Controllable Double Point (Dpc) - ABB COM600 Series User Manual

Version 5.0, dnp 3.0 serial slave opc
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

1MRS755495
3.4.5.9.
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Time And Type
Send as static data (always
Variation
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event without time
Scale and Unit
Multiplier
1...1000000000
Default: 1

Controllable double point (DPC)

Table 3.4.5.9-1 Configurable DPC properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
DPC
Class
Addresses
Control Index
0...65535
Default: 0
Indication Index
0...65535
Default: 0
Common
Class
Class 0...3
Default: Class 0
Update Rate
0...65535
Default: 0
Data Class Spe-
cific
Control Object
Default: Binary control output
block (12).
Description
Specifies the type of the timestamp a
message is sent with.
Multiplier for scaling decimal values.
Description
Common data class according to IEC
61850.
Control index.
Indication index.
Class of ASDU. Data sent from the slave
to the master can be assigned to four
classes. Data in class 1 is sent with higher
priority than data in class 3.
Maximum update rate of signal state
changes between the OPC server and
client in milliseconds. 0 means that the
server sends all the changes to the client.
Object number for control.
37

Advertisement

Table of Contents
loading

Table of Contents