3.4.5.19.
50
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Time and Type Variation

Enumerated Status (ENS)

Table 3.4.5.19-1 Configurable ENS properties for OPC client
Property/Parameter
Basic
Common Data Class
Addresses
Indication Index
Common
Class
Update Rate
Data Class Specific
Indication Object
Send All updates
Send as static data (always
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event with time
Value or Value range/ Default
ENS
-1...65535
Default: -1
Class 0...3
Default: Class 0
0...65535
Default: 0
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
True
False
Default: False
1MRS755495
Specifies the type of the
timestamp a message is sent
with.
Description
Common data class according
to IEC 61850.
Indication index.
Data sent from the slave to the
master can be assigned to four
classes. Data in class 1 is sent
with higher priority than data in
class 3.
Maximum update rate of signal
state changes between the
OPC server and client in milli-
seconds. 0 means that the
server sends all changes to the
client.
Object number for indication.
Defines if all changes in value
are send to the master.

Advertisement