced to zero. 2.2.1.6 Alarm and warning limits 2.2.1.6.1 Upper alarm limit Set upper alarm limit. Alarm is User triggered if mass flow value is above the limit. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 274 /h, yd bu/s, bu/min, bu/ h, bu/d, Custom 2.2.2.2 Custom units Define a name for the custom User units. The custom units can then be selected in the units list. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 275 Sets the hysteresis for alarm User and warning limits. The hystere‐ sis is the distance between the limits for activation and deactiva‐ tion of an alarm/warning. : See Sensor dimension dependent default settings (Page 259) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 276: Standard Volume Flow

    2.2.3.5.5 Hysteresis Sets the hysteresis for alarm User and warning limits. The hystere‐ sis is the distance between limits for activation and deactivation of an alarm/warning. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 277 The hystere‐ [kg/m³] sis is the distance between the limits for activation and deactiva‐ tion of alarm/warning : See Sensor dimension dependent default settings (Page 259) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 278 Density adjustment 2.2.5.6.1 Adjustment factor Set compensation factor to ad‐ -1.999 to1.999 Expert just density calculation. 2.2.5.6.3 Adjustment offset Enter the displayed density ad‐ -14000.0 to Expert justment offset. [kg/m³] 14000.0 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 279 [°C] is above the limit. 2.2.6.3.3 Lower Limit Warning Set lower warning limit. Warning -50 to 200 User is triggered if temperature value [°C] is below the limit. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 280 Unit is not ap‐ s, kg/min, kg/h, kg/ plied at communication inter‐ d, t/min, t/h, t/d, lb/ face. s, lb/min, lb/h, lb/ d, STon/min, STon/h, STon/d, T/h, T/d, Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 281 Lower Limit Alarm Set lower alarm limit. Alarm is User triggered if fraction A value is be‐ low the limit. 2.2.7.5.6 Alarm Hysteresis Enter the hysteresis to avoid un‐ User wanted rapid switching. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 282 A % value is above the limit. 2.2.7.7.3 Lower Limit Warning Set lower limit warning. Warning 0.0 to 100.0 User is displayed if fraction A % value is below the limit. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 283 2.2.7.9.1 Adjustment Factor Enter the displayed fraction flow Expert adjustment factor. 2.2.7.9.2 Adjustment Offset Enter the displayed fraction flow Expert adjustment offset. : See Sensor dimension dependent default settings (Page 259) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 284: Totalizer

    ● 2 ● 3 ● 4 ● 5 ● 6 2.3.1.6 Direction Select totalizing direction. Forward count‐ ● Forward User counting and backward counting ● Forward counting ● Backward counting ● Hold MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 285 1 value is above the limit. 2.3.1.10.33) Lower warning limit Set lower warning limit. Warning [normal m3] User is triggered if totalizer 1 value is above the limit. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 286 The custom units can then be selected in the units list. 2.3.2.4 Custom conversion fac‐ Define a mass factor for the cus‐ User tom units. The factor is based on SI mass units kg MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 287 2 value is above the limit. 2.3.2.10.32) Lower warning limit Set lower alarm limit. Warning is [m3] User triggered if totalizer 2 value is above the limit. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 288 3. Units are not applied at Sm³, Custom communication interface. 2.3.3.3 Custom units Define a name for the custom User units. The custom units can then be selected in the units list. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 289 2.3.3.10.5 1) Hysteresis Sets the hysteresis for alarm User and warning limits. The hystere‐ [kg] sis is the distance between the limits for activation and deactiva‐ tion of an alarm/warning MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 290 User ● Cancel totalizer 3 to zero ● Ok Process Value is set to Mass flow Process Value is set to Volume flow Process Value is set to Standard volume flow MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 291: Inputs And Outputs

    ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % ● Control valve For functional safety applica‐ tions (SIL): ● Mass flow ● Volume flow ● Density MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 292 : See Sensor dimension dependent default settings (Page 259) Process value is set to Mass flow Process value is set to Volume flow Process value is set to Density MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 293 Select measured flow direction. Positive User ● Positive The flow meter will only output ● Negative current when flow value is meas‐ ● Bidirectional ured in selected direction. ● Bidirectional (symmetric) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 294 ● Mass flow output. ● Volume flow ● Standard volume flow ● Density ● Reference density ● Medium temperature ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 295 Media B 2.4.2.7.2 Direction Select measured flow direction. Positive User ● Positive The flow meter will only output ● Negative current when flow value is meas‐ ● Bidirectional ured in selected direction. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 296 ● bbl-beer (beer barrels = 31 US gallons) ● bbl42 (1 barrel = 42 US gallons) ● In (cubic inches) ● ft (cubic feet) ● yd (cubic yards) ● bush (bushels) ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 297 ’Fail-safe value’. 2.4.2.7.13 Fail-safe minimum dura‐ Minimum time the output stays ● 0 to 100 s User tion in fail-safe mode. Short events will be prolonged. 2.4.2.8 Digital output MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 298 Select the functionality for digital Alarm class User ● Alarm class output. Only applicable when ● Individual 'Operation Mode' is set to 'Sta‐ alarms tus'. ● Primary valve dosing control ● Secondary valve dosing control MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 299 ● 37 Sensor supply voltage out of range ● 38 Temperature measurement fault ● 39 Temperature measurement fault ● 40 Temperature measurement fault ● 41 Temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 300 ● 45 Flow values not valid ● 46 Invalid calibration data ● 47 Invalid compensation data ● 49 Malfunction in pickup amplitude ● 50 Malfunction in pickup amplitude ● 51 Malfunction in MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 301 ● 59 Mass flow out of specification ● 60 Volume flow out of specification ● 61 Density out specification ● 62 Media temp. below limit ● 63 Media temp. above limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 302 ● 76 Internal error in sensor ● 77 Internal error in sensor ● 78 Internal error in sensor ● 79 Auto filtering ● 87 The sensor is stabilizing MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 303 ● 106 Density flow below warning limit ● 107 Density flow below alarm limit ● 08 Media temperature flow above alarm limit ● 109 Media temperature above warning limit ● 110 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 304 Default settings B.5 Inputs and outputs HMI menu ID Parameter Description Default value Value range Access [unit] level below warning limit ● 111 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 305 ● 122 Fract. A flow below warning limit ● 123 Fract. A flow below alarm limit ● 124 Fract. B flow above alarm limit ● 125 Fract. B flow above warning limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 306 ● 132 Std. vol. above alarm limit ● 133 Std. vol. above warning limit ● 134 Std. vol. below warning limit ● 135 Std. vol. below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 307 2 below alarm limit ● 144 Totalizer 3 above alarm limit ● 145 Totalizer 3 above warning limit ● 146 Totalizer 3 below warning limit ● 147 Totalizer 3 below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 308 Individual saturation alarms occurs. ● 154 CH1 loop cur. In upper saturation ● 155 CH1 loop current deviation ● 157 Functional Safety event ● 158 CH 1 cable break MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 309 ● 211 CH4 output frequency too high ● 213 Invalid dosing settings ● 215 Channel 3 simulated ● 216 Channel 4 simulated ● 217 Process values frozen ● 218 outputs forced MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 310 The output is ac‐ alarm tive when alarm in selected ● Function alarm class occurs. check ● Process value alarm ● Process value warning ● Maintenance demanded ● Maintenance required ● None MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 311 Process Value is set to Density Process Value is set to Fluid Temperature Process Value is set to Standard volume flow Process Value is set to Fraction A % / Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 312 Direction Select measured flow direction. Positive User ● Positive The flow meter will only output ● Negative current when flow value is meas‐ ● Bidirectional ured in selected direction. ● Symmetric MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 313 Redundancy mode Set the Redundancy mode. The User ● Off frequency on channel 3 will fol‐ ● 90º low frequency on channel 2 with ● 180 º 90 or 180 deg. shift. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 314 ● Current value ● Fail-safe value 2.4.3.6.10 Fail-safe value Define fail-safe current output 0 Hz User ● 0 to 12500 Hz value if 'Fail-safe behaviour' pa‐ rameter is set to ’Fail-safe value’. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 315 ● t (1 t = 1000 Mass flow ● STon (1 STon = 2000 lb) ● T (1 T = 2240 ● oz (ounces) ● lb (pounds) ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 316 Define the amount per pulse, or User multiple pulses if you configure more than 1 pulse per amount 2.4.3.7.6 Pulses per amount Define number of pulses which User will be output when configured amount is reached MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 317 Select the functionality for digital Alarm class User ● Alarm class output. Only applicable when ● Individual 'Operation Mode' is set to 'Sta‐ alarms tus'. ● Primary valve dosing control ● Secondary valve dosing control MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 318 ● 37 Sensor supply voltage out of range ● 38 Temperature measurement fault ● 39 Temperature measurement fault ● 40 Temperature measurement fault ● 41 Temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 319 ● 44 Flow values not valid ● 45 Flow values not valid ● 46 Invalid calibration data ● 47 Invalid compensation data ● 49 Malfunction in pickup amplitude ● 50 Malfunction in MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 320 ● 59 Mass flow out of specification ● 60 Volume flow out of specification ● 61 Density out specification ● 62 Media temp. below limit ● 63 Media temp. above limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 321 ● 76 Internal error in sensor ● 77 Internal error in sensor ● 78 Internal error in sensor ● 79 Internal error in sensor ● 87 The sensor is stabilizing MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 322 ● 106 Density flow below warning limit ● 107 Density flow below alarm limit ● 108 Media temperature flow above alarm limit ● 109 Media temperature above warning limit ● 110 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 323 Default settings B.5 Inputs and outputs HMI menu ID Parameter Description Default value Value range Access [unit] level below warning limit ● 111 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 324 ● 122 Fract. A flow below warning limit ● 123 Fract. A flow below alarm limit ● 124 Fract. B flow above alarm limit ● 125 Fract. B flow above warning limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 325 ● 132 Std. vol. above alarm limit ● 133 Std. vol. above warning limit ● 134 Std. vol. below warning limit ● 135 Std. vol. below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 326 2 below alarm limit ● 144 Totalizer 3 above alarm limit ● 145 Totalizer 3 above warning limit ● 146 Totalizer 3 below warning limit ● 147 Totalizer 3 below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 327 In lower when one of the Individual saturation alarms occurs. ● 154 CH1 loop cur. In upper saturation ● 155 CH1 loop current deviation ● 158 CH 1 cable break MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 328 ● 215 Channel 3 simulated ● 216 Channel 4 simulated ● 217 Process values frozen ● 218 All outputs forced ● 219 CH2 loop current deviation ● 220 CH3 loop current deviation MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 329 The output is ac‐ alarm tive when alarm in selected ● Function alarm class occurs. check ● Process value alarm ● Process value warning ● Maintenance demanded ● Maintenance required ● None MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 330 3.5 to 25 mA User signal when forcing is activated. 2.4.3.9.3 Forced value (CH2) Enter the value for the output 4.00 mA 3.5 to 25 mA User signal when forcing is activated. Current MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 331 ● 7.0 ms ● 7.5 ms 2.4.3.9.7 Polarity Set the level of an active input: Active high level ● Active high active high or active low. level ● Active low level MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 332 Select the functionality for digital Individual User ● Alarm class output. Only applicable when alarms ● Individual 'Operation Mode' is set to 'Sta‐ alarms tus'. ● Primary valve dosing control ● Secondary valve dosing control MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 333 ● 37 Sensor supply voltage out of range ● 38 Temperature measurement fault ● 39 Temperature measurement fault ● 40 Temperature measurement fault ● 41 Temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 334 ● 42 Flow values not valid ● 43 Flow values not valid ● 44 Flow values not valid ● 45 Flow values not valid ● 46 Invalid calibration data MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 335 ● 74 Internal error in sensor ● 75 Internal error in sensor ● 76 Internal error in sensor ● 77 Internal error in sensor ● 87 The sensor is stabilizing MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 336 ● 76 Internal error in sensor ● 77 Internal error in sensor ● 87 The sensor is stabilizing ● 108 Media temperature flow above alarm limit ● 109 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 337 Default settings B.5 Inputs and outputs HMI menu ID Parameter Description Default value Value range Access [unit] level above warning limit ● 110 Media temperature below warning limit ● 111 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 338 ● 122 Fract. A flow below warning limit ● 123 Fract. A flow below alarm limit ● 124 Fract. B flow above alarm limit ● 125 Fract. B flow above warning limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 339 ● 132 Std. vol. above alarm limit ● 133 Std. vol. above warning limit ● 134 Std. vol. below warning limit ● 135 Std. vol. below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 340 2 below alarm limit ● 144 Totalizer 3 above alarm limit ● 145 Totalizer 3 above warning limit ● 146 Totalizer 3 below warning limit ● 147 Totalizer 3 below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 341 In lower when one of the Individual saturation alarms occurs. ● 154 CH1 loop cur. In upper saturation ● 155 CH1 loop current deviation ● 158 CH 1 cable break MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 342 ● 202 CH3 loop cur in upper saturation ● 203 CH3 cable break ● 204 CH3 output frequency too ● 205 CH3 output frequency too high ● 206 CH3 pulse overflow MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 343 ● 218 All outputs forced ● 219 CH2 loop current deviation ● 220 CH3 loop current deviation ● 221 CH4 loop current deviation ● 222 Invalid register mapping ● 223 Invalid coil configuration MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 344 The output is active alarm when one of the Individual ● Function alarms occurs. check ● Process value alarm ● Process value warning ● Maintenance demanded ● Maintenance required ● None MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 345 Fail-safe activation con‐ Fail-safe becomes active if ei‐ Invalid process User ● Invalid dition ther the selected process value value process value is unreliable, or the device ● Maintenance shows "Maintenance alarm". alarm MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 346 Select current output reaction in Lower fault cur‐ User ● Lower fault case of a fault. rent current ● Upper fault current ● Last valid value ● Current value ● Fail safe value MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 347 2.4.5.6.7 Damping value Set filter time constant. Defines User ● 0 to 100 s the damping of the current out‐ put signal. 0.0 means filter is off MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 348 ● t (1 t = 1000 Mass flow ● STon (1 STon = 2000 lb) ● T (1 T = 2240 ● oz (ounces) ● lb (pounds) ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 349 1 kg User pulses if you configure more than 1 pulse per amount 2.4.5.7.5 Pulses per amount Define number of pulses which User will be output when configured amount is reached MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 350 Select the functionality for digital Alarm class User ● Alarm class output. Only applicable when ● Individual 'Operation Mode' is set to 'Sta‐ alarms tus'. ● Primary valve dosing control ● Secondary valve dosing control MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 351 ● 37 Sensor supply voltage out of range ● 38 Temperature measurement fault ● 39 Temperature measurement fault ● 40 Temperature measurement fault ● 41 Temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 352 ● 44 Flow values not valid ● 45 Flow values not valid ● 46 Invalid calibration data ● 47 Invalid compensation data ● 49 Malfunction in pickup amplitude ● 50 Malfunction in MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 353 ● 59 Mass flow out of specification ● 60 Volume flow out of specification ● 61 Density out specification ● 62 Media temp. below limit ● 63 Media temp. above limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 354 ● 76 Internal error in sensor ● 77 Internal error in sensor ● 78 Unstable measurement condition and ● 79 Auto filtering ● 87 The sensor is stabilizing MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 355 ● 106 Density flow below warning limit ● 107 Density flow below alarm limit ● 108 Media temperature flow above alarm limit ● 109 Media temperature above warning limit ● 110 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 356 Default settings B.5 Inputs and outputs HMI menu ID Parameter Description Default value Value range Access [unit] level below warning limit ● 111 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 357 ● 122 Fract. A flow below warning limit ● 123 Fract. A flow below alarm limit ● 124 Fract. B flow above alarm limit ● 125 Fract. B flow above warning limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 358 ● 132 Std. vol. above alarm limit ● 133 Std. vol. above warning limit ● 134 Std. vol. below warning limit ● 135 Std. vol. below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 359 2 below alarm limit ● 144 Totalizer 3 above alarm limit ● 145 Totalizer 3 above warning limit ● 146 Totalizer 3 below warning limit ● 147 Totalizer 3 below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 360 ● 198 CH2 output frequency too ● 199 CH2 output frequency too high ● 213 Invalid dosing configuration ● 214 Channel 2 simulated ● 217 Process values frozen ● 218 All outputs forced MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 361 The output is ac‐ alarm tive when alarm in selected ● Function alarm class occurs. check ● Process value alarm ● Process value warning ● Maintenance demanded ● Maintenance required ● None MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 362 3.5 to 25 mA User signal when forcing is activated. 2.4.5.9.3 CH2 forced value Enter the value for the output 4.00 mA 3.5 to 25 mA User signal when forcing is activated. Current MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 363 ● 7.0 ms ● 7.5 ms 2.4.5.9.7 Polarity Set the level of an active input: Active high level ● Active high active high or active low. level ● Active low level MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 364 Select the functionality for status Individual ● Alarm class User output. Only applicable when alarms ● Individual 'Operation Mode' is set to 'Sta‐ alarms tus'. ● Primary valve dosing control ● Secondary valve dosing control MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 365 ● 37 Sensor supply voltage out of range ● 38 Temperature measurement fault ● 39 Temperature measurement fault ● 40 Temperature measurement fault ● 41 Temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 366 ● 45 Flow values not valid ● 46 Invalid calibration data ● 47 Invalid compensation data ● 49 Malfunction in pickup amplitude ● 50 Malfunction in pickup amplitude ● 51 Malfunction in MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 367 ● 59 Mass flow out of specification ● 60 Volume flow out of specification ● 61 Density out specification ● 62 Media temp. below limit ● 63 Media temp. above limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 368 ● 74 Internal error in sensor ● 75 Internal error in sensor ● 76 Internal error in sensor ● 77 Internal error in sensor ● 87 The sensor is stabilizing MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 369 ● 105 Density flow above warning limit ● 106 Density flow below warning limit ● 107 Density flow below alarm limit ● 108 Media temperature flow above alarm limit ● 109 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 370 Default settings B.5 Inputs and outputs HMI menu ID Parameter Description Default value Value range Access [unit] level above warning limit ● 110 Media temperature below warning limit ● 111 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 371 ● 122 Fract. A flow below warning limit ● 123 Fract. A flow below alarm limit ● 124 Fract. B flow above alarm limit ● 125 Fract. B flow above warning limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 372 ● 132 Std. vol. above alarm limit ● 133 Std. vol. above warning limit ● 134 Std. vol. below warning limit ● 135 Std. vol. below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 373 2 below alarm limit ● 144 Totalizer 3 above alarm limit ● 145 Totalizer 3 above warning limit ● 146 Totalizer 3 below warning limit ● 147 Totalizer 3 below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 374 Individual ● 199 CH2 alarms occurs. output frequency too high ● 213 Invalid dosing configuration ● 214 Channel 2 simulated ● 217 Process values frozen ● 218 All outputs forced MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 375 The output is active alarm when one of the Individual ● Function alarms occurs. check ● Process value alarm ● Process value warning ● Maintenance demanded ● Maintenance required ● None MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 376 Process Value is set to Density Process Value is set to Fluid Temperature Process Value is set to Corrected Volumeflow Process Value is set to Fraction A % / Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 377: Dosing

