COM600 Station Automation Series
User's Guide

Controllable double point (DPC)

Table 3.4.8.9-1 Configurable DPC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
DPC
Class
Addresses
Control Index Close
-1 to 65535
Default: -1
Control Index Open
-1 to 65535
Default: -1
Index 52a
-1 to 65535
Default: 11
Index 52b
-1 to 65535
Default: 12
Index BFI
-1 to 65535
Default: 12
Data Class Spe-
cific
Control Code Quali-
Momentary
fier
Latched
Pulsed
Default: Momentary
Control Object
Binary control output block
(12).
Control Variation
0 to 65535
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Operate
True
False
Default: True
Description
Common data class according to IEC
61850.
Index for Control Close command.
Index for Control Open command.
Index for 52a.
Index for 52b.
Index for Breaker Failure Indication.
Qualifier for control.
Object number for control.
Variation for control
Object number for indication.
DNP direct operate of SBO (function code
configuration).
1MRS756566