Configuring Dnp Opc Server Properties; Configuring Dnp Opc Server Lan Channel Properties - ABB COM600 Station Automation Series User Manual

Dnp 3.0 lan/wan master opc 3.2
Hide thumbs Also See for COM600 Station Automation Series:
Table of Contents

Advertisement

1MRS756566
3.4.2.
3.4.3.
COM600 Station Automation Series
User's Guide

Configuring DNP OPC Server properties

Table 3.4.2-1 DNP OPC Server properties
Property/Parameter
Basic
Prog ID AE
Prog ID DA

Configuring DNP OPC Server LAN Channel properties

The DNP OPC Server LAN Channel properties that can be configured and value ranges
for them can be found in Table 3.4.3-1. The actual configuration by using Communication
Engineering Tool (CET) is performed as described in 3.4.1, General about configuring
objects.
Table 3.4.3-1 DNP LAN Channel properties
Property/Parameter
Basic
In use
Communication Port
Local Address
Communication Control
Check Connection Request
Connection timeout
Connection Type
Value or Value range/Default
Value or Value range/Default
In Use
Not In Use
Default: In Use
127.0.0.1
True
False
Default: True
0 to 65535
Default: 500
TCP/IP
UDP/IP
Default: TCP/IP
DNP 3.0
LAN/WAN Master
(OPC) 3.2
Description
Instance identification of dia-
gnostic OPC alarm and event
server.
Instance identification of dia-
gnostic OPC data access
server.
Description
Specifies if channel is in use or
not.
IP address of Ethernet interface
in COM610.
Specifies if incoming connec-
tion requests are checked.
Maximum time in milliseconds
of the TCP connect operation.
Connectin protocol used.
23

Advertisement

Table of Contents
loading

Table of Contents