    Select unit for the recipe. Unit is User ● g not applied at communication in‐ ● kg terface. ● t Mass flow ● STon ● T ● oz ● lb ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 378 2.5.5.3 Amount Define the filling amount. The User valve will be closed and filling stopped when defined amount is reached. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 379 2.5.5.6.5 Stage 2 Secondary Define the dosing amount value 0.0 to 100.0 User Close to close the secondary valve. The value is in % of defined dos‐ ing amount. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 380 The value is in % of defined dos‐ ing amount. 2.5.5.6.6 Fully Closed Current Define current level to fully close 0 to 20 User Level the analog valve. [mA] MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 381 Select unit for the recipe. Unit is User ● g not applied at communication in‐ ● kg terface. ● t Mass flow ● STon ● T ● oz ● lb ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 382 2.5.6.3 Amount Define the filling amount. The User valve will be closed and filling stopped when defined amount is reached. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 383 2.5.6.6.5 Stage 2 Secondary Define the dosing amount value 0.0 to 100.0 User Close to close the secondary valve. The value is in % of defined dos‐ ing amount. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 384 The value is in % of defined dos‐ ing amount. 2.5.6.6.6 Fully Closed Current Define current level to fully close 0 to 20 User Level the analog valve. [mA] MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 385 Select unit for the recipe. Unit is User ● g not applied at communication in‐ ● kg terface. ● t Mass flow ● STon ● T ● oz ● lb ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 386 2.5.7.3 Amount Define the filling amount. The User valve will be closed and filling 1.0 SI stopped when defined amount is reached. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 387 2.5.7.6.5 Stage 2 Secondary Define the dosing amount value 0.0 to 100.0 User Close to close the secondary valve. The value is in % of defined dos‐ ing amount. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 388 The value is in % of defined dos‐ ing amount. 2.5.7.6.6 Fully Closed Current Define current level to fully close 0 to 20 User Level the analog valve. [mA] MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 389 2.5.7.7.4 Overrun value Define the dosing overrun User amount. An alarm is raised and valve(s) closed if dosing amount is exceeded. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 390 2.5.7.2 Unit Select unit for the recipe. Unit is User ● NL not applied at communication in‐ ● Nm³ terface. ● SI Standard volume flow ● Sft³ ● Sm³ ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 391 (% of dosing amount). 2.5.7.6.2 Stage 1 Primary Open Define the dosing amount value 0.0 to 100.0 User to open the primary valve. The value is in % of defined dosing amount. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 392 The value is in % of defined dos‐ ing amount. 2.5.7.6.2 Stage 1 Primary Open Define the dosing amount value User to open the primary valve. The value is in % of defined dosing amount. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 393 2.5.7.7 Fault Handling 2.5.7.7.1 Duration mode Enable or disable dosing time User ● Off supervision. An alarm is raised ● On and valve(s) closed if dosing time is exceeded. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 394 Select unit for the recipe. Unit is User ● g not applied at communication in‐ ● kg terface. ● t Mass flow ● STon ● T ● oz ● lb ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 395 2.5.8.3 Amount Define the filling amount. The 1.00 User valve will be closed and filling stopped when defined amount is reached. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 396 2.5.8.6.5 Stage 2 Secondary Define the dosing amount value 0.0 to 100.0 User Close to close the secondary valve. The value is in % of defined dos‐ ing amount. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 397 The value is in % of defined dos‐ ing amount. 2.5.8.6.6 Fully Closed Current Define current level to fully close 0 to 20 User Level the analog valve. [mA] MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 398 2.5.8.7.4 Overrun value Define the dosing overrun User amount. An alarm is raised and valve(s) closed if dosing amount is exceeded. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 399 2.5.9.2 Unit Select unit for the recipe. Unit is User ● NL not applied at communication in‐ ● Nm³ terface. ● SI Standard volume flow ● Sft³ ● Sm³ ● Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 400 (% of dosing amount). 2.5.9.6.2 Stage 1 Primary Open Define the dosing amount value 0.0 to 100.0 User to open the primary valve. The value is in % of defined dosing amount. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 401 The value is in % of defined dos‐ ing amount. 2.5.9.6.2 Stage 1 Primary Open Define the dosing amount value User to open the primary valve. The value is in % of defined dosing amount. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 402 2.5.9.7 Fault Handling 2.5.9.7.1 Duration mode Enable or disable dosing time User ● Off supervision. An alarm is raised ● On and valve(s) closed if dosing time is exceeded. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 403: Date And Time

