Panasonic S-200PE2E5 Technical Data & Service Manual

Panasonic S-200PE2E5 Technical Data & Service Manual

Dc inverters
Table of Contents

Advertisement

Order No. SBPAC1607004CE
TECHNICAL DATA & SERVICE MANUAL
Indoor Unit
Outdoor Unit
High Static Pressure
4-Way Cassette Type
Ducted Type
Type E2
S-200PE2E5, S-250PE2E5
Type U2
S-100PU2E5A, S-125PU2E5A
U-200PE2E8A, U-250PE2E8A
SM830252-01
.
REFERENCE NO
85464849352001
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk

Advertisement

Table of Contents
loading

Summary of Contents for Panasonic S-200PE2E5

  • Page 1 Order No. SBPAC1607004CE TECHNICAL DATA & SERVICE MANUAL Indoor Unit Outdoor Unit High Static Pressure 4-Way Cassette Type Ducted Type Type E2 S-200PE2E5, S-250PE2E5 Type U2 S-100PU2E5A, S-125PU2E5A U-200PE2E8A, U-250PE2E8A SM830252-01 REFERENCE NO 85464849352001 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 2 IMPORTANT! • Provide a power outlet to be used exclusively for each unit. Please Read Before Starting • Provide a power outlet exclusively for This air conditioner must be installed by the sales dealer each unit, and full disconnection means or installer.
  • Page 3 …In a Snowy Area (for Heat Pump- • Keep your fingers and clothing away type Systems) from any moving parts. Install the outdoor unit on a raised • Clean up the site after you finish, platform that is higher than drifting snow. remembering to check that no metal Provide snow vents.
  • Page 4: Check Of Density Limit

    Check of Density Limit The standards for minimum room volume are as follows. (1) No partition (shaded portion) The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its density will not exceed a set limit. The refrigerant (R410A), which is used in the air conditioner, is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws imposed to protect the ozone layer.
  • Page 5: Table Of Contents

    —— CONTENTS —— Section 1. SPECIFICATIONS ....................1-1. Unit Specifications ....................... 1-2. Major Component Specifications ..................1-3. Other Component Specifications ..................1-12 1-4. Dimensional Data ....................... 1-14 1-5. Refrigerant Flow Diagram ....................1-18 1-6. Operating Range ........................ 1-20 1-7. Capacity Correction Graph According to Temperature Condition ........ 1-21 1-8.
  • Page 6 Section 7. REMOTE CONTROLLER FUNCTIONS SECTION..........7-1. Simple Settings Function ....................7-2. List of Simple Setting Items....................7-3. Detailed Settings Function ....................7-4. List of Detailed Setting Items ....................7-5. Simple Setting Items ......................7-11 7-6. Detailed Setting Items ......................7-13 7-7.
  • Page 7 1. SPECIFICATIONS 1-1. Unit Specifications..................... 1-2. Major Component Specifications ................1-3. Other Component Specifications ................1-12 1-4. Dimensional Data ..................... 1-14 1-5. Refrigerant Flow Diagram ..................1-18 1-6. Operating Range ...................... 1-20 1-7. Capacity Correction Graph According to Temperature Condition ..... 1-21 1-8.
  • Page 8: Unit Specifications

    Single-Type 1-1. Unit Specifications High Static Pressure Ducted Type S-200PE2E5 / U-200PE2E8A INDOOR MODEL S-200PE2E5 PANEL MODEL OUTDOOR MODEL U-200PE2E8A Branch pipe MODEL Performance test condition ISO13253 / EN14511 / EN12102 Ø, Hz 1Ø 50Hz 3Ø 50Hz Power supply 220V...
  • Page 9 Single-Type High Static Pressure Ducted Type S-250PE2E5 / U-250PE2E8A INDOOR MODEL S-250PE2E5 PANEL MODEL OUTDOOR MODEL U-250PE2E8A Branch pipe MODEL Performance test condition ISO13253 / EN14511 / EN12102 Ø, Hz 1Ø 50Hz 3Ø 50Hz Power supply 220V 230V 240V 380V 400V 415V 25.0...
  • Page 10 Twin-Type 4-Way Cassette Type S-100PU2E5A ×2 / U-200PE2E8A INDOOR MODEL S-100PU2E5A×2 PANEL MODEL Standard type: CZ-KPU3 / ECONAVI type: CZ-KPU3A OUTDOOR MODEL U-200PE2E8A Branch pipe MODEL Performance test condition ISO5151 / EN14511 / EN12102 Ø, Hz 1Ø 50Hz 3Ø 50Hz Power supply 220V 230V...
  • Page 11 Twin-Type 4-Way Cassette Type S-125PU2E5A ×2 / U-250PE2E8A INDOOR MODEL S-125PU2E5A×2 PANEL MODEL Standard type: CZ-KPU3 / ECONAVI type: CZ-KPU3A OUTDOOR MODEL U-250PE2E8A Branch pipe MODEL Performance test condition ISO5151 / EN14511 / EN12102 Ø, Hz 1Ø 50Hz 3Ø 50Hz Power supply 220V 230V...
  • Page 12: Major Component Specifications

    1-2. Major Component Specifications (A) Indoor Units High Static Pressure Ducted Type S-200PE2E5 MODEL No. S-200PE2E5 Source 220 - 230 - 240V, single-phase, 50Hz Controller P.C.B. Ass'y CR-280ME2E5 Fan (Number...diameter) SIROCCO (2...ø250) Fan motor DMUB6D1AC...560W Model...Nominal output DMUB6D2AC...560W Power source 100 - 391 VDC No.
  • Page 13 (A) Indoor Units High Static Pressure Ducted Type S-250PE2E5 MODEL No. S-250PE2E5 Source 220 - 230 - 240V, single-phase, 50Hz Controller P.C.B. Ass'y CR-280ME2E5 Fan (Number...diameter) SIROCCO (2...ø250) Fan motor DMUB8D1AC...560W Model...Nominal output DMUB8D2AC...560W Power source 100 - 391 VDC No.
  • Page 14 (A) Indoor Units 4-Way Cassette Type S-100PU2E5A MODEL No. S-100PU2E5A Source 220 - 230 - 240 V, single-phase, 50 Hz Controller P.C.B. Ass'y ACXA73-02060(Microprocessor) Fan (Number...diameter) Turbo (1...ø485) Fan motor Model...Nominal output SIC-72FW-D895-1…90W Power source 280 VDC No. of pole...r.p.m. (230V, High) 8P…600 VAC, F Run capacitor...
  • Page 15 (A) Indoor Units 4-Way Cassette Type S-125PU2E5A MODEL No. S-125PU2E5A Source 220 - 230 - 240 V, single-phase, 50 Hz Controller P.C.B. Ass'y ACXA73-02060(Microprocessor) Fan (Number...diameter) Turbo (1...ø485) Fan motor Model...Nominal output SIC-72FW-D895-1…90W Power source 280 VDC No. of pole...r.p.m. (230V, High) 8P…620 VAC, F Run capacitor...
  • Page 16 (B) Outdoor Units U-200PE2E8A MODEL No. U-200PE2E8A Source 380/400/415V 3-Phase 50Hz Controller P.C.B. Ass'y ACXA73C07280 Control circuit fuse Compressor Model..number 5JD650XDB22 Source 520V DC MOTOR Nominal output 4,200 Compressor oil 2,050 Coil resistance Ω U-V 0.678  U-W 0.700  V-W 0.691 (Ambient temperature 25°C) Safety control Discharge temperature control Overload relay models –...
  • Page 17 (B) Outdoor Units U-250PE2E8A MODEL No. U-250PE2E8A Source 380/400/415V 3-Phase 50Hz Controller P.C.B. Ass'y ACXA73C07260 Control circuit fuse Compressor Model..number 5JD650XDB22 Source 520V DC MOTOR Nominal output 5,500 Compressor oil 2,050 Coil resistance Ω U-V 0.678  U-W 0.700  V-W 0.691 (Ambient temperature 25°C) Safety control Discharge temperature control Overload relay models –...
  • Page 18: Other Component Specifications

    1-3. Other Component Specifications Outdoor Units U-200PE2E8A MODEL No. Outdoor Unit U-200PE2E8A Power Transformer Rated – Source VAC, Hz – – Secondary – Coil resistance Ω – – Thermal cut off temperature Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 Resistance kΩ...
  • Page 19 Outdoor Units U-250PE2E8A MODEL No. Outdoor Unit U-250PE2E8A Power Transformer Rated – Source VAC, Hz – – Secondary – Coil resistance Ω – – Thermal cut off temperature Thermistor (Coil / Air sensor): TH1, TH2, TH3, TH4 Resistance kΩ -20°C: 38.48±2%     20°C: 6.517±2% -10°C: 23.67±2%     30°C: 4.448±2% 0°C: 15.00±2%     40°C: 3.100±2% 5°C: 12.06±2%     45°C: 2.607±2%...
  • Page 20: Dimensional Data

    1-4. Dimensional Data (A) Indoor Units: High Static Pressure Ducted Type Required Minimum Space for Installation and Service (1) Dimensions of suspension bolt pitch and unit Unit: mm 1170 (Suspension bolt pitch) (60) (60) 1100 Inspection access (600 × 600)(Field supply) * Space for removing Min.
  • Page 21 Dimensional Data (A) Indoor Units: 4-Way Cassette Type Indoor Units: S-100PU2E5A / S-125PU2E5A / S-140PE2U5A S-100PU2E5A / S-125PU2E5A unit: mm 860~910 (Ceiling opening dimensions) (Suspension bolt pitch) Less than 35 Less than 35 (Air intake) Less than 300 View X View XX Raise dimension of drain tube 4 - M4...
  • Page 22 (B) Outdoor Unit: U-200PE2E8A Unit: mm Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), Air intake flared connection (ø9.52) Refrigerant tubing (gas tube), (10) flared connection (ø19.05) *1 Refrigerant tubing port Electrical wiring port (ø13) Electrical wiring port (ø22) Air intake Electrical wiring port (ø27) Electrical wiring port (ø35)
  • Page 23 (B) Outdoor Unit: U-250PE2E8A Unit: mm Mounting hole (4-R6.5), anchor bolt : M10 Refrigerant tubing (liquid tube), Air intake flared connection (ø12.7) (10) Refrigerant tubing (gas tube), flared connection (ø19.05)* Refrigerant tubing port Electrical wiring port (ø13) Electrical wiring port (ø22) Air intake Electrical wiring port (ø27) Electrical wiring port (ø35)
  • Page 24: Refrigerant Flow Diagram

