Siemens 3VA1 100 A Manual page 310

Molded case circuit breakers
Hide thumbs Also See for 3VA1 100 A:
Table of Contents

Advertisement

Accessories
4.8 Residual current devices
Terminals
Note
Cables for the following terminals must be routed separately from the main circuits. Their
maximum cable length is 300 m.
A number of auxiliary contacts which perform different functions are located underneath a
contact hazard protective cover:
Alarm switches
TRIP-IND (TRIP INDICATOR)
A tripped signal can be output via the floating contact for display via a warning lamp, for
example. This trip alarm switch operates as soon as the residual current exceeds the
response current setting value and has therefore caused the residual current device to trip.
The standard trip alarm switch has changeover contacts and screw-type connections.
The terminal designations of the relevant contact are shown in the diagram below.
310
3VA molded case circuit breakers
Manual, 04/2015, A5E03603177010-02