Double Point Status (Dps) - ABB COM600 Series User Manual

Version 5.0, dnp 3.0 serial slave opc
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

3.4.5.10.
38
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Send All Updates
True
False
Default: False
Send As Inverse
True
Value
False
Default: False
Send As Single
True
Point
False
Default: False
Time And Type
Send as static data (always
Variation
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event with time

Double point status (DPS)

Table 3.4.5.10-1 Configurable DPS properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
DPS
Class
Addresses
Indication Index
0...65535
Default: 0
Common
Description
Object number for indication.
Defines if all changes in value are sent to
the master.
Defines if the value of a message is
inverse.
Defines if a value is sent as single point.
Specifies the type of the timestamp a
message is sent with.
Description
Common data class according to IEC
61850.
Indication index.
1MRS755495