    1-5. Refrigerant Flow Diagram Cooling cycle Heating cycle Outdoor Unit : U-200PE2E8A Indoor Unit : S-200PE2E5 High pressure switch Gas line 4-way valve service valve Ø 25.4 Oil separater Brazing connection Muffler Strainer Outdoor-air Suction Temp Temp Thermistor Thermistor Capillary tube...
  • Page 25 Cooling cycle Heating cycle Outdoor Unit : U-200PE2E8A Indoor Unit : S-100PU2E5A×2 High pressure switch Gas line 4-way valve service valve Ø 25.4 Oil separater Brazing connection Muffler Strainer Outdoor-air Suction Temp Temp Thermistor Thermistor Capillary tube Heat exchanger Temp Thermistor Heat Heat exchanger...
  • Page 26: Operating Range

    1-6. Operating Range S-200PE2E5 ─ U-200PE2E8A S-250PE2E5 ─ U-250PE2E8A Temperature Indoor air intake temp. Outdoor air intake temp. Maximum 32°C DB 46°C DB Cooling Minimum 18°C DB -15°C DB Maximum 30°C DB 24°C DB Heating Minimum 16°C DB -20°C DB S-100PU2E5A ×2 ─...
  • Page 27: Capacity Correction Graph According To Temperature Condition

    1-7. Capacity Correction Graph According to Temperature Condition U-200PE2E8A / U-250PE2E8A (For 50 Hz) Cooling capacity ratio (maximum capacity) Heating capacity ratio (maximum capacity) Indoor air intake temp (WB) °C Indoor air intake temp ( °C °C °C 22WB 19WB 16WB °C Indoor air intake temp (WB)
  • Page 28 U-200PE2E8A Rated capacity ratio for cooling Rated capacity ratio for heating 136% 133% Capacity (W) Capacity (W) U-250PE2E8A Rated capacity ratio for cooling Rated capacity ratio for heating 134% 135% Capacity (W) Capacity (W) NOTE 2 1. The graphs " "...
  • Page 29: Noise Criterion Curves

    1-8. Noise Criterion Curves High Static Pressure Ducted Type HIGH MODEL : S-200PE2E5 : S-250PE2E5 MODEL SOUND LEVEL : HIGH 43 dB(A) SOUND LEVEL : HIGH 47 dB(A) 38 dB(A) 42 dB(A) CONDITION : Under the unit 1.5 m CONDITION : Under the unit 1.5 m...
  • Page 30 COOLING HEATING : U-200PE2E8A : U-200PE2E8A MODEL MODEL SOUND LEVEL : 60 dB(A) SOUND LEVEL : 62 dB(A) CONDITION : 1 m in front at height of 1.5 m CONDITION : 1 m in front at height of 1.5 m NC-70 NC-70 NC-60...
  • Page 31: Airflow Distance Chart

    1-9. Airflow Distance Chart 4-Way Cassette (Type U2) S-100PU2E5A / 125PU2E5A Heating : Distribution of wind velocity (Strong wind : Discharge angle approx.65°) (Room temperature approx.20°C) 1.5m/s 1.0m/s 0.5m/s 0.3m/s Horizontal air flow distance (m) Heating : Distribution of temperature (Strong wind : Discharge angle approx.65°) (Room temperature approx.20°C) Horizontal air flow distance (m)
  • Page 32: Fresh Air Intake

    1-10. Fresh Air Intake 1-10-1. Precautions Regarding External Air Intake (1) Ventilation Load Ensure that the design of the air-conditioner takes air-conditioning loads into consideration when external air intake is involved. (2) Restrictions on External Air Intake Ensure that the design conforms to the restrictions on air intake volume stipulated in accordance with the model of the indoor unit and the intake method.
  • Page 33 1-10-2. External Air Intake Volume & Resistance Within Unit / Operation Noise Characteristics • 4-Way Cassette (Type U2) When an External Air Intake Flange (ø100) is in Use External Air Intake Volume and Resistance and With the External Air Intake Flange Attached Operation Noise Characteristics within the Unit Type U2 Duct (ø100) for Connecting...
  • Page 34: Electrical Wiring

    1-11. ELECTRICAL WIRING General Precautions on Wiring Before wiring, confirm the rated voltage of the unit as shown on its nameplate, then carry out the wiring closely following the wiring diagram. WARNING This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD).
  • Page 35 Wiring System Diagrams <Type E2> Indoor unit Power supply Outdoor unit 220/230/240V ~ 50 Hz INV unit Power supply Ground Remote 380/400/415V, 3 N~, 50 Hz controller Ground (SG: Shows the ground for the shielded cable.) <Type U2> Indoor unit (No.
  • Page 36 CAUTION (1) When linking the outdoor units in a network, disconnect the terminal extended from the short plug from all outdoor units except any one of the outdoor units. (When shipping: In shorted condition.) For a system without link (no wiring connection between outdoor units), do not remove the short plug. (2) Do not install the inter-unit control wiring in a way that forms a loop.
  • Page 37 How to connect wiring to the terminal For stranded wiring (1) Cut the wire end with cutting pliers, Stranded wire Special Screw then strip the insulation to expose washer the stranded wiring about 10 mm and Ring pressure tightly twist the wire ends. (Fig. 1-5) Ring pressure terminal Screw and...
  • Page 38 This air conditioner must be installed in accordance with national wiring regulations. Cables connected to outdoor unit must be approved polychloroprene sheathed type 60245 IEC 57 or H05RN-F/H07RN-F or heavier. The units must be connected to the supply cables for fi xed wiring by qualifi ed technician. Circuit breaker must be incorporated in the fixed wiring in accordance with the national wiring regulations.
  • Page 39 OUTDOOR UNIT/3-PHASE MODEL Power supply (220/230/240V~) Power supply (380/400/415V 3N~) c r i c r i Switch Switch Earth Control cable Earth Wired remote Indoor unit Outdoor unit controller This equipment complies with EN/IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equals to 1850 kVA at the interface point between the user’s supply and the public system.
  • Page 40: Installation Instructions

    1-12. Installation Instructions Outdoor Unit Tubing Length (A) Single type During tubing work, try to make both the tubing length (L) Single and the difference in elevation (H1) as short as possible. Refer to Table 1-1. Main tubing L Table 1-1 Tubing Data for Models (Single) Models U-200PE2E8A U-250PE2E8A...
  • Page 41 TWIN, TRIPLE AND DOUBLE TWIN TYPE CONNECTIONS Two, three or four indoor units can be operated simultaneously with a single remote control unit. Note that individual operation is not possible. Master unit and slave unit can be set automatically in twin and triple system.No address setting is necessary. Applicable “TWIN”...
  • Page 42: Check Of Limit Density

    2. Check of limit density When installing an air conditioner in a room, it is Minimum indoor volume & fl oor area relative to the necessary to ensure that even if the refrigerant gas amount of refrigerant are roughly as given in the accidentally escapes, its density does not exceed the following table.
  • Page 43: Optional Distribution Joint Kits

    Optional Distribution Joint Kits CZ-P155BK1: Cooling capacity after distribution is 16.0 kW (54,600 BTU/h) or less. CZ-P680BK2: Cooling capacity after distribution is more than 16.0 kW (54,600 BTU/h) and less than 68.0 kW (232,000 BTU/h). CZ-P3HPC2: Cooling capacity after distribution is 28.0 kW (95,500 BTU/h) or less. Distribution Branch Size ( 1, 2, 3, 4, ) Unit: mm (in.) Indoor Unit...
  • Page 44 I nstalling Distribution Joint Kit (for Twin & Double-Twin) (CZ-P155BK1 & CZ-P680BK2) For branching tubes, install 150 mm or longer (including Horizontal installation reducer) straight tubing up to the point where the tube Horizontal line branches (or after the point where the tubes join together). indoor unit side Outdoor unit side 150 mm or longer straight tubing up...
  • Page 45 Installing Distribution Joint Kit (for Triple) (CZ-P3HPC2) Check the system combination before installing the distribution joints. Three indoor units must be installed within the same room. Use the supplied tube connectors to adjust the tube sizes of the distribution joints. How to Install Distribution Joints Use the supplied distribution joints to complete refrigerant tubing Distribution joint insulation material (supplied)
  • Page 46: Selecting The Installation Site

    3. SELECTING THE INSTALLATION SITE The following parts are supplied as accessories with each outdoor unit. Check that all accessory parts are present before installing the outdoor unit. Part name Diagram Quantity Part name Diagram Quantity Protective bushing Joint piping A (ø19.05 → ø25.4) (for protecting electrical wires) Banding strap Joint piping B (ø19.05)
  • Page 47 4. INSTALLATION SERVICE SPACE Please secure necessary space to guarantee performance and service & maintenance. For multiple installations, please secure enough space to enable removal of side face screws between units. (unit: mm) Where there are obstacles at the intake Where there are obstacles at the discharge If upper part is open If upper part is open...
  • Page 48: Transport And Install The Outdoor Unit

    5. TRANSPORT AND INSTALL THE OUTDOOR UNIT Transporting 1. Transport the outdoor unit in its original packaging as close as possible to the installation More than 40mm location. 2. In the event that the unit needs to be lifted or suspended, use a rope or belt and use cloth or wood as padding to avoid damaging the unit.
  • Page 49: Refrigerant Installation

