Siemens SIMATIC S7-1500 Manual page 48

Technology module tm pto 4
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

Interrupts/diagnostic alarms
5.2 Diagnostic alarms
Diagnostic alarms
The diagnostics are displayed as plain text in STEP 7 (TIA Portal) in the online and
diagnostics view. You can evaluate the error codes with the user program. The respective
channel number is shown for each diagnostic information.
The following diagnostics can be signaled:
Table 5- 5
Diagnostic alarms, their meaning and remedies
Diagnostic alarm
Error
code
Parameter as-
10
H
signment error
Supply voltage
11
H
missing
Internal error
100
Watchdog tripped.
103
Module is defec-
tive.
Error at the digital
10F
outputs
1,2
Digital outputs DQ0.0, DQ0.1, DQ1.0 and DQ1.1 have shared diagnostics. Digital outputs DQ2.0, DQ2.1, DQ3.0 and
1
DQ3.1 have shared diagnostics.
Diagnostics for short-circuit and overload are effective only for 24 V outputs and only up to an output frequency of ap-
2
proximately 100 Hz. The module is otherwise protected from irrevocable damage caused by short-circuit at the outputs,
and the diagnostic alarm is not displayed.
Cross-channel diagnostics of the digital outputs
The digital outputs of channels 0 and 1 as well as channels 2 and 3 have shared
diagnostics. As a result, when there is an error at one digital output, faults are automatically
signaled for
Ensure that this fault scenario is taken into consideration when using multiple channels.
48
Meaning
Received parameter data record invalid
Undervoltage
Wiring of supply voltage L+ faulty
Supply voltage L+ of the technology module
missing
Front connector not inserted correctly
Technology module defective
H
Firmware error
H
Technology module defective
Error at the digital outputs (LED display
H
DQn.m lights up red)
Possible causes:
Short-circuit
Overload
CAUTION
two
channels and the pulse output of both channels is stopped.
To correct or avoid errors
Check parameter data record
Check supply voltage L+
Check wiring of supply voltage L+
Feed supply voltage L+ to the technology
module via terminal 41
Insert front connector correctly
Replace technology module
Run firmware update
Replace technology module
Correct wiring at the digital outputs
Check consumers connected to the
digital outputs
Technology Module TM PTO 4 (6ES7553-1AA00-0AB0)