    2.7.2 Set date and time Set current date and time of the User device. This date and time is used for all timestamps of log‐ ged information MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 404: Local Display

    (30 s) ● Always on 2.8.3 Contrast User ● 0% ● 10% ● 20% ● 30% ● 40% ● 50% ● 60% ● 70% ● 80% ● 90% ● 100% 2.8.4 Damping MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 405 Select the first value for the view. Mass flow User ● Mass flow ● Volume flow ● Standard volume flow ● Density ● Medium temperature ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 406 ● Volume flow ● Standard volume flow ● Density ● Medium temperature ● Standard volume flow ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 407 Graph Scale Lower Limit Define the scaling upper limit of User the value axis for fixed mode. 2.8.5.11 Graph Scale Upper Limit Define the scaling lower limit of User the value axis for fixed mode. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 408 ● Medium temperature ● Sensor frame temperature ● Standard volume flow Fraction flow Medium A ● Fraction flow Medium B ● Fraction flow Medium A % ● Fraction flow Medium B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 409 ● Standard volume flow ● Density ● Medium temperature ● Fraction flow Medium A ● Fraction flow Medium B ● Fraction flow Medium A % ● Fraction flow Medium B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 410 Select the logging period (time 5 min User ● 1 min axis length). ● 5 min ● 15 min ● 30 min ● 1 h ● 2 h ● 3 h MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 411 ● Mass flow User ature ● Volume flow ● Standard volume flow ● Density ● Medium temperature ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 412 User ● Mass flow view. ● Volume flow ● Standard volume flow ● Density ● Medium temperature ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 413 Graph Scale Lower Limit Define the scaling upper limit of User the value axis for fixed mode. 2.8.7.12 Graph Scale Upper Limit Define the scaling lower limit of User the value axis for fixed mode. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 414 ● Density ● Medium temperature ● Sensor frame temperature ● Standard volume flow ● Fraction A ● Fraction flow Medium B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 415 ● Standard volume flow ● Density ● Medium temperature ● Sensor frame temperature ● Standard volume flow ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 416 View Select the view type. Three values User ● Single value ● Three values ● One value and bargraph ● One value and graph ● Six values ● Six Diagnostic values MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 417 ● Mass flow view. ature ● Volume flow ● Standard volume flow ● Density ● Medium temperature ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 418 2.8.9.9 Graph Scale Mode Select the scaling mode. Auto‐ Auto User ● Auto matic scaling or fixed scaling us‐ ● Fixed ing “Graph Scale Lower Limit” and “Graph Scale Upper Limit”. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 419 Select the first value for the view. Totalizer 2 ● Mass flow User ● Volume flow ● Standard volume flow ● Density ● Medium temperature ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 420 ● Standard volume flow ● Density ● Medium temperature ● Fraction flow Medium A ● Fraction flow Medium B ● Fraction flow Medium A % ● Fraction flow Medium B % MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 421 Graph Scale Upper Limit Define the scaling lower limit of User the value axis for fixed mode. 2.8.11 Status icons Select the set of status icons for Standard Standard User diagnostic events. NAMUR MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 422: Maintenance And Diagnostics