    For indoor unit refrigerant piping installation, refer to the installation 6. REFRIGERANT INSTALLATION instruction manual that comes with that indoor unit. Do not reuse existing piping, install new piping. 1. Precautions during refrigerant installation. Use clean pipes with no dust inside. The pipe may corrode with the presence of fl...
  • Page 50 Precautions when operating the 3-way valve for piping installation Do not open the 3-way valve until the piping installation is completed. • It is closed during shipment. • During installation the side panel may warp if only the fl are nut is loosened and tightened with a torque wrench. As a result, always be sure to secure to the hexagonal part of the 3-way valve with a spanner, or other tool.
  • Page 51 Precautions for insulation installation Maximum temperature limit of gas or liquid piping exceeds 120 °C In high humidity environment, reinforce the insulation material for the refrigerant piping. Failure to do so may result in condensation on the surface of the insulation material. Use materials with good heat-resistant properties as the heat insulator for the pipes.
  • Page 52 SELECTING THE LOCATION FOR When installing multiple units, allow enough space in between the units and the side of the building. INSTALLATION SERVICE (unit: mm) Example of connecting pipe process (1) Front mounting (2) Right mounting / flare processing Flare processing Flare processing Joint...
  • Page 53: Selecting The Installation Site

    Indoor Unit Type E2 8. SELECTING THE INSTALLATION SITE CAUTION When moving the unit during or after unpacking, make sure to lift it by holding its lifting lugs. Do not exert any pressure on other parts, especially the refrigerant piping, drain piping and flange parts. If you think the humidity inside the ceiling might exceed 30°C and RH 80%, reinforce the insulation on the unit body.
  • Page 54: How To Install The Indoor Unit

    9. HOW TO INSTALL THE INDOOR UNIT High Static Pressure Ducted Type (Type E2) 9-1. Required Minimum Space for Installation and Service (1) Dimensions of suspension bolt pitch and unit Unit: mm 1170 (Suspension bolt pitch) (60) (60) 1100 Inspection access (600 × 600)(Field supply) * Space for removing Min.
  • Page 55 9-2. Suspending the Indoor Unit Depending on the ceiling type: 1. Check the suspension bolt pitch. 2. Ensure that the ceiling is strong enough to support the weight of the unit. 3. To prevent the unit from dropping, firmly fasten the suspension bolts as shown in the figure below. Unit: mm Hole-in-anchor Hexagonal nut (field supply)
  • Page 56 9-3. Installing the Refrigerant Tubing The size of the refrigerant tubing is as shown in the table below. Table 1-2 Type ø25.4 ø25.4 Gas tube (Brazing connection) (Brazing connection) ø9.52 (Flare connection) ø12.7 (Flare connection) Tightening torque (approximate) : 34 ~ 42 N · m Tightening torque (approximate) : 34 ~ 42 N·m Liquid tube Thickness of connecting tube : 0.8 mm...
  • Page 57 9-4. Installing the Drain Piping Sealing tape Prepare standard hard PVC pipe (O.D. 32 mm) for the drain and use the supplied drain socket to prevent water leaks. The PVC pipe must be purchased separately. When doing this, apply adhesive for the PVC pipe at the Drain socket connection point.
  • Page 58 9-5. Caution for Ducting Work • This unit has high static pressure. In case of small pressure resistance (for instance, a short duct), install an airflow control damper (field supply) for adjusting airflow volume as airflow volume / airflow noise increases. •...
  • Page 59 9-6. External Static Pressure Setting Choose one of the methods (selection of “a”, “b”, “c” within the range of dotted line as shown in the flowchart below) and make settings. a. No setting changes: When using as it is factory preset at shipment. (If resetting after external static pressure setting once, it might be different from factory preset.) b.
  • Page 60 9-6-1. How to Set on PC Board 1. Turn off the power breaker to halt the supply of electricity to the PC board. 2. Open the lid of the electrical component box and confirm the location where the Select switch on the indoor unit control PCB is placed.
  • Page 61 9-6-3. Operating the High-spec Wired Remote 3. Select the “Code no.” by pressing the Controller (CZ-RTC3 / CZ-RTC5A) button. Change the “Code no.” to “5D” by pressing the button (or keeping it pressed). 20:30 (THU) Detailed settings 20:30 (THU) Unit no. Code no.
  • Page 62 9-6-4. Indoor Fan Performance Cooling Heating Cooling Item code “ ” Heating Cooling Setting at shipment Heating Type 200 Type 250 (Pa) (Pa) Airflow Volume (m /min.) Airflow Volume (m /min.) Fig. 1-18 1-56 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 63: Selecting The Installation Site

    Type U2 10. SELECTING THE INSTALLATION SITE 2. SELECTING THE INSTALLATION SITE Indoor Unit 4-Way Cassette Type 2-1. Indoor Unit AVOID: ● areas where leakage of flammable gas may be expected. ● places where large amounts of oil mist exist. ●...
  • Page 64: How To Install The Indoor Unit

    11. HOW TO INSTALL THE INDOOR UNIT 3. HOW TO INSTALL THE INDOOR UNIT 4-Way Cassette Type (Type U2) ■ 4-Way Cassette Type (Type U2) Note: For DC Fan Tap Change Procedure for 4-Way Cassette, see page 1-348. Preparation for Suspending This unit uses a drain pump.
  • Page 65 Placing the Unit Inside the Ceiling (3) Thread the 3 hexagonal nuts and 2 washers onto each of the 4 suspension bolts. Use 1 nut and 1 washer for the This unit is equipped with the drain pump. Check a tape upper side, and 2 nuts and 1 washer for the lower side, measure or carpenter’s level.
  • Page 66 Installing the Drain Pipe Before Performing the Installation Drain Piping (3) Limitations of Drain Hose Connection (1) Limitations of Raising the Drain Pipe Connection CAUTION CAUTION Do not bend the supplied drain hose 90° or more. The drain pipe can be raised to a maximum height of ●...
  • Page 67 Installing the Drain Pipe CAUTION Do not apply force to the drain port when connecting the ● drain pipe. Install and fix it near the indoor unit as close 3) Move the hose band so that the center position of the as possible.
  • Page 68 Checking the Drainage Important Note for Wiring 4-Way Cassette Type Be careful since the fan will start CAUTION when you short the pin on the indoor control board. After wiring (refer to 1-10. Electrical Wiring.) and drain piping are completed, use the following procedure to check that the water will drain smoothly.
  • Page 69 ■ HOW TO PROCESS TUBING Caution Before Connecting Tubes Tightly 5. HOW TO PROCESS TUBING (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. Connecting the Refrigerant Tubing (2) Be sure to apply refrigerant lubricant (ether oil) to the inside of the flare nut before making piping connections.
  • Page 70 For the flare nuts at tubing connections, be sure to use the Flare insulator (supplied) ● flare nuts that were supplied with the unit, or else flare nuts Insulating tape Flare union for R410A (type 2). The refrigerant tubing that is used must (supplied) be of the correct wall thickness as shown in the table below.
  • Page 71 Finishing the Installation CAUTION After finishing insulating and taping over the tubing, use sealing putty to seal off the hole in the wall to prevent rain and draft Never place the panel face-down. ● from entering. Either hang it vertically or place it on top of a Apply putty here projecting object.
  • Page 72 ■ HOW TO INSTALL THE CEILING PANEL ■ 4-Way Cassette Type (Type U2) CAUTION CZ-KPU3 Accessories Never place the panel face-down. ● Either hang it vertically or place it on top of a Panel for cassette ×1 Screws ×4 projecting object. Placing it face-down will damage the surface.
  • Page 73 (2) Removing the corner cover Drain tube corner Push the latches on the corner cover in the direction of Refrigerant tube the arrow 1 and remove them by sliding in the direction corner of the arrow 2. Marking with DRAIN Panel for cassette Push latches upward to disengage.
  • Page 74 (5) How to Attach the Corner & Air-Intake Grille Corner cover installation position A. Attaching the corner cover marked with the Panasonic Logo at shipment. 1) Check that the safety cord from the corner cover is * Installation possible at any of 4...
  • Page 75 Others Others 1) When setting on the P.C. Board <Procedure> (1) Checking After Installation Stop the system before performing these steps. 1) Check that there are no gaps between the unit and the 1 Open the electrical component box cover, then panel for cassette, or between the panel for cassette check the indoor unit control PCB.
  • Page 76 <Procedure of CZ-RTC4> 3 Select the “Unit no.” by pressing the button for changes. Stop the system before performing these steps. 1 Press and hold the buttons simultaneously for 4 seconds or longer. 2 If group control is in effect, press the button to set.
  • Page 77 <Procedure of CZ-RTC5A> Stop the system before performing these steps. (1) Keep pressing the buttons simultaneously for 4 or more seconds. YYYY The “Maintenance func” screen appears on the LCD display. (2) Press the button to see each menu. If you wish to see the next screen instantly, press the (5) Select the “Set data”...
  • Page 78 (5) Press the button. (The display stops blinking and remains lit, and setting is completed.) If you wish to change the selected indoor unit, follow the step (2). (6) Press the button to return to normal remote If you wish to change the selected indoor unit, follow the controller display.
  • Page 79 Type of Copper Tube and Insulation Material Accessories Supplied with Unit If you wish to purchase these materials separately from a local (4-Way Cassette) source, you will need: Part Name Figure Q’ty Remarks Deoxidized annealed copper tube for refrigerant tubing. Full-scale Foamed polyethylene insulation for copper tubes as Printed on...
  • Page 80 Panel for Cassette (ECONAVI type) CZ-KPU3A Applicable indoor unit : 4-Way Cassette Accessories Supplied Part Name Figure Q’ty Remarks ECONAVI ECONAVI type panel Screw 4 × 12 Operating Instructions Installation Instructions Since the accessories need for installation work, do not dispose of them until the unit of work is complete.
  • Page 81 How to Install the Panel for Cassette Preparation for Panel for Cassette Installation (1) Checking the unit position (1) Removing the air-intake grille 1) Remove the 2 screws on the latch of the air-intake 1) Check that the ceiling hole is within this range: grille.
  • Page 82 (3) Installing the panel for cassette 4) Check that the panel is attached tightly to the ceiling. The power must be turned ON in order to change the At this time, make sure that there are no gaps flap angle. (Do not attempt to move the flap by hand. between the unit and the panel for cassette, or Doing so may damage the flap.) between the panel for cassette and the ceiling surface.
  • Page 83 (5) How to Attach the Corner & Air-Intake Grille Corner cover installation position A. Attaching the corner cover marked with the Panasonic Logo at shipment. 1) Check that the safety cord from the corner cover is * Installation possible at every corner fastened to the panel for cassette pin, as shown in the figure below.
  • Page 84 Others 1) When setting on the P.C. Board <Procedure> (1) Checking After Installation Stop the system before performing these steps. 1) Check that there are no gaps between the unit and the 1 Open the electrical component box cover, then panel for cassette, or between the panel for cassette check the indoor unit control PCB.
  • Page 85 <Procedure of CZ-RTC4> 3 Select the “Unit no.” by pressing the button for changes. Stop the system before performing these steps. 1 Press and hold the buttons simultaneously for 4 seconds or longer. 2 If group control is in effect, press the button to set.
  • Page 86 <Procedure of CZ-RTC5A> Stop the system before performing these steps. 1 Keep pressing the buttons simultaneously for 4 or more seconds. The “Maintenance func” screen appears on the LCD display. 2 Press the button to see each menu. If you wish to see the next screen instantly, press the 5 Select the “Set data”...
  • Page 87 (5) Press the button. (The display stops blinking and remains lit, and setting is completed.) If you wish to change the selected indoor unit, follow the step (2). Press the button to return to normal remote If you wish to change the selected indoor unit, follow the controller display.
  • Page 88 4. Start settings. ECONAVI SYSTEM SETTING By pressing the buttons, select “YES” and Change the settings of main and sub indoor units to press the button. correspond to the ECONAVI system function. For the benefit of using the ECONAVI function, the main indoor unit should be provided with the ECONAVI function.
  • Page 89 4. Check the sensor status shows “Normal”. ECONAVI TEST OPERATION (By pressing the buttons, the status of Preparation: Refer to the manuals of the indoor unit and turn each indoor unit can be scrolled on the screen.) on the main power switch in advance. The sensor status of all indoor units are displayed.
  • Page 90 When actuating the external device interlock, use the thermostat signal. OPTION Connector (CN060) Output external signals PAW-OCT: Panasonic has developed an optional accessory (consisting of plug + wires) called PAW-OCT to enable an easy connection to this OPTION Connector (CN060).
  • Page 91 ■ CHECKLIST AFTER INSTALLATION WORK □ Work List Content Check Possibility of Failure & Checkpoint Are the indoor units installed following the □ There is a possibility of light injure or loss of Installation content on page 1-57 "10. SELECTING property.
  • Page 92: Mounting Procedure

