Configuring Data Objects; General About Configuring Data Objects; Lan/Wan Master (Opc); Directional Protection Activation Information (Acd) - ABB COM600 Station Automation Series User Manual

Dnp 3.0 lan/wan master opc 3.2
Hide thumbs Also See for COM600 Station Automation Series:
Table of Contents

Advertisement

DNP 3.0
LAN/WAN Master
(OPC) 3.2
3.4.8.
3.4.8.1.
3.4.8.2.
30
COM600 Station Automation Series
User's Guide

Configuring data objects

General about configuring data objects

Object properties of the data objects are listed in the following tables.
When configuring address values for DNP IED data objects, the valid address range is
0 to 65535. If the value is -1, then the address is not available.

Directional protection activation information (ACD)

Table 3.4.8.2-1 Configurable ACD properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
ACD
Class
Addresses
General Index
-1 to 65535
Default: -1
Neutral Index
-1 to 65535
Default: -1
Phase A Index
-1 to 65535
Default: -1
Phase B Index
-1 to 65535
Default: -1
Phase C Index
-1 to 65535
Default: -1
Data Class Spe-
cific
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Description
Common data class according to IEC
61850.
General Index
Neutral Index
Phase A Index
Phase B Index
Phase C Index
Object number for indication.
1MRS756566