1MRS752278
COM600 series, Version 5.0
IEC 60870-5-103 Master (OPC) User's Manual
Name
Value or Value range/ Default
Receiver Interrupt
0...255
Delay
Default: 0
Response Timeout
0...65535
Default: 2
RTS Keep Up
0...255
Default: 0
RTS Keep Up Delay
0...20
Default: 1
Time Synchroniza-
0...65535
tion Interval
Default: 15
Transmission Wait
0...65535
Delay
Default: 0
Polling
Enquiry Limit
0...255
Default: 3
One link, one station
True
poll
False
Default: False
Polling Delay
0...65535
Default: 50
Polling Limit
2...100
Default: 10
Polling Period
1...255
Default: 10
Reply Poll Count
1...20
Default: 10
Secondary Polling
0...100
Limit
Default: 0
Description
Delay of the receiving activation in milli-
seconds
Maximum waiting time of a link layer
response in seconds
RTS keep up padding characters
Keep up delay of the RTS
Time synchronization interval in seconds
Transmission wait delay after given CTS
in milliseconds
Number of times that a message is
retransmitted.
One link, one station poll. If true, master
infinitely polls the first link which responds
(typically used with dial-up). If false, all the
links are polled normally.
Delay between polling messages in milli-
seconds
Limits the number of successive polls of
a device.
The polling frequence of a suspended
station
The reply polling specifies the number of
successive polls to a station where a
command has been sent.
Limits the number of successive class 2
polls of a device. The value must be
smaller than the value of Polling Lmit.
23