    Optional Parts 1.Accessory parts ■ Air Intake Chamber CZ-FDU3 The accessory parts are required for the installation work so they should not be discarded until the work is completed. ● The following parts are provided inside the package so check that they are accounted for. Installation Instructions No.
  • Page 93 Mounting procedure (continued) Indoor unit Through-hole for 22P cable connector (white) Electrical component box Air intake chamber Cover Ceiling panel 22P cable connector Fig. 1-20 (white) Clamp 1-87 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 94 Selecting the DC fan motor taps It is necessary to set the fan speed in accordance with the intended application and the optional parts to be used if any such part is used. (Table 1-6) If this speed is not changed, a reduction in the air flow may result, causing the air outlet temperature to drop and condensation to form during cooling.
  • Page 95 ■ Air-flow Blocking Kit CZ-CFU3 Installation Instructions Accessory parts The accessory parts are required for the installation work so they should not be discarded until the work is completed. No. of No. of No. of Part name Part name Part name parts parts parts...
  • Page 96 Air outlet blocking patterns As seen from underneath the indoor unit ● When a 2- or 3-way air outlet configuration is used or when the air outlet duct connection flange (Φ150):field supply Air outlet duct is connected, block the air outlets as per the air outlet blocking connection flange patterns illustrated below.
  • Page 97 Selecting the DC fan motor taps It is necessary to set the fan speed in accordance with the intended application and the optional parts to be used if any such part is used. (Table 1-7) If this speed is not changed, a reduction in the air flow may result, causing the air outlet temperature to drop and condensation to form during cooling.
  • Page 98 ■ Thermal Insulation Kit CZ-INSU3 Installation Instructions Parts installed on the indoor unit ● Details of parts Part Side panel insulator Side panel insulator Side panel insulator Side panel insulator name <1> <2> <3> <4> Perforations Perforations Perforations Perforations Shape Square Slit Slit...
  • Page 99 Parts installed on the indoor unit (continued) <2> <3> <5> <4> <1> Fig. 1-27 <6> <8> <9> <7> Fig. 1-28 When attaching the insulators, ensure that they overlap. (Side insulators <1> to <5>) Fig. 1-29 <10> (In 4 places) 1-93 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 100 Parts mounted on ceiling panels ● Details of parts Part Insulator Insulator Insulator Insulator Insulator Insulator name <11> <12> <13> <14> <15> <16> Slit Slit Shape Slit Perforations Slit Perforations Slit Perforations (Receiver used for (Receiver used for ECONAVI) wireless remote controller) No.
  • Page 101: How To Process Tubing

    1-13. HOW TO PROCESS TUBING <Type E2> The liquid tubing side is connected by a flare nut, and the gas tubing side is connected by brazing. 1. Connecting the Refrigerant Tubing Use of the Flaring Method Many of conventional split system air conditioners employ the flaring method to connect refrigerant tubes that run between indoor and outdoor units.
  • Page 102 Caution Before Connecting Tubes Tightly (1) Apply a sealing cap or water-proof tape to prevent dust or water from entering the tubes before they are used. Apply refrigerant lubricant. (2) Be sure to apply refrigerant lubricant (ether oil) to the inside of the flare nut before making piping connections.
  • Page 103 3. Insulating the Refrigerant Tubing Two tubes arranged together Tubing Insulation Gas tubing Liquid tubing Thermal insulation must be applied to all units tubing, including distribution joint (field supply). * For gas tubing, the insulation material must be heat resistant to 120°C or above. For other tubing, it must be resistant to 120°C or above.
  • Page 104: Vacuum Purging

    1-14. VACUUM PURGING Leak Tightness Test Method Keep 3-way valve fully closed and pressurize through 3-way valve service port. Do not pressurize to the default value at once. Pressurize gradually. 1 Pressurize to 0.5MPa (5kgf/cm ² G) and then leave it for 5 minutes Use nitrogen gas for the leak tightness test.
  • Page 105: Precautions Regarding Test Run

    1-16. PRECAUTIONS REGARDING TEST RUN Check Before Test Run Content check Power supply cable Is the wire set up and connected as described in the instructions? Check for any phase sequence. Indoor/outdoor Are the wire connection’s screws loose? connection wire Is the open and close device / leakage breaker installed? Is the power supply cable’s thickness and length appropriately measured as described in the instructions? Earth wire...
  • Page 106: Checks After Installation Have Completed

    1-17. CHECKS AFTER INSTALLATION HAVE COMPLETED Check the following items after completing installation. Is there a short circuit with the intake air fl ow? Is the insulation secure? (Refrigerant piping) Are there any errors with the wiring? Are the terminal screws loose? Tightening torque (Unit: N•m {kgf•m}) M4…...
  • Page 107: Supplement

    1-19. Supplement 1. Dimensions of Air-Discharge Chamber In snowy regions, if there is concern that snow may enter the air discharge chamber, remove the base of the chamber before using. Q’ty Reference diagram Upward, Air-discharge support Unit: mm Upward, side installation fixture t0.8 Upward, Louver...
  • Page 108 8. Supplement Reference diagram for Upward, side installation fixture (field supply) Unit: mm 2-ø5 HOLE 585±0.2 (1.6) (1.6) (1.6) (1.6) 608.2 Reference diagram for Upward, Louver (field supply) Unit: mm 610.4±0.2 1-102 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 109 8. Supplement Reference diagram for Upward, Louver installation guide (field supply) Unit: mm 90° ø3.3±0.05 ø6.5 DTL A(S=1:1) (2 POSITION) 2-M4 FUNNEL EXTRUDED HOLE (THIS SURFACE 凸) 585±0.2 2-R3 2-ø5 HOLE 615±0.2 Reference diagram for Downward, Air-discharge support (field supply) Unit: mm (121.5) 59.2...
  • Page 110 8. Supplement Reference diagram for Downward, Right side installation fixture (field supply) Unit: mm 6 2-ø5 HOLE 615±0.2 DTL A (S=1:2) Reference diagram for Downward, Left side installation fixture (field supply) Unit: mm 2-ø5 HOLE DTL A 615±0.2 (S=1:2) 1-104 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 111 8. Supplement Reference diagram for Downward, Louver (field supply) Unit: mm 610.4±0.2 Reference diagram for Downward, Upward installation fixture (field supply) Unit: mm (2.6) 605.2 (2.6) 605.2 610.4±0.2 1-105 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 112 8. Supplement Reference diagram for Downward, Downward installation fixture (field supply) Unit: mm DTL A (S=1:2) 220.4 550.4 610.4±0.2 1-106 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 113 8. Supplement 2. Dimensions of Wind-proof Duct Reference diagram Air Intake Unit: mm Air discharge Air discharge 41.5 (322.5) Air discharge Air discharge Wind-proof Duct discharge discharge Wind-proof Duct discharge discharge Reference diagram for wind-proof duct (field supply) Unit: mm SPOT WELDING 4 POSITION SPOT WELDING 4 POSITION SPOT WELDING...
  • Page 114 8. Supplement 3. Dimensions of Snow-proof Vents Reference diagram Q’ty Air-discharge Top side t 1.0 Unit: mm (32.5) 233.5 Air-discharge Right side t 1.0 Air-discharge Left side t 1.0 Snow-proof Top side 1 t 1.0 Snow-proof Rear side 1 t 1.0 Snow-proof Right side 1 t 1.0 Snow-proof Left side 1...
  • Page 115 8. Supplement 2 Reference diagram for Air-discharge Right side (field supply) Unit: mm 90° ø3.3±0.05 ø6.5 2-M4 FUNNEL EXTRUDED HOLE DTL FUNNEL EXTRUDED HOLE(S=1:1) (THIS SURFACE 凹) (3 POSITION) (1.7) (615.2) M4 FUNNEL EXTRUDED HOLE (THIS SURFACE 凹) 615.2 2-ø5 HOLE 3 Reference diagram for Air-discharge Left side (field supply) 90°...
  • Page 116 8. Supplement 4 Reference diagram for Snow-proof Top side 1 (field supply) Unit: mm (282.5) 2-ø5.5 HOLE 5×14.5 OVAL HOLE 15.9 6-ø5.5 HOLE SEC A-A(S=1:1) 282.5 303.5 5 Reference diagram for Snow-proof Rear side 1 (field supply) Unit: mm 6-ø5 HOLE 1-110 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 117 8. Supplement 6 Reference diagram for Snow-proof Right side 1 (field supply) Unit: mm 90° ø3.3±0.05 ø6.5 DTL M4 FUNNEL EXTRUDED HOLE(S=1:1) (5 POSITION) 552.5 13.5 2-M4 FUNNEL EXTRUDED HOLE 3-M4 FUNNEL (THIS SURFACE 凹) EXTRUDED HOLE (555.5) (THIS SURFACE 凹) M4 FUNNEL EXTRUDED HOLE 755.5...
  • Page 118 8. Supplement 8 Reference diagram for Snow-proof Top side 2 (field supply) Unit: mm (690) 3-ø5.5 HOLE 2-ø5.5 HOLE 5×27 OVAL HOLE 5×15.6 OVAL HOLE 214.5 6-ø5.5 HOLE SEC A-A(S=1:1) 9 Reference diagram for Snow-proof Rear side 2 (field supply) Unit: mm 6-ø5 HOLE M4 FUNNEL EXTRUDED HOLE...
  • Page 119 8. Supplement 10 Reference diagram for Snow-proof Right side 2 (field supply) Unit: mm 90° ø3.3±0.05 ø6.5 DTL M4 FUNNEL EXTRUDED HOLE(S=1:1) (5 POSITION) 552.5 13.5 2-M4 FUNNEL EXTRUDED HOLE 3-M4 FUNNEL (THIS SURFACE 凹) EXTRUDED HOLE (555.5) (THIS SURFACE 凹) M4 FUNNEL EXTRUDED HOLE 755.5...
  • Page 120 8. Supplement 12 Reference diagram for Packing (field supply) Unit: mm EPT SEAL 10±2 ADHESIVE SEPARATOR 1-114 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 121: Capacity Table