    HW version Transmitter hardware version. Read only 3.1.15.2 FW version Transmitter firmware version. Read only 3.1.15.3 Serial number Unique transmitter serial num‐ Read ber. Also shown on the device only nameplate. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 423 Transmitter detailed Transmitter detailed events ● DE10 events ● DE11 ● DE12 ● DE21 ● DE22 ● DE23 ● DE24 ● DE26 ● DE27 ● DE28 ● DE29 ● DE30 ● DE31 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 424 Value range Access [unit] level 3.2.6 Suppression time A coming event is suppressed ● 0 to 300 s until the suppression time has elapsed. This prevents alarm flooding. 3.2.7 Enable alarms MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 425 ● 106 Density flow below warning limit ● 107 Density flow below alarm limit ● 08 Media temperature flow above alarm limit ● 109 Media temperature above warning limit ● 110 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 426 Default settings B.9 Maintenance and diagnostics HMI menu ID Parameter Description Default value Value range Access [unit] level below warning limit ● 111 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 427 ● 122 Fract. A flow below warning limit ● 123 Fract. A flow below alarm limit ● 124 Fract. B flow above alarm limit ● 125 Fract. B flow above warning limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 428 ● 132 Std. vol. above alarm limit ● 133 Std. vol. above warning limit ● 134 Std. vol. below warning limit ● 135 Std. vol. below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 429 2 below alarm limit ● 144 Totalizer 3 above alarm limit ● 145 Totalizer 3 above warning limit ● 146 Totalizer 3 below warning limit ● 147 Totalizer 3 below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 430 ● 164 Fraction simulated ● 166 Std. volume flow simulated ● 167 Totalizer 1 simulated ● 168 Totalizer 2 simulated ● 169 Totalizer 3 simulated ● 170 Loop current simulated MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 431 ● 291 Pressure cation interface. simulated ● 292 Kin. viscosity simulated ● 298 Std. volume flow simulated MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 432 ● 201 CH3 loop cur. In lower saturation ● 202 CH3 loop cur in upper saturation ● 203 CH3 cable break ● 204 CH3 output frequency too ● 205 CH3 output MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 433 ● 206 CH3 pulse overflow ● 207 CH4 loop cur. In lower saturation ● 208 CH4 loop cur in upper saturation ● 209 CH4 cable break ● 210 CH4 output MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 434 ● 218 All outputs forced ● 219 CH2 loop current deviation ● 220 CH3 loop current deviation ● 221 CH4 loop current deviation ● 222 Invalid register mapping ● 223 Invalid coil configuration MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 435 ● 193 Dosing and the alarm on the communi‐ quantity cation interface. overrun ● 194 Invalid proc. Val. during dosing ● 213 Invalid dosing configuration 3.2.8 Assign alarm class MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 436 ● Function check ● Process value warning ● Maintenance demanded ● Maintenance required ● Function check Namur: ● Out of specification ● Failure ● Maintenance demanded ● Maintenance required ● Function MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 437 Sensor type. Also shown on the Read device nameplate. only 3.1.19.2 Size Nominal sensor diameter (DN). Read only 3.1.19.3 Order Number Replacement sensor order num‐ Read ber (MLFB). Also shown on the only device nameplate. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 438 HMI menu ID Parameter Description Default value Value range Access [unit] level 3.4.1 Sensor 3.4.1.1 Driver current The actual current value that ex‐ Read cites the sensor. High current: only check process conditions. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 439 Sensor frame temperature 3.4.2.4.1 Current value The measured temperature of [°C] Read the sensor frame. only 3.4.3 Inputs and outputs 3.4.3.1 Channel 1 – output with HART 3.4.3.1.1 Loop Current [mA] MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 440 Error status - pulse Read ● Upper only saturation ● Fail-safe behaiviour active 3.4.3.2.3 Error status Error status - frequency ● Upper Read only saturation ● Lower saturation ● Fail-safe behaiviour active MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 441 Error status - pulse Read ● Upper only saturation ● Fail-safe behaiviour active 3.4.3.3.3 Error status Error status - frequency Read ● Upper only saturation ● Lower saturation ● Fail-safe behaiviour active MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 442 Actual value of status output. Read only 3.4.3.5.2 Loop current Actual value of current output [mA] Read only 3.4.3.5.3 Error status Error status - pulse Read ● Upper only saturation ● Fail-safe behaiviour active MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 443 ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % ● Control valve 3.5.1.2 Minimum Minimum value measured. Read only 3.5.1.3 Timestamp at minimum Timestamp at minimum Read only MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 444 Maximum Maximum value measured. Read only 3.5.2.5 Timestamp at maximum Timestamp at maximum Read only 3.5.2.6 Reset The peak values will be reset to User current values. 3.5.3 Process values 3 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 445 ● Media temperature ● Standard Volume flow ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % ● Control valve 3.5.4.2 Minimum Minimum value measured. Read only MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 446 Factory-set frame temperature Read temp. compensation for density calcu‐ only lation. 3.6.6.8 Wetted materials Type of wetted material of the Read sensor. only 3.6.7 Fraction order code Order code of the active fraction. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 447 ● 1 min ● 5 min ● 15 min ● 30 min ● 1 h ● 2 h ● 4 h ● 6 h ● 12 h ● 24 h 3.7.5.4 Process values MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 448 90. 3.7.5.4.8 Logging value 8 Select the process values to be logged. Up to 20 can be selected here. With a remote tool you can configure up to 90. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 449 3.7.5.4.20 Logging value 20 Select the process values to be logged. Up to 20 can be selected here. With a remote tool you can configure up to 90. 3.7.5.5 Advanced logging MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 450 ● Current output want the channel to operate. ● Frequency output ● Pulse output ● Status output 3.8.1.2.2 Simulation Enable or disable simulation of Disabled ● Disabled User the current output. ● Enabled MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 451 Enter the frequency output sim‐ 1 Hz User ● 1 to 12500 Hz ulation value. 3.8.1.5.3 Simulation value Enter the pulse output simula‐ 1 Hz User ● 1 to 12500 Hz tion value. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 452 Simulation value -20 to +20 User [normal m3/h] 3.8.2.6 Density 3.8.2.6.1 Simulation value 1000 User [kg/m3] 3.8.2.7 Fluid Temperature 3.8.2.7.1 Simulation value User [°C] 3.8.2.8 Frame Temperature 3.8.2.8.1 Simulation value User [°C] MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 453 Simulate alarms HMI menu ID Parameter Description Default value Value range Access [unit] level 3.8.3.1 Simulation mode User ● Off ● Simulate Alarm (ID number) ● Simulate alarm class 3.8.3.2 Alarms MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 454 ● 37 Sensor supply voltage out of range ● 38 Temperature measurement fault ● 39 Temperature measurement fault ● 40 Temperature measurement fault ● 41 Temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 455 ● 44 Flow values not valid ● 45 Flow values not valid ● 46 Invalid calibration data ● 47 Invalid compensation data ● 49 Malfunction in pickup amplitude ● 50 Malfunction in MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 456 ● 58 Unstable driver oscillation ● 60 Volume flow out of specification ● 61 Density out specification ● 62 Media temp. below limit ● 63 Media temp. above limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 457 ● 75 Internal error in sensor ● 76 Internal error in sensor ● 77 Internal error in sensor ● 78 Unstable measurement condition ● 79 Auto filtering ● 87 The sensor is stabilizing MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 458 ● 106 Density flow below warning limit ● 107 Density flow below alarm limit ● 108 Media temperature flow above alarm limit ● 109 Media temperature above warning limit ● 110 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 459 Default settings B.9 Maintenance and diagnostics HMI menu ID Parameter Description Default value Value range Access [unit] level below warning limit ● 111 Media temperature MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 460 ● 122 Fract. A flow below warning limit ● 123 Fract. A flow below alarm limit ● 124 Fract. B flow above alarm limit ● 125 Fract. B flow above warning limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 461 ● 132 Std. vol. above alarm limit ● 133 Std. vol. above warning limit ● 134 Std. vol. below warning limit ● 135 Std. vol. below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 462 2 below alarm limit ● 144 Totalizer 3 above alarm limit ● 145 Totalizer 3 above warning limit ● 146 Totalizer 3 below warning limit ● 147 Totalizer 3 below alarm limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 463 ● 153 CH1 loop alarms. Select from alarm list Alarm cur. In lower saturation ● 154 CH1 loop cur. In upper saturation ● 155 CH1 loop current deviation 158 CH 1 cable break MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 464 Select one or more alarm items User ● 192 Dosing to be simulated. time overrun ● 193 Dosing quantity overrun ● 194 Invalid proc. Val. during dosing ● 213 Invalid dosing configuration MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 465: Audit Trail

