Accessories

Bell Alarm With Lockout

The bell alarm with lockout module combines both the bell
alarm and a manual lockout function. The bell alarm switch
operates identically to the standard bel l a l a rm module,
except that the mech a n ical pop-out target must be manually
reset before the breaker can be closed.
Operation of the bell alarm with lockout module can be in­
dependently set by means of setting the DIP switches at the
rea r of the M icroVersaTrip P/usTM and PM™ trip un its. For the
Power+™ trip unit, the bell alarm with lockout module oper­
ates only when an overcurrent (including g round fault) trip
occurs. Current ratings of the single SPDT switch a re identical
to the bell a la rm module.
Bell alarm with mechanical reset lockout
Table 28.1
Bell Alarm with Lockout Module
Catalog Nu mber
AC Ratings
SPBAL240
6 A @ 240 Vac
SPBAL600 Q)
6 A @ 600 Vac
Q) 600 Vac module not UL listed

U ndervoltage Release Module

The undervoltage release is an e lectronic module used to
open the circuit b reaker when the monitored voltage d rops
below 3 5-60% of its rated value. The undervoltage release
"resets" when the mon itored voltage is re-esta blished allow­
ing the circuit b reaker to reclose (the sealing voltage of the
UVR is 60-85% of its rated voltage).
U n dervaltage release mod ule
28
An undervoltage release trip operation is produced by the
Power+, MicroVersaTrip Plus or MicroVersaTrip PM trip unit in
response to a signal from the undervoltage release module.
This a l lows the trip unit to record, display, distingu ish and
commun icate (in Mic roVersaTrip PM trip units) that the break­
er opening event was due to undervoltage release. Opera­
tion of the undervo/tage release module will prevent b reaker
contact closure, i.e. "kiss-free" o peration. When energized,
the undervo/tage release supplies +24 Vdc power to the Mi­
croVersaTrip Plus and PM trip un its to power the display.
The undervoltage release module is ava ilable in a wid e range
of control and power system voltages ranging from 1 2 Vdc
to 600 Vac. U ndervoltage release modules used with 480
Vac and 600 Vac control power a re supplied with a 5 0 VA
control power transformer which mou nts externally from the
b reaker. These transformers p rovide a n output of 120 Vac,
5 0/60 Hz. to the UVR modules. (See outl ine d rawings in Physi­
cal Data Section.)
Table 28.2
Undervoltage Release Module
Catalog
N u m ber
S PUV012DC
SPUV024DC
SPUV048DC
DC Ratings
S PUV125DC
0.5 A @ 125 Vdc
SPUVZSODC
0.25 A@ 250 Vdc
SPUV024AC
0.5 A @ 1 2 5 Vdc
S PU V048AC
0.25 A @ 250 Vdc
SPUV 120AC
S P UV208AC
S P UV240AC
SPUV480AC
S P UV600AC
Tim e Delay Mod u le for UVR
The time delay module prevents nuisance tripping d ue to
momentary loss of voltage. Cat. N o. SPUVTD has 0.1 to 1.0
seconds delay. The module has 120 Vac in put and 125 Vdc
output and must be used with the 125 Vdc UVR (Cat . No.
SPUV125DC).
Voltage Ratings
Peak i n rush
Cu rrent
Cu rrent
(50-60 Hz)
(Amps)
12 Vdc
1 6
24 Vdc
15
48 Vdc
75
1 2 5 Vdc
3
250 Vdc
1 . 5
24 Vac
15
48 Vac
7.5
120 Vac
3
208 Voc
1. 9
240 Vac
1.5
480 Vac
2
600 Vac
2
Nominal
I n put
zoo
(mAl
140
70
30
1 5
3 70
2 10
80
6 0
45
50
60