    8.60 22.2 8.18 20.8 7.59 220V/230V/240V 24.5 21.4 6.90 22.2 20.2 8.43 20.6 19.4 8.26 18.6 18.4 7.84 17.2 17.2 7.25 S-200PE2E5 50Hz 1phase 26.3 17.4 7.06 24.0 16.4 8.60 22.4 15.7 8.43 20.4 14.8 8.01 19.0 14.2 7.42 U-200PE2E8A (380V/400V/415V 28.0 13.4 7.23 25.8 12.6 8.77 24.2 11.9 8.60 22.2 11.2 8.18 20.8 10.6 7.59...
  • Page 122 4-Way Cassette Type 1. Cooling Capacity Performance Data TC:Cooling Capacitty SHC:Sencible Heat Capacity IPT:Cooling Power Consumption unit : kW Outdoor air intake temp(°C D.B.) Ambient Power Model Return 20°C 30°C 35°C 40°C 46°C Source SHC IPT SHC IPT SHC IPT SHC IPT SHC IPT 24.5 19.1 6.71 22.2 18.1 8.20 20.6 17.4 8.04 18.6 16.5 7.63 17.2 15.8 7.05...
  • Page 123: Section 2. Test Run

    2. TEST RUN 2. TEST RUN 2-1. Preparing for Test Run ..................... 2-2 Indoor Units 2-2. Caution ........................2-3. Test Run Procedure ....................2-4. Items to Check Before the Test Run ............... 2-5. Test Run Using the Remote Controller ..............2-6.
  • Page 124: Preparing For Test Run

    2-1. Preparing for Test Run Before attempting to start the air conditioner, check the following: (1) All loose matter is removed from the cabinet especially steel filings, bits of wire, and clips. (2) The control wiring is correctly connected and all (Power must be turned ON at least electrical connections are tight.
  • Page 125: Items To Check Before The Test Run

    2-4. Items to Check Before the Test Run (1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crankcase heater. (2) Fully open the closed valves on the liquid-tube and gas-tube sides. 2-5.
  • Page 126: Precautions

    2-6. Precautions Request that the customer be present when the test run is performed. At this time, explain the operation manual and have the customer perform the actual steps. Be sure to pass the manuals and warranty certificate to the customer. Check that the 220 –...
  • Page 127 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 128: System Control

    2-8. System Control System control refers to the link wiring connection for control of simultaneous-operation multi systems, group control, and main-sub remote controller control. 2-8-1. Basic wiring diagram Single type Be careful to avoid miswiring when connecting the wires. (Miswiring will damage the units.) (for 3-phase Outdoor unit) Type E2 Type U2...
  • Page 129 2-8-2. Setting the Outdoor unit system addresses For basic wiring diagram (Set the system address: 1) Outdoor unit control PCB 8, 10 HP LED 2 System address rotary switch (Set to “0” at time of shipment) LED 1 System address rotary switch SW 2 SW 1 System address...
  • Page 130 2-8-3. Automatic address setting using the remote controller Auto Address Setting from the High-spec Wired Remote Controller (CZ-RTC5A) Keep pressing the buttons simultaneously for 4 or more seconds. The “Maintenance func” screen appears on the LCD display. 20:30 (THU) Press the button to see each menu.
  • Page 131 Display During Auto Address Setting On the surface of outdoor unit control P.C. board * Do not short circuit the A.ADD pin again during auto address setting. LEDs 1 and 2 go out and address setting is interrupted. * When auto address setting is normally completed, both LEDs 1 and 2 go out. Blinks alternately In other cases, correct settings referring to the following table and perform auto address setting again.
  • Page 132 Checking the indoor unit addresses Use the remote controller to check the indoor unit address. CZ-RTC5A (High-spec wired remote controller) Keep pressing the buttons The “Simple settings” screen appears on the LCD display. simultaneously for 4 or more seconds. Select the “Unit no.” by pressing the The “Maintenance func”...
  • Page 133 2-8-4. Main-sub remote controller control Control using 2 remote controller switches Main-sub remote controller control refers to the use of 2 remote controllers to control 1 or multiple indoor units. (A maximum of 2 remote controllers can be connected.) Connecting 2 remote controllers to control 1 Indoor unit Remote controller Remote controller switch (main)
  • Page 134: Caution For Pump Down

    2-9. Caution for Pump Down Pump down means refrigerant gas in the system is returned to the outdoor unit. Pump down is used when the unit is to be moved, or before servicing the refrigerant circuit. This outdoor unit cannot collect more than the rated refrigerant amount as CAUTION shown by the nameplate on the back.
  • Page 135: Section 3. Electrical Data

    3. ELECTRICAL DATA 3-1. Outdoor Units (Electric Wiring Diagram) ..............3-2 3-2. Indoor Units (Electric Wiring Diagram) ..............3-3 High Static Pressure Ducted Type ......................3-3 4-Way Cassette Type ..........................3-4 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 136: Outdoor Units (Electric Wiring Diagram)

    3-1. Outdoor Units Electric Wiring Diagram U-200PE2E8A / U-250PE2E8A AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 137: Indoor Units (Electric Wiring Diagram)

    3-2. Indoor Units High Static Pressure Ducted Type S-200PE2E5, S-250PE2E5 Electric Wiring Diagram AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 138: 4-Way Cassette Type

    4-Way Cassette Type S-100PU2E5A, S-125PU2E5A Electric Wiring Diagram AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 139: Section 4. Process And Functions

    4. PROCESS AND FUNCTIONS 4-1. Control Functions ....................... 4 - 2 4-2. Outdoor Unit Control PCB (ACXA73-04770, ACXA73-04750) ......... 4 - 8 4-3. Outdoor Unit HIC Board (ACXA73-04760) ..............4-12 4-4. Indoor Unit Control PCB Switches and Functions ..........4-13 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 140: Control Functions

    4-1. Control Functions 1. Indoor Air Temperature Control The thermostat is switched on and off in accordance with T shown below. T= (Indoor air temperature) - (Temperature set with the remote controller) In the body thermostat mode Indoor air temperature = (Body sensor) - (Shift temperature *) (setting at factory shipment) In the remote controller thermostat mode Indoor air temperature = (Remote controller sensor) * Shift Temperature...
  • Page 141 1) Indoor Air Temperature Control By the control method, not only the thermostat is switched on and off, as explained section “1. Indoor Air Temperature Control ", but also the frequency of the compressor's inverter is controlled in accordance with T and fluctuations in indoor air temperature.
  • Page 142 4) Condensation Temperature Control (cooling) This system control is performed to limit the inverter frequency in order to restrict high pressure’s abnormal increase and high-load operating prevention in the cooling mode. In accordance with the temperature of the outdoor heat exchanger temperature sensors (C1, C2), such controls are performed as to halting the operations of the indoor unit, decreasing the inverter frequency and restricting its increase, etc.
  • Page 143 6) Cooling Freeze Prevention Control The following control is performed during cooling operations (including dry mode operation), in accordance with whichever of the indoor heat exchanger temperatures (E1 or E2) is lower. (See the chart below.) (a) Frequency will not be decreased less than 6 minutes after thermostat ON. (b) The threshold value is increased in accordance with the indoor load (differences of temperature).
  • Page 144 8) Defrosting Control This control function removes frost that has adhered to the outdoor heat exchanger during the heating operation. The control is performed to prevent the deterioration of the heating capabilities attributed to the adherence of frost, and to prevent the crack or crush of pipes attributed to the accretion of ice. The following control is performed in accordance with the ambient temperature and the outdoor heat exchanger temperature sensor (C1).
  • Page 145 Ending Defrosting Defrosting operations are ended when the following conditions are satisfied. • Ending defrosting conditions When the temperature of the outdoor heat exchanger temperature sensor (C1) is 10°C or higher. When the temperature of the outdoor heat exchanger temperature sensor (C1) is 6°C or higher for consecutive 60 seconds.
  • Page 146: Outdoor Unit Control Pcb (Acxa73-04770, Acxa73-04750)