    ● Cancel 3.9.3 Firmware update Read change log only 3.9.4 Clear FW update Do you wish to clear the firm‐ Cancel User ● Ok change log ware change log? ● Cancel MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 466: Resets

    PC as MSD ● Enabled when USB cable is connected. 4.1.3 MSD connect Connects/disconnects the trans‐ Disconnect ● Disconnect mitter as mass storage device to/ ● Connect from PC. HART Channel 1 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 467 ● Density ● Standard density ● Medium temperature ● Fraction A ● Fraction B ● Fraction A % ● Fraction B % ● Totalizer 1 ● Totalizer 2 ● Totalizer 3 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 468 Select mass flow unit for the kg/h g/s, g/min, g/h, kg/ User communication interface (mass/ s, kg/min, kg/h, kg/ time). d, t/min, t/h, t/d, lb/ s, lb/min, lb/h, lb/ d, STon/min, STon/h, STon/d, T/h, T/d, Custom MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 469 (mass/vol‐ L, g/mL, g/cm³, g/ ume). L, kg/L, kg/m³, lb/ in³, lb/gal, lb/ft³, STon/yd³, Custom 4.2.8.11 Temperature units Select temperature unit for the °C °C, °F, °R, K User communication interface. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 470 User communication interface. Unit is Sm³ not applied at Local User Inter‐ face. 4.3.9 Damping 4.2.9.1 Damping value Define the damping filter time 0.0 s 0 to 100.0 s User constant. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 471 ● Odd parity, 1 stopbit ● No parity, 2 stopbits 4.3.6 Floating point byte order Select byte transmission se‐ 3-2-1-0 User ● 1-0-3-2 quence ● 0-1-2-3 ● 2-3-0-1 ● 3-2-1-0 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 472 Register of an existing product 65535 0 to 65535 User parameter which the Modbus re‐ quest is redirected to. 4.3.8.18 Source register 9 Requested register communica‐ 65535 0 to 65535 User ted via Modbus. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 473 65535 0 to 65535 User ted via Modbus. 4.3.8.37 Target register 18 Register of an existing product 65535 0 to 65535 User parameter which the Modbus re‐ quest is redirected to. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 474 User munication interface. Unit is not s, kg/min, kg/h, kg/ applied at Local User Interface. d, t/min, t/h, t/d, lb/ s, lb/min, lb/h, lb/ d, STon/min, STon/h, STon/d, T/h, T/d MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 475 Totalizer 3 unit Select Totalizer 3 unit for the L, hL, m³, Ugal, User communication interface. Unit is BL, BB, BO, in³, not applied at Local User Inter‐ ft³, yd³, gal, bush face. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 476: Security

    Activate user PIN Do you wish to enable the ac‐ Expert cess control? Deactivate user PIN Do you wish to disable the ac‐ Expert cess control? MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 477: Language

    HMI menu ID Parameter Description Default value Value range Access [unit] level Language Select the local display lan‐ English User ● English guage ● Deutsch ● Italiano ● Français ● Español ● 汉语 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 478 Default settings B.15 Language MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 479: Certificates And Support

    ● Information about field service, repairs, spare parts and lots more under Services. Additional Support If you have additional questions about the device, please contact your local Siemens representative and offices at: Local contact person (http://www.automation.siemens.com/partner) QR code label A QR code label can be found on the device.
  • Page 480: Certificates

