Controllable Double Point (Dpc); Controllable Integer Status (Inc); Binary Controlled Step Position Information (Bsc) - ABB COM600 Station Automation Series User Manual

Dnp 3.0 lan/wan master opc 3.2
Hide thumbs Also See for COM600 Station Automation Series:
Table of Contents

Advertisement

DNP 3.0
LAN/WAN Master
(OPC) 3.2
5.2.15.
Name
Type
stVal
BOOLEAN
ctlOperOn
BOOLEAN
ctlOperOff
BOOLEAN
ctlSelOn
BOOLEAN
ctlSelOff
BOOLEAN
ctlCan
BOOLEAN
stSelt
BOOLEAN
q
Quality
t
TimeStamp
d
Description
5.2.16.
Name
Type
ctlVal
INTEGER
stVal
BOOLEAN
q
Quality
t
TimeStamp
d
Description
5.2.17.
Name
Type
ctlVal
ENUMERATED
valWTr
ValWithTrans
62
COM600 Station Automation Series
User's Guide

Controllable double point (DPC)

Value/Value range
FALSE | TRUE
FALSE | TRUE
FALSE | TRUE
FALSE | TRUE
FALSE | TRUE
FALSE | TRUE
FALSE | TRUE
Text

Controllable integer status (INC)

Value/Value range
-
FALSE | TRUE
Text

Binary controlled step position information (BSC)

Value/Value range
stop (0) | lower (1)
| higher (2) |
reserved (3)
Mandat-
DNP data object
ory/Optional
field
M
State (0:OFF,
1:ON)
O
Control Code
O
Control Code
O
Control Code
O
Control Code
O
-
O
Control Code
M
DNP status
M
<server provided if
none> | Time of
occurrence | MSEC
O
-
Mandat-
DNP data object
ory/Optional
field
M
Control Code
M
Current Value
M
DNP status
M
<server provided if
none> | Time of
occurrence | MSEC
O
-
Mandat-
DNP data object
ory/Optional
field
M
Control Code
M
State
1MRS756566
OPC data types
VT_BOOL
VT_BOOL
VT_BOOL
VT_BOOL
VT_BOOL
VT_BOOL
VT_BOOL
VT_I4
VT_DATE
VT_BSTR
OPC data types
VT_I4
VT_I4
VT_I4
VT_DATE
VT_BSTR
OPC data types
VT_I1
VT_I4

Advertisement

Table of Contents
loading

Table of Contents