    4-2. Outdoor Unit Control PCB U-200PE2E8A (ACXA73-04770) LED1 LED2 TEST MODE PUMPDOWN A.ADD STOP AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 147 U-250PE2E8A (ACXA73-04750) LED1 LED2 TEST MODE PUMPDOWN STOP A.ADD AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 148: Outdoor Unit Control Pcb (Acxa73-04770, Acxa73-04750)

    Outdoor Unit Control PCB (ACXA73-04770, ACXA73-04750) Explanation of Functions A. ADD pin (2P, Black) Auto address setting pin • Short-circuit this pin for 1 second or longer to automatically set the addresses at the indoor units that are connected to that outdoor unit and are within the same system.
  • Page 149 Table 4-1. Method of System Address Setting [SW2 (rotary, yellow), SW1 (2P DIP switch, black)] Outdoor system SW2 setting SW1 setting address No. (system address switch) 1P (10s-digit place) 2P (20s-digit place) 1 system only System controller Outdoor Outdoor Outdoor Outdoor Indoor Indoor...
  • Page 150: Outdoor Unit Hic Board (Acxa73-04760)

    4-3. Outdoor Unit HIC Board U-200PE2E8A, U-250PE2E8A (ACXA73-04760) 4-12 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 151: Indoor Unit Control Pcb Switches And Functions

    4-4. Indoor Unit Control PCB Switches and Functions [Indoor unit control PCB] T10 (CN061): 6P plug (YEL) / Used for remote control operation. (Refer to the Remote Control Section.) Control items: (1) Start/stop input (2) Remote controller prohibit input (3) Start signal output (4) Alarm signal output EXCT (CN073): 2P plug (RED) / Can be used for demand control.
  • Page 152 Indoor Unit Control PCB (A747661) : S-200PE2E5, S-250PE2E5 POWER LED (D002) EXCT (CN073) EEPROM (IC010) JP001 DISP (CN063) EMG (CN044) T10 (CN061) OC (CN040) CHK (CN062) FAN DRIVE (CN032) 4-14 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 153 ■ Indoor Unit Control PCB (A7302060) : S-100PU2E5A, S-125PU2E5A FAN DRIVE (CN032) DISP CHK (CN062) EEPROM (IC010) OPTION (CN060) EXCT (CN073) T10 (CN061) POWER LED (D002) JP001 4-15 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 154 – MEMO – 4-16 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 155: Section 5. Trouble Diagnosis

    5. TROUBLE DIAGNOSIS 5-1. Contents of Remote Controller Switch Alarm Display .......... 5-2 5-2. Outdoor Unit Control Panel LED Display ..............5-4 5-3. PAC System Alarm Codes ..................5-5 5-4. Inspection of Parts (Outdoor Unit) ................5-32 5-5. Symptom: Thermostat in OFF continues or cycles OFF & ON too frequently ..5-33 5-6.
  • Page 156: Contents Of Remote Controller Switch Alarm Display

    5-1. Contents of Remote Controller Switch Alarm Display Blinking: OFF: Wireless remote controller receiver display Wired remote Possible cause of malfunction control display Faulty remote controller Failure in receiving serial Disconnection/Contact failure of remote controller wiring signal from remote controller's indoor unit CHK(check) pins on the indoor unit control PCB are short circuited In the case of non-group control:...
  • Page 157 Blinking: OFF: Wireless remote controller receiver display Wired remote Possible cause of malfunction control display Faulty wiring connections of (ceiling) indoor unit panel Indoor unit fan motor locked Indoor unit fan motor trouoble Indoor unit fan motor layer short Contact failure in thermostat protector circuit Faulty drain pump Timer and standby Activation of float switch...
  • Page 158: Outdoor Unit Control Panel Led Display

    5-2. Outdoor Unit Control Panel LED Display : ON : Blinking : OFF ) LED1 LED2 Display meaning After the power is turned ON (and automatic address setting is not in progress), no communica- tion with the indoor units in that system is possible. (Both ON) After power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are confirmed in that system;...
  • Page 159: Pac System Alarm Codes

    5-3. PAC System Alarm Codes Alarms for outdoor units Alarm Alarm Meaning Code Remote Controller Reception Error Remote Controller Transmission Error Error in Indoor Unit Receiving Signal from Remote Controller (central) Error in Indoor Unit Receiving Signal from the Outdoor Unit Error in Indoor Unit Transmitting Signal to the Outdoor Unit Outdoor Unit Failed to Receive Serial Communication Signals from Indoor Unit Duplicate Indoor Unit Address Settings Error...
  • Page 160 Symptoms and Parts to Inspect Remote Alarm Eliminating controller Judgement conditions Judgement and correction contents condition of alarm alarm display Stops when temp. exceeds 1. Check refrigerant cycle (gas Abnormal discharge Recovery at restart temperature error leak). • Discharge temp. Alarm output on 5 pre-trips 2.Trouble with electronic detected at or...
  • Page 161 Check Prior to Auto Address Setting * If an outdoor unit displays an alarm, conduct this process after diagnosing the problem. 1 Auto Address Is the power of the indoor unit(s) and outdoor unit(s) on? Power on Indoor/ Has the wiring of the indoor/outdoor control line been completed? outdoor Is it all connected? Connect the wiring...
  • Page 162 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes E04 Error in Indoor Unit Receiving Signal from the Outdoor unit Error Detection Method When there is no communication within a 3-minute period from the outdoor unit. Or, judged an error when no reply comes from the outdoor unit.
  • Page 163 For information on the procedures for replacing the indoor unit’s control board, refer to the manual that is packaged with the indoor unit control PCB. Indoor Unit Control PCB (A747661) Indoor Unit Control PCB (A7302060) : S-200PE2E5, S-250PE2E5 : S-100PU2E5A, S-125PU2E5A POWER LED (D002) EEPROM (IC010)
  • Page 164 • For information on the remote control’s detailed settings, refer to the Reference Materials. Indoor Unit Control PCB (A747661) Indoor Unit Control PCB (A7302060) : S-200PE2E5, S-250PE2E5 : S-100PU2E5A, S-125PU2E5A POWER LED (D002) EEPROM (IC010) EXCT (CN073)
  • Page 165 E16 Automatic Address Alarm (The total capacity of indoor units is too high.) Error Detection Method It is judged an error the total capacity of indoor units is too high or the total number of indoor units is too many. The total capacity of indoor units is too high.
  • Page 166 F06 Inlet Temperature Sensor (C1) in Heat Exchanger Trouble Error Detection Method In case of open or short • Error Diagnosis 1 Sensor Is the connector properly connected to PCB? Trouble Reconnect & check Replace sensor. Is the resistor between the sockets infinity or 0 ? 2 Control Outdoor unit control PCB failure Replace PCB with a new one.
  • Page 167 F12 Compressor inlet Suction Temperature Sensor (TS) Trouble Error Detection Method It is judged an error when open circuit or short circuit. Error Diagnosis 1 Sensor Sensor connector is connected to PC board properly. Reconnect and check Replace sensor Resistance between sockets is infinity or 0 ohm. 2 Outdoor control Replace PC board because of outdoor control PC board failure.
  • Page 168 H01 Primary (input) Overcurrent Detected Error Detection Method • Primary current effective value detected overcurrent (trip current value). Trip current value HP = horse power 3-phase model 8 HP 10 HP Heating 23.0A 23.0A Cooling 21.5A 21.5A Error Diagnosis 1 Power Check power supply Not satisfied with + 10% rated supply voltage supply*...
  • Page 169 H03 Primary Current CT Sensor (current sensor) Failure Error Detection Method It is judged an error based on the criteria listed below. • If 18A or greater is detected when the compressor is stopped (alarm triggered even if the connector is unplugged). •...
  • Page 170 H31 HIC Trouble Error Detection Method It is judged an error if the computer detects an error signal from the HIC. An error signal is issued by the HIC if abnormal heat occurs inside the HIC or if there is an overcurrent. However, it is judged an error in the same way if the signal line from the HIC is not connected properly or opened.
  • Page 171 Tester terminals HIC- HIC+ Resistance value (ohm) 1 k to 10 k 1 k to 10 k 1 k to 10 k 5 k to 20 k 20 k to 20 k to 20 k to 20 k to Tester terminals Resistance value (ohm) 20 k to 20 k to...
  • Page 172 L04 Outdoor Unit Address Duplication Error Detection Method It is judged an error when the identical self-address communication on the indoor and outdoor wirings is received over 5 times within 3 minutes. Error Diagnosis 1 System Are other outdoor units using a duplicate setting? address Installation When units are networked, first set the system address for each outdoor unit in the order...
  • Page 173 L18 4-way Valve Operation Failure Error Detection Method It is judged an error when during heating operation (Comp. ON), the highest detected temperature at an outdoor unit heat exchanger (C1) was 20°C or more above the outdoor air temperature (Air Temp.) continuously for 5 minutes or longer.
  • Page 174 P04 High Pressure Trouble Error Detection Method It is judged an error if the internal circuit of the high pressure switch is dead. The electronic circuitry of the high pressure switch is cut off if the pressure at the pressure sensor port of the high pressure switch reaches 3.80 MPa.
  • Page 175 3 Problem Prevent air short The intake temperature (ambient temperature) of the indoor unit is around the circuit above 36°C. heat exchanger Clean the filter The filter of the indoor unit is clogged. Replace the indoor fan (motor) The fan of the indoor unit is broken or the fan motor is faulty. 4 Blockage Is the outdoor unit’s electronic control valve operating correctly? in the...
  • Page 176 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes P05 AC Power Supply Trouble Error Detection Method • Instantaneous blackout Zero-cross (waveform input of power supply) error • DC voltage charge failure • Error Diagnosis Note : The work involved in diagnosing each of the items is extremely dangerous, so turn the power off at the breaker before performing the tests.
  • Page 177 P13 Alarm Valve Open Error Detection Method Detection is performed only in the test run. When once detected or the test run finished without any error, the second detection will not be done. In case of forgetting to open a valve, P04 (high-pressure switch operational alarm) is occasionally preceded due to the following conditions.
  • Page 178 P15 Insufficient Gas Level Detected Abnormal Detection Method Alarm occurs in the following cases: • Compressor's current value shows lower than a certain value. • Compressor's discharge temperature exceeds 95°C. • Electronic expansion valve is fully opened. • The difference between indoor unit heat exchanger temperature and intake temperature is less than 4K. Error Diagnosis 1 Adjustment Recharge with...
  • Page 179 P16 Compressor Overcurrent Trouble Meaning of Alarm • Secondary current effective value detected the overcurrent (trip current value). 3-phase model (8, 10HP) : Trip current = 24.3 A • Secondary current instantly detected overcurrent (trip current value). 3-phase model (8, 10HP) : Trip current = 50.0 A peak Check of content 0 Multiple...
  • Page 180 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes 4 Check the Take measures Outdoor air intake temperature is high. situation Correct May be caused by poor outdoor unit air flow (dirty or clogged heat exchanger, blocked discharge port, etc.) Prevent air short Air short circuit has occurred.
  • Page 181 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes 9 Check the See what happens. Replace the HIC PC board and operate the unit. (Apply putty and HIC PC screws must not be loose) Does it operate normally? 10-1 boards 10 Check the...
  • Page 182 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes P22 Outdoor Unit Fan Motor Trouble Error Detection Method • It is judged an error when the outdoor fan motor’s rotating signal cannot be detected normally. Error Diagnosis 1 Wiring Are the connectors “CN-FM_UP”...
  • Page 183 P29 Lack of INV compressor wiring, INV compressor actuation failure (including locked), DCCT failure Error Detection Method Abnormal current is detected at DCCT before start-up. • Start-up failed during overcurrent and/or step-out detected. • • Open-wire of compressor and/or backspin detected. •...
  • Page 184 ■ Outdoor Unit Control HIC PCB ACXA73-04760 : (U-200PE2E8A, U-250PE2E8A) (3-phase outdoor unit HIC PC board) 5-30 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 185 Mini VRF SYSTEM Trouble Diagnosis 4. Mini VRF System Alarm Codes P31 Group Control Error Error Detection Method • Other indoor unit alarms within the group. 1 Other indoor Survey the indoor unit that alarms other than “P31” in the indoor unit group and specify the unit causes of failure.
  • Page 186: Inspection Of Parts (Outdoor Unit)

