Property/Parameter
Header Timeout
Link Layer Confirmations
Enabled
Maximum Message Length
Maximum Random Delay for
Retransmission
Polling Period
ResponseTimeout
Test Function for Link
Test Function for Link Interval

Configuring DNP LAN Device

Table 3.4.4-1 lists the configurable properties for DNP Devices and value ranges for
these properties. The actual configuration by using Communication Engineering Tool
(CET) is performed as described in 3.4.1, General about configuring objects.
Table 3.4.4-1 DNP LAN IED properties
Name
Value or Value range/ Default
Basic
Diagnostics enabled
True
False
Default: False
Value or Value range/Default
0 to 65535
Default: 2000
Not In Use
In Use
Default: In Use
50 to 249
Default: 230
0 to 65535
Default: 0
0 to 255
Default:10
0 to 255
Default: 15
True
False
Default: False
0 to 65535
Default: 20
Description
Diagnostics Enabled
1MRS756566
Description
Maximum wait time in milli-
seconds within which the first
byte of a link layer response
should have been received.
Specifies whether the link layer
confirmations are in use.
Maximum length of a data
fragment.
Delay in milliseconds between
retransmissions.
Data polling period.
The time in milliseconds that
DNP3.0 link waits for received
message.
Specifies if 'Test Function for
Link' is enabled.
Delay in milliseconds between
test fuction of link commands.
If value is zero (0), the test
function of link command is not
sent.