    Certification documents including calibration report are supplied with each sensor included on the SensorFlash. Material, pressure test, and factory conformance certificates are optional at ordering. Note EAC declaration The EAC declaration is available on the SensorFlash SD card delivered with the device. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 481: Hmi Menu Structure

    Pulsating Flow wizard (menu item 1.6) (Page 108) Dosing Application Dosing Application wizard (menu item 1.7) (Page 109) Copy configuration Table D-19 Maintenance Mainte‐ nance (Page 505) Communication Menu item 4: Communication (Page 512) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 482 Deactivate user PIN Menu item 5.1: Deactivate user PIN Auto logout Menu item 5.1: Auto logout Logout Menu item 5.1: Logout Language See also Inputs/Outputs wizard (menu item 1.4) (Page 103) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 483: Menu Item 2.1: Sensor

    Filter time constant 2.1.4.2 Alarm limit 2.1.4.3 Warning limit 2.1.4.4 Measurement sample Time 2.1.4.5 Filter hysteresis 2.1.4.6 Minimum filter time 2.1.4.7 Filter iteration 2.1.4.8 Bandwidth factor 2.1.4.9 Filter pole shift 2.1.4.10 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 484: Menu Item 2.2: Process Values

    Custom conversion factor 2.2.2.4 Decimal places 2.2.2.5 Low flow cut-off 2.2.2.6.1 Upper alarm limit 2.2.2.6 Alarm and warning limits 2.2.2.6.2 Upper warning limit 2.2.2.6.3 Lower warning limit 2.2.2.6.4 Lower alarm limit Hysteresis 2.2.2.6.5 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 485 2.2.5.5.2 Upper warning limit 2.2.5.5.3 Lower warning limit 2.2.5.5.4 Lower alarm limit 2.2.5.5.5 Hysteresis 2.2.5.6.1 Adjustment Factor 2.2.5.6 Density adjustment 2.2.5.6.3 Fraction offset 2.2.5.7 Empty tube detection 2.2.5.8 Empty tube limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 486 2.2.7.8 Fraction B % 2.2.7.8.2 Upper Limit Warning 2.2.7.8.3 Lower Limit Warning 2.2.7.8.4 Lower Limit Alarm 2.2.7.8.5 Alarm Hysteresis 2.2.7.8.6 Decimal Places 2.2.7.9 Fraction Adjustment 2.2.7.9.1 Adjustment Factor 2.2.7.9.2 Fraction offset MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 487: Menu Item 2.3: Totalizer

    Lower Limit Alarm 2.3.2.9 Alarm Hysteresis 2.3.2.10 Reset 2.3.2.11 Preset Upper alarm limit 2.3.2.10 Alarm and warning limits 2.3.2.10.1 Upper warning limit 2.3.2.10.2 Lower warning limit 2.3.2.10.3 Lower alarm limit 2.3.2.10.4 Hysteresis 2.3.2.10.5 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 488: Menu Item 2.4: Inputs And Outputs

    Fail Safe Value 2.4.1.12 Fail-safe minimum duration Note Menu item visibility The availability in the HMI of the menu items for channels 2, 3 and 4 depend on the I/O configuration. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 489 Fail-safe minimum duration 2.4.2.7.11 2.4.2.8 Digital output 2.4.2.8.1 Mode Sensor alarms (group 1) 2.4.2.8.2 Sensor alarms (group 2) 2.4.2.8.3 Process alarms (1) 2.4.2.8.4 Process alarms (2) 2.4.2.8.5 2.4.2.8.8 Totalizers alarms Device alarms 2.4.2.8.9 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 490 Name Name Channel 1 alarms 2.4.2.8.10 Input/output alarms (1) 2.4.2.8.11 Simulation alarms (1) 2.4.2.8.13 Simulation alarms (2) 2.4.2.8.14 Alarm class 2.4.2.8.15 NAMUR status signal 2.4.2.8.16 2.4.2.8.17 Polarity On-delay 2.4.2.8.18 Off-delay 2.4.2.8.19 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 491 2.4.3.7.10 2.4.3.7.11 Fail-safe value Fail-safe minimum duration 2.4.3.7.12 Mode 2.4.3.8 Digital output 2.4.3.8.1 Sensor alarms (group 1) 2.4.3.8.2 Sensor alarms (group 2) 2.4.3.8.3 2.4.3.8.4 Process alarms (1) Process alarms (2) 2.4.3.8.5 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 492 Device alarms Channel 1 alarms 2.4.4.11 Input/output alarms (1) 2.4.4.12 Simulation alarms (1) 2.4.4.14 Simulation alarms (2) 2.4.4.15 2.4.4.16 Alarm class NAMUR status signal 2.4.4.17 Polarity 2.4.4.18 On-delay 2.4.4.19 Off-delay 2.4.4.20 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 493 Flow direction 2.4.5.6.2 2.4.5.6.3 Upper frequency value Lower frequency value 2.4.5.6.4 Upper range value 2.4.5.6.5 Lower range value 2.4.5.6.6 Damping value 2.4.5.6.7 Fail-safe behavior 2.4.5.6.8 Fail-safe value 2.4.5.6.9 2.4.5.6.10 Fail-safe minimum duration MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 494 Input function 2.4.5.9 Digital input 2.4.5.9.1 CH1 forced current value 2.4.5.9.2 CH2 forced current value 2.4.5.9.3 2.4.5.9.4 CH3 forced current value CH4 forced current value 2.4.5.9.5 Debounce time 2.4.5.9.6 Polarity 2.4.5.9.7 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 495: Menu Item 2.5: Dosing

    Polarity 2.4.6.18 On-delay 2.4.6.19 Off-delay 2.4.6.20 Menu item 2.5: Dosing Table D-9 Dosing Level 3 Level 4 Level 5 Name Name Name 2.5.1 Dosing mode 2.5.2 Process value 2.5.3 Active recipe MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 496 2.5.5.6.8 Current value to fully open 2.5.5.6.9 Amount for fully open 2.5.5.6.10 Amount for partially open 2.5.5.7 Fault Handling 2.5.5.7.1 Duration Mode 2.5.5.7.2 Duration Time 2.5.5.7.3 Overrun Mode 2.5.5.7.4 Overrun Value MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 497 2.5.6.6.8 Current value to fully open 2.5.6.6.9 Amount for fully open 2.5.6.6.10 Amount for partially open 2.5.6.7 Fault Handling 2.5.6.7.1 Duration Mode 2.5.6.7.2 Duration Time 2.5.6.7.3 Overrun Mode 2.5.6.7.4 Overrun Value MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 498 2.5.7.6.8 Current value to fully open 2.5.7.6.9 Amount for fully open 2.5.7.6.10 Amount for partially open 2.5.7.7 Fault Handling 2.5.7.7.1 Duration Mode 2.5.7.7.2 Duration Time 2.5.7.7.3 Overrun Mode 2.5.7.7.4 Overrun Value MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 499 2.5.8.6.8 Current value to fully open 2.5.8.6.9 Amount for fully open 2.5.8.6.10 Amount for partially open 2.5.8.7 Fault Handling 2.5.8.7.1 Duration Mode 2.5.8.7.2 Duration Time 2.5.8.7.3 Overrun Mode 2.5.8.7.4 Overrun Value MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 500: Menu Item 2.7: Date And Time

