ABB COM600 Station Automation Series User Manual page 35

Dnp 3.0 lan/wan master opc 3.2
Hide thumbs Also See for COM600 Station Automation Series:
Table of Contents

Advertisement

1MRS756566
COM600 Station Automation Series
User's Guide
Property/ Para-
Value or Value range/ Default
meter
Phase BC Index
-1 to 65535
Default: -1
Phase CA Index
-1 to 65535
Default: -1
Sub-Type
Subtype
DEL Simple
Data Class Spe-
cific
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Scale and Unit
Phase Multiplier
Default: Deka
Phase Number of
0 to 9
Decimals
Default: 0
Scale
Default: None
Unit
Default: Dimensionless
Table 3.4.8.8-2 Additional configurable properties for Sub-Type Limit Check
Property/ Para-
Value or Value range/ Default
meter
Sub-Type
DEL Full
Limit Value Super-
vision
High
Default: 0
High-High
Default: 0
Low
Default: 0
Low-Low
Default: 0
LAN/WAN Master
Description
Phase BC Index
Phase CA Index
DEL Subtype
Object number for indication.
Specifies the multiplier for current SI unit.
Specifies the number of decimals shown
in HSI.
Scale to be used with this type.
SI unit for measurement as described in
IEC61850
Description
Sub-type of current data object
High limit for measurement. Event is cre-
ated when value crosses the limit.
High-high limit for measurement. Event is
created when value crosses the limit.
Low limit for measurement. Event is cre-
ated when value crosses the limit.
Low-low limit for measurement. Event is
created when value crosses the limit.
DNP 3.0
(OPC) 3.2
35

Advertisement

Table of Contents
loading