ABB COM600 Series User Manual page 85

Version 5.0, dnp 3.0 serial slave opc
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

1MRS755495
Timeouts while waiting for:
[x] Never
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES
ONLY:
Reports Binary Input Change Events when no specific
variation requested:
[ ] Never
[ ] Only time-tagged
[ ] Only non-time-tagged
[x] Configurable to send one or the other, depends on data
point initialization.
Sends Unsolicited Responses:
[ ] Never
[x] Configurable, depends on data point initialization
[ ] Only certain objects
[ ] Sometimes (attach explanation)
[x] ENABLE/DISABLE UNSOLICITED function codes suppor-
ted
Default Counter Object/ Variation:
[ ] No Counters Reported
[x] Configurable, depends on data point initialization
[ ] Default Object________________________
[ ] Default Variation______________________
[ ] Point-by-point list attached
Sends Multi-Fragment Responses:
[x] Yes
[ ] No
CODE
Transfer Function Codes
0
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
[ ] Always
[ ] Sometimes
Table A1-5 Supported function codes
FUNCTION
DESCRIPTION
Confirm
Message fragment confirmation
No response
[ ] Configurable
Reports time-tagged Binary Input Change Events when
no specific variation requested:
[ ] Never
[ ] Binary Input Change With Time
[ ] Binary Input Change With Relative Time
[x] Configurable, depends on data point initialization.
Sends Static Data in Unsolicited Responses:
[x] Never
[ ] When Device Restarts (depends on data point initialization)
[ ] When Status Flags Change (depends on data point initializ-
ation)
No other options are permitted
Counters Roll Over at:
[ ] No Counters Reported
[ ] Configurable (attach explanation)
[ ] 16 bit
[x] 32 Bits, roll-over bits not set
[ ] Other Value__________________________________
[ ] Point-by-point list attached
Supported
Yes
85

Advertisement

Table of Contents
loading

Table of Contents