    Overrun Value Menu item 2.7: Date and time Table D-15 Date and time Level 3 Level 4 Level 5 Name Name Name 2.7.1 Current data and time 2.7.2 Set date and time MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 501: Menu Item 2.8: Local Display

    View 3 2.8.7.2 Type 2.8.7.3 value 2.8.7.4 value 2.8.7.5 value 2.8.7.6 value 2.8.7.7 value 2.8.7.8 value 2.8.7.9 Scale mode 2.8.7.10 Log time window 2.8.7.11 Scale lower limit 2.8.7.12 Scale upper limit MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 502 Type 2.8.10.3 value 2.8.10.4 value 2.8.10.5 value 2.8.10.6 value 2.8.10.7 value 2.8.10.8 value 2.8.10.9 Scale mode 2.8.10.10 Log time window 2.8.10.11 Scale lower limit 2.8.10.12 Scale upper limit 2.8.11 Status icons MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 503: Menu Item 3.1: Identification

    3.1.15.2 FW version 3.1.15.3 HMI cfg. version 3.1.17.1 HW version 3.1.17 I/O electronics 3.1.17.2 FW version 3.1.17.3 Serial number 3.1.19.1 Type 3.1.19 Sensor 3.1.19.2 Size 3.1.19.3 Order number 3.1.19.4 Serial number MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 504: Menu Item 3.2: Diagnostic Events

    149 Transm. temp above 3.2.8.9 alarm limit Note Transmitter Detail Alarms Menu item 3.2.7 (Transmitter Detail Alarms) is only visible in case an alarm with detailed alarm information is pending. MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 505: Menu Item 3.3: Maintenance

    Level 4 Level 5 Name Name Name 3.4.1 Sensor 3.4.1.1 Driver current 3.4.1.2 Pickup S1 amplitude 3.4.1.3 Pickup S2 amplitude 3.4.1.4 Max. pickup amplitude diff 3.4.1.5 Derived frequency 3.4.1.6 Offset 3.4.1.7 Offset MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 506 Totalized amount 3.4.3.5.2 Output frequency 3.4.3.5.2 Digital output signal 3.4.3.5.2 Loop current 3.4.3.5.2 Error status 3.4.3.5.3 3.4.3.5.4 Pulse counter Reset pulse counter 3.4.3.5.5 Digital output signal 3.4.3.6 Channel 4 – relay 3.4.3.6.1 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 507: Menu Item 3.5: Peak Values

    Menu item 3.6: Characteristics Table D-22 Characteristics Level 3 Level 4 Level 5 Name Name Name 3.6.1 SIL Variant 3.6.2 CT Variant 3.6.3 CT Active 3.6.4.1 Composition 3.6.4 Transmitter 3.6.4.2 Hazardous area Approval MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 508: Menu Item 3.7: Sensorflash

    Wetted materials 3.6.4 Fraction order code D.15 Menu item 3.7: SensorFlash Table D-23 SensorFlash Level 3 Level 4 Level 5 Name Name Name 3.7.1 Eject 3.7.2 installed 3.7.3 Capacity 3.7.4 Free space MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 509 3.7.5.4.17 Logging value 17 3.7.5.4.18 Logging value 18 3.7.5.4.19 Logging value 19 3.7.5.4.20 Logging value 20 3.7.5.5.1 Register 1 3.7.5.5 Advanced logging 3.7.5.5.2 Register 2 3.7.5.5.3 Register 3 3.7.5.5.90 Register 90 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 510: Menu Item 3.8: Simulation

    Standard volume flow 3.8.2.4.1 Simulation value 3.8.2.6 Density 3.8.2.6.1 3.8.2.7 Medium temperature 3.8.2.7.1 Simulation value Simulation value 3.8.2.9 Fraction A % value 3.8.2.9.1 Simulation value 3.8.2.10 Fraction B % value 3.8.2.10.1 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 511: Menu Item 3.9: Audit Trail

    FW update change log 3.9.4 Clear FW update change D.18 Menu item 3.10: Self test Table D-26 Self test Level 3 Level 4 Level 5 Name Name Name 3.10.1 Display test MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 512: Menu Item 3.11: Resets

    Firmware update D.21 Menu item 4: Communication Table D-29 Communication Level 3 Level 4 Level 5 Name Name Name 4.1.1 USB mode USB (Service channel) 4.1.2 Auto connection 4.1.3 MSD connent MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 513 Fraction volume flow units 4.2.8.9 Temperature units 4.2.8.10 Totalizer 1 units 4.2.8.11 Totalizer 2 units 4.2.8.12 Totalizer 3 units 4.2.9.1 Damping value 4.2.9 Damping 4.2.9.2 Process values (1) 4.2.9.3 Process values (2) MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 514: Menu Item 5: Security

    Table D-30 Security Level 3 Level 4 Level 5 Name Name Name Change user PIN Change expert PIN Recovery ID PIN recovery Activate user PIN Deactivate user PIN Auto logout Logout MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 515 Approvals, 21 Process value, 273 Hot swappable, 180, 181, 183 Reset, 466 Hotline, 479 Security, 476 Self Test, 466 SensorFlash, 447 Simulation, 450 Icons, 187 totalizer, 284 Identification, 503 Design, 29 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 516 Service information, 171 Siemens standard alarm classes, 185 NAMUR status signals, 186 Signal output, 489, 491 Navigation view, 127 Signal processing, 35 Simulate Input/Outputs, 510 Simulation, 166 Operation, 111 Specification nameplate Transmitter, 86 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 517 Rotate transmitter, 52 Wall mounting, 51, 55 Transmitter diagnostic events, 194 Vibrations, 45, 211 Warning symbols, 17 Wiring, (See Electrical connection) Zero point adjustment, 97, 138 Automatic, 138 via PDM, 97 MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...
  • Page 518 Index MASS 2100 & FC300 (FCT030) Operating Instructions, 06/2017, A5E39789040-AA...