CG.5.2 Binary / Control Relay Output Block (Objects 10/12)
64
Any detected change in the state of any point assigned to Class 1 will cause the
generation of an event object.
Table CG–6: Binary Output Point List
INDEX
0
Reset
1
Generator Start
2
Generator Stop
3
Clear Trip Counters
4
Clear Last Trip Data
5
Clear MWh and Mvarh
6
Clear Peak Demand Data
7
Clear Generator Information
8
Clear Breaker Information
The following restrictions should be noted when using object 12 to control the points listed
above:
1.
The Count field is checked first. If it is zero, the command will be accepted but no
action will be taken. If this field is non-zero, the command will be executed exactly
once regardless of its value.
2.
The Control Code field of object 12 is then inspected:
• The Queue and Clear sub-fields are ignored.
• If the Control Code field is zero (i.e., NUL operation) the command is accepted but
no action is taken.
• For all points, the only valid control is "Close - Pulse On" (41 hex). This is used to
initiate the function (e.g., Reset) associated with the point.
• Any value in the Control Code field not specified above is invalid and will be
rejected.
• The On Time and Off Time fields are ignored. A "Pulse On" control takes effect
immediately when received. Thus, the timing is irrelevant.
• The Status field in the response will reflect the success or failure of the control
attempt thus:
• A Status of "Request Accepted" (0) will be returned if the command was accepted.
• A Status of "Request not Accepted due to Formatting Errors" (3) will be returned if
the Control Code field was incorrectly formatted or an invalid Code was present in
the command.