    Mini VRF SYSTEM Trouble Diagnosis 5. Inspection of Parts (Outdoor Unit) 5-4. Inspection of Parts (Outdoor Unit) (1) Electronic control valve (MOV1) MOV1: Measure the voltage between plug pin 5 and pins 1 through 4 at the CN-MOV1 connector (5P, white) on the outdoor unit control PCB.
  • Page 187: Symptom: Thermostat In Off Continues Or Cycles Off & On Too Frequently

    Mini VRF SYSTEM 6. Symptom: Thermostat in OFF continues or Trouble Diagnosis cycles OFF & ON too frequently 5-5. Symptom: Thermostat in OFF continues or cycles OFF & ON too frequently How to detect abnormality • Abnormality does not occur. Protective function can be checked when the outdoor maintenance remote controller is connected.
  • Page 188: Sensor Temperature Display Function (Displayed Regardless Of Operation And Stop)

    5-6. Sensor Temperature Display Function (Displayed regardless of operation and stop) The procedure below displays the sensor temperatures from the remote controller, indoor unit, and outdoor unit on the remote controller. (1) Press and hold the buttons simultaneously for 4 seconds or longer. (2) The unit No.
  • Page 189: Table Of Thermistor Characteristics

    5-7. Table of Thermistor Characteristics (1) Outdoor Air Temp. (TO) Sensor, Intake Temp. (TS) Sensor, Heat Exchanger Temp. (C1) Sensor, Heat Exchanger Temp. (C2) Sensor -20 -15 -10 Temperature ( C) Temperature ( C) (2) Discharge Temp. (TD) Sensor 90 100 110 Temperature ( C) 5-35 AMP Air Conditioning...
  • Page 190: How To Remove The Compressor

    5-8. How to Remove the Compressor Pay careful attention to prevent water or foreign objects from entering into the refrigerant tubing when removing or installing the compressor. Removing 1.After collecting the refrigerant in the system, replace nitrogen gas from the service port of the gas tubing valve. 2.Remove the sound absorbing material protecting the compressor.
  • Page 191: How To Remove The Electrical Component Box

    5-9 How to Remove the Electrical Component Box Removing 1.Remove the front panel and inspection panel from the outdoor unit. 2.Remove all local wires connected to the electrical component box. 3.Remove the wires (temperature sensor, coils of every sort of valve, pressure switch, fan motor and wires for connecting compressor) connected to the electrical component box in the unit.
  • Page 192 Mini VRF SYSTEM 6. Symptom: Thermostat in OFF continues or Trouble Diagnosis cycles OFF & ON too frequently How to detect abnormality Abnormality does not occur. Protective function can be checked when the outdoor maintenance remote controller is • connected. Error Diagnosis Adjust setting Indoor control...
  • Page 193: Section 6. Outdoor Unit Maintenance Remote Controller

    6. OUTDOOR UNIT MAINTENANCE REMOTE CONTROLLER In the case of CZ-RTC4 6-1. Overview ........................6-2 6-2. Functions ........................6-2 6-3. Normal Display Operations and Functions ............. 6-3 6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures ......................6-8 6-5.
  • Page 194: Overview

    6-1. Overview What is the outdoor unit maintenance remote controller? Beginning with the DC-INV series of outdoor units, nonvolatile memory (EEPROM) is used in the outdoor unit PCB. In this way, the setting switches that were located on earlier PCBs have been converted to EEPROM data. This remote controller is an outdoor unit maintenance tool that is used to make and change the EEPROM set- tings.
  • Page 195: Normal Display Operations And Functions

    6-3. Normal Display Operations and Functions Normal display functions • Connect the special service checker wiring to the outdoor unit PCB. The connection is shown in the figure below. When connecting the special service Outdoor unit PCB checker wiring to the remote controller (3P, BLU) CZ-RTC4, cut out the wire as shown in the Special service...
  • Page 196 All units start/stop (Fig. 6-1) <Operation> (Start/Stop operation) button can be used to start and stop all the indoor units. • The LED illuminates if any indoor units is operating. • The LED blinks if an alarm at any of the operating indoor units occurs.
  • Page 197 n Display (functions) • Use the temperature setting buttons to change the item code. (1) Item code (2) Item Remarks Outdoor unit alarm Alarm code display No. of connected indoor units Quantity Unit Nos. of connected indoor unit 7-segment display Operating status of indoor unit 7-segment display Thermostat ON status of indoor unit...
  • Page 198 (3) XX-YY R.C. Locations where (1), (2), and (3) are displayed as Displays the outdoor unit sub-bus address which is shown in Fig. 6-4. currently selected. XX = Outdoor system address on main bus line (1 – 30) YY = Outdoor unit sub-bus address (1 – 8) “1”...
  • Page 199 n 7-segment, 4-digit display for remote controller timer display The connected unit Nos. are displayed as shown below, using the 7-segment 4-digit ( ) display and the colon.  Display for unit Nos. 1 – 20 Not lit Not lit Not lit Not lit Meaning of display colon...
  • Page 200: Monitoring Operations: Display Of Indoor Unit And Outdoor Unit Sensor Temperatures

    6-4. Monitoring Operations: Display of Indoor Unit and Outdoor Unit Sensor Temperatures <Operating procedure> (1) Press and hold the (Check) button and buttons simultaneously for 4 seconds or longer to engage temperature monitor mode. During temperature monitoring, is illuminates. (The display and operations are the same as for monitor mode using the indoor unit remote controller.) (2) Press the...
  • Page 201 ■ Display of unit No. 1 (main unit) Item code Meaning of Code Indoor unit data Indoor unit intake temp. Indoor unit heat exchanger temp. (E1) Indoor unit heat exchanger temp. (E2) – – – – Outdoor unit data Discharge temp. (TD) –...
  • Page 202: Monitoring The Outdoor Unit Alarm History: Display Of Outdoor Unit Alarm History

    6-5. Monitoring the Outdoor Unit Alarm History: Display of Outdoor Unit Alarm History * Displays outdoor unit alarms only. Does not display indoor unit alarms. * Check the indoor unit alarm histories separately using the indoor unit remote controllers or other control device. <Operating procedure>...
  • Page 203: Settings Modes: Setting The Outdoor Unit Eeprom

    6-6. Settings Modes: Setting the Outdoor Unit EEPROM 2WAY SYSTEM 6. Mode Settings  Setting mode 1 Outdoor Unit Maintenance Remote Controller <Operating procedure> Press and hold the (Check) button and Display of fi rst 3 digits (Ventilation) button simultaneously for 4 seconds or longer.
  • Page 204 Never use the DN code unlisted in the following table. (P) : Factory preset mode Item Setting No. 1=Silent mode 1 (P) Outdoor fan silent mode 2=Silent mode 2,,,,, 3=Silent mode 3 Capacity matching ignored 0=Invalid (P) 1=Valid 0=Invalid 1=stop for 2 hours and drive for 20 minutes constantly 2=stop for 20 minutes and drive for 20 minutes constantly Indoor unit drain pump forced operation 3=Drive constantly...
  • Page 205: Section 7. Remote Controller Functions Section

