1MRS755495
3.4.5.6.
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Send As 16 Bit
Send as 32 bit value
Value
Send as 16 bit value
Default: Send as 16 bit value
Send As Delta
Send as binary counter
Counter
Send as delta counter
Default: Send as delta counter
Time And Type
Send as static data (always
Variation
without time)
Event without time Event with
time
Event with relative time (valid
for binary inputs only)
Default: Event with time
Binary controlled step position information (BSC)
Table 3.4.5.6-1 Configurable BSC properties for OPC client
Property/ Parameter
Value or Value range/
Default
Basic
Common Data Class
BSC
Addresses
Control Index
0...65535
Default: 0
Indication Index
0...65535
Default: 0
Common
Class
Class 0...3
Default: Class 0
Update Rate
0...65535
Default: 0
Data Class Specific
Description
Defines if the value is sent as 16 or 32 bit
value.
Defines if the value is sent as delta or
binary counter.
Specifies the type of the timestamp a
message is sent with.
Description
Common data class according to IEC 61850.
Control index.
Indication index.
Class of ASDU. Data sent from the slave to the
master can be assigned to four classes. Data
in class 1 is sent with higher priority than data
in class 3.
Maximum update rate of signal state changes
between the OPC server and client in milli-
seconds. 0 means that the server sends all the
changes to the client.
33