3.4.5.2.
24
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
Clicking Apply connects the data objects to the IED. The connected data objects appears
as child objects for the IED. The cross reference information can then be also modified
by selecting the data object and using the object properties window.
When configuring address values for DNP IED data objects,
the valid address range is 0 - 65535 . If the value is -1, then
the address is not available.
If you change the object names or structuring of objects of OPC Server, which are con-
nected to the IED, open the cross reference tool and verify that the changes are correctly
handled and then click Apply to update the configuration accordingly.
DNP OPC Client supports data objects for status, measurements, controllable status, and
controllable analog information. The following subsections list the configurable data
object properties for the DNP OPC Client.

Directional protection activation information (ACD)

Table 3.4.5.2-1 Configurable ACD properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
ACD
Class
Addresses
General Index
-1 to 65535
Default: -1
Neutral Index
-1 to 65535
Default: -1
Phase A Index
-1 to 65535
Default: -1
Phase B Index
-1 to 65535
Default: -1
Phase C Index
-1 to 65535
Default: -1
Data Class Spe-
cific
Description
Common data class according to IEC
61850.
General Index
Neutral Index
Phase A Index
Phase B Index
Phase C Index
1MRS755496