1MRS752278
3.4.7.4.
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Subtype of the
current data
object: Same com-
mand and indica-
tion addresses
Addresses
Command ASDU
0...255
Type
Default: 20
Command Function
0...255
Type
Default: 101
Command Informa-
0...255
tion Number
Default: 105
Subtype of the
current data
object: Separate
command and
indication
addresses
Addresses
Command ASDU
0...255
Type
Default: 20
Command Function
0...255
Type
Default: 101
Command Informa-
0...255
tion Number
Default: 105
Indication Function
0...255
Type
Default: 101
Indication Informa-
0...255
tion Number
Default: 105
Binary controlled step position information (BSC)
Table 3.4.7.4-1 Controllable BSC properties for OPC servers
Property/ Para-
Value or Value range/ Default
meter
Basic
Description
IEC103 command ASDU type
IEC103 command function type
IEC103 command information number
IEC103 command ASDU type
IEC103 command function type
IEC103 command information number
IEC103 indication function type
IEC103 indication information number
Description
37