26
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Name
Value/Value range
Command Hand-
ling
Command Address
0...65535
Default: 32000
Execute Waiting
0...600
Time After Select
Default: 30
Lengths
Application Mes-
0...5
sage Data Retries
Default: 0
Information Address
1...2
Length
Default: 2
Maximum Message
249...2048
Length
Default: 2048
Time Handling
Time Synchroniza-
Handled, time set Positive
tion
acknowledged, time not set
Negative acknowledged, time
not set
Default: Handled, time set
Queues
Measurement
1...100
Queue Threshold
Default: 95
Measurement
0...65535
Update Queue
Default: 1000
State Indications
0...65535
Updates Queue
Default: 1000
Description
The object address of the bitstream pro-
cess object.
The maximum time in seconds that the
slave waits for an execute command after
receiving an operator command.
The maximum number of retransmissions
of an application data fragment.
The length of a data object address used
in the DNP 3.0 messages.
The maximum length of an application
data fragment.
Determines the behavior of the slave
device when it receives a time synchroniz-
ation message.
Defines a threshold (percent of the queue
capacity) which causes that update of a
measurement removes the oldest entry of
the same measurement from the queue.
Maximum number of measurement pro-
cess data changes that are stored intern-
ally in a queue in the client.
Maximum number of state indication pro-
cess data changes that are stored intern-
ally in a queue in the client.