Iec103 Device Attributes - ABB COM600 series User Manual

Substation management unit
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

5.3.4.
52
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
Name
Value or Value range/ Default
Received telegrams
Parity errors
Overrun errors
Checksum errors
Framing errors
Buffer overflow
errors

IEC103 Device attributes

Table 5.3.4-1 IEC103 Device attributes
Name
Value or Value range/ Default
In use
0 = Out of use
1 = In use
Default: 1
Description
Incremented each time a telegram is
received by the IEC103 OPC Server from
the IEC103 channel.
Incremented each time a parity error is
detected in a message received from the
IEC103 channel.
Incremented each time an overrun error
is detected in a message received from
the IEC103 channel.
Incremented each time a checksum error
is detected in a message received from
the IEC103 channel.
Incremented each time a framing error is
detected in a message received from the
IEC103 channel.
Incremented each time a buffer overflow
occurs in the IEC103 channel.
Description
Data type: Integer
Access: No limitations
The operational status of the device - in
use or out of use. Taking the device out
of use with this attribute stops all data
communication with the device. All opera-
tions that would result in data exchange
are disabled. The device itself is not
affected by the attribute, only the protocol
stack's image of the device. Setting IU to
1 is allowed only if the device address is
legal.