    7. REMOTE CONTROLLER FUNCTIONS SECTION 7-1. Simple Settings Function .................... 7-2 7-2. List of Simple Setting Items ..................7-4 7-3. Detailed Settings Function ..................7-5 7-4. List of Detailed Setting Items ..................7-7 7-5. Simple Setting Items....................7-11 7-6. Detailed Setting Items ....................7-13 7-7.
  • Page 206: Remote Controller Functions Section

    Optional Controller 4. Simple Settings Function Remote Controller Functions 7-1. Simple Settings Function This allows the filter lifetime, operating mode priority change, central control address, and other settings to be made for an individual or group-control indoor unit to which the remote controller used for simple settings is connected.
  • Page 207 <Procedure of CZ-RTC5A> 20:30 (THU) START CZ-RTC5A Fig. 7-2 3 Select the “Code no.” by pressing the button. Change the “Code no.” by pressing the 1 Keep pressing the button. buttons simultaneously for 4 or more seconds. The “Maintenance func” screen appears on the Simple settings 20:30 (THU) LCD display.
  • Page 208: List Of Simple Setting Items

    7-2. List of Simple Setting Items Setting data Item code Item Description 0000 Not displayed 0001 150 hours Filter sign ON time 0002 2,500 hours (filter life time) 0003 5,000 hours 0004 10,000 hours 0005 Use the filter clogging sensor. 0000 Standard (setting at time of shipping) Degree of filter fouling Highly fouled...
  • Page 209: Detailed Settings Function

    Optional Controller 5. Detailed Settings Function Remote Controller Functions 7-3. Detailed Settings Function This allows the system address, indoor unit address, and other settings to be made for the individual or group-control indoor unit to which the remote controller used for detailed settings is connected. When detailed settings mode is engaged, operation stops at the individual or group-control indoor unit where the remote controller used for detailed settings is connected.
  • Page 210 <Procedure of CZ-RTC5A> 20:30 (THU) START CZ-RTC5A 3 Select the “Code no.” by pressing the Fig. 7-4 button. Change the “Code no.” by pressing the 1 Keep pressing the button (or keeping it pressed). buttons simultaneously for 4 or more seconds. The “Maintenance func”...
  • Page 211: List Of Detailed Setting Items

    7-4. List of Detailed Setting Items Setting data Item Item code Description Description Description 0000 0001 4-Way Cassette (U2) 0002 High Static Pressure 0003 0005 0006 Ducted (E2) Type 0007 0008 0010 0011 0001 0003 0005 0007 0009 0011 Indoor unit capacity 0012 0015...
  • Page 212 Setting data Item code Item Description 0000 5 minutes Forced thermostat ON (1B) 0001 4 minutes –10°C –010 –9°C –009 Cooling discharge –8°C –008 temperature shift 0010 10°C –10°C –010 –9°C –009 Heating discharge –8°C –008 temperature shift 0010 10°C 0001 ±...
  • Page 213 Setting data Item code Item Description 0000 No forced operation 0001 Forced operation for 1 minute Automatic drain pump operation Continuous operation 0060 None 0000 Ventilation fan operation 0001 Ventilation fan operated by remote controller. Wired remote controller 0000 Not used. (Body sensor is used.) Remote controller sensor is used.
  • Page 214 Setting data Item code Item Description Type 200: 60Pa, Type 250: 72Pa Fan tap setting 0001 (Setting at shipment) (External static pressure Type E2 0002 140Pa of the rated air flow volume) 0003 270Pa Purpose Fan tap setting 0000 Standard (factory setting) (Fan tap change in order High ceiling setting 1 (with standard, ECONAVI panel) to prevent drop in air...
  • Page 215: Simple Setting Items

    7-5. Simple Setting Items Item code Item Description Filter sign ON time setting Changes the indoor unit filter lifetime when a high-performance filter or (filter lifetime) other optional product is installed. Reduces the filter sign ON time to 1/2 of the standard time (setting at the Degree of filter fouling time of shipping) for cases when filter fouling is more severe than normal.
  • Page 216 When the operating mode at the priority remote controller is changed, the operating modes of other remote controllers change as shown below. Mode change at priority remote controller Operating modes at other remote controllers Current mode New mode Current mode New mode Cooling or dry Heating...
  • Page 217: Detailed Setting Items

    7-6. Detailed Setting Items Item code Item Description Unit type Set when the indoor unit EEPROM memory is replaced during servicing. Indoor unit capacity System (outdoor unit) These are not set at the time of shipping from the factory. address These must be set after installation if automatic address setting is not Indoor unit address performed.
  • Page 218 Item code Item Description 1F (Upper limit) Cooling 20 (Lower limit) This setting changes the temperature range (upper limit and lower 21 (Upper limit) Change to the Heating limit) which is set from the remote controller or central control device. 22 (Lower limit) remote control The set upper limit must be greater than or equal to the lower limit.
  • Page 219 (Continued from previous page) Item code Item Description Heat exchanger The heat exchanger temperature control point for prevention of cold temperature for cold air air discharge during heating operation can be changed. discharge The indoor unit PCB optional output for the fan can be switched Fan output switching according to the purpose of use.
  • Page 220 DC Fan Tap Change Procedure <Procedure> It is necessary to set the fan speed in accordance with the intended application and the optional parts to be used if any such part is used. (Table 1) If this speed is not changed, a reduction in the air flow may result, causing the air outlet temperature to drop and condensation to form during cooling.
  • Page 221: Remote Controller Servicing Functions

    Optional Controller 1. Remote Controller Servicing Functions Remote Controller Functions 7-7. Remote Controller Servicing Functions The remote controller includes a number of servicing functions. Use these as needed for test runs and inspections. CZ-RTC4 Fig. 7-6 List of Servicing Functions Functions Description Button operation...
  • Page 222 ■ High-spec Wired Remote Controller CZ-RTC5A Display of "maintenance function" screen 1 Keep pressing the buttons simultaneously for 4 or more seconds. Maintenance func 20:30 (THU) The “Maintenance func” screen appears on the 1. Outdoor unit error data LCD display. 2.
  • Page 223: Test Run Function

    2. Test Run Function Remote Controller Functions 7-8. Test Run Function Operates the unit with the thermostat forced ON. Press and hold the button for 4 seconds or longer. ° “ ” appears on the remote controller LCD ° display (Fig. 7-8). Press the button to start the test run.
  • Page 224 <Procedure of CZ-RTC5A> 1 Keep pressing the buttons simultaneously for 4 or more seconds. 20:30 (THU) The “Maintenance func” screen appears on the LCD display. Maintenance func 20:30 (THU) START 1. Outdoor unit error data 2. Service contact 3. RC setting mode 4.Test run Sel.
  • Page 225 Sensor Temperature Display Function (displayed regardless of whether unit is operating or stopped) The procedure below display the sensor temperatures from the remote controller, inddor unit, and outdoor unit on the remote controller. <Procedure of CZ-RTC4> ° Press and hold the buttons °...
  • Page 226 <Procedure of CZ-RTC5A> 1 Keep pressing the buttons simultaneously for 4 or more seconds. The “Maintenance func” screen appears on the 20:30 (THU) LCD display. Maintenance func 20:30 (THU) 1. Outdoor unit error data START 2. Service contact 3. RC setting mode 4.Test run Sel.
  • Page 227: Automatic Address Setting

    Automatic address setting <Procedure of CZ-RTC5A> 1 Keep pressing the buttons simultaneously for 4 or more seconds. 20:30 (THU) The “Maintenance func” screen appears on the LCD display. 2 Press the button to see each START menu. If you wish to see the next screen instantly, press button.
  • Page 228 – MEMO – 7-24 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...
  • Page 229: Section 8. How To Install The Wireless Remote Controller Receiver

    8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER 8. HOW TO INSTALL THE WIRELESS REMOTE CONTROLLER RECEIVER Important Safety Instructions ..................8-2 Optional Controller (Remote Controller) ................ 8-1. Names and Functions ....................8-2. Installing Batteries ....................8-5 8-3. Setting the Current Time ..................8-4.
  • Page 230: Important Safety Instructions

    Important Safety Instructions WARNING Installation Precautions • Do not install yourself Installation should always be performed by your dealer or a professional service provider. Electric shock or fire may result if an inexperienced person performs any installation or wiring procedures incorrectly.
  • Page 231: Optional Controller (Remote Controller)

    2. Wireless Remote Controller Optional Controller (Remote Controller) Wireless Remote Controller CZ-RWSK2, CZ-RWSU3 One remote controller can control a group of up to eight indoor units. 8-1. Names and Functions REMOTE CONTROLLER 15. Sensor button Used this button to activate the Displays the operation status.
  • Page 232 RECEIVER CZ-RWSC3 1. Receiver Receives the signal sent from the remote controller. 2. Emergency Indicator lamps operation When an error occurs, one of the button lamps flashes. When an indicator lamp is flashing, refer to “8-13. Before Requesting Service”. OPERATION lamp Lights up when the unit is operating.
  • Page 233: Installing Batteries

    8-2. Installing Batteries 1. Remove the cover. 2. Insert two LR03 size batteries. Put the batteries in with the polarity [+/–] as shown in the figure. 3. Gently insert one end of an unfolded paper clip (or a similar object that can fit) into the Reset hole and press the Reset button inside the hole, then put the cover back on.
  • Page 234: Operation

    8-4. Operation Auto , Heat , Dry , Cool , Fan Models that only provide the cooling function cannot operate in the auto or heating modes. Power: Turn on the power of the indoor unit at least 14 hours before operation. 1.
  • Page 235: Timer Operation

    8-5. Timer Operation When setting the timer, make sure the current time on the remote controller is accurate. The timer’s clock can only be set when the display of the remote controller is ON. After setting the timer, put the remote controller in a place where its signal will reach the receiver of the indoor unit.
  • Page 236: Adjusting The Wind Direction

    8-6. Adjusting the Wind Direction Never try to manually move the flap (up-down wind direction plate) that is operated by the remote controller. When the unit stops, the flap (up-down wind direction plate) automatically faces downwards. When the unit is in heating standby, the flap (up-down wind direction plate) faces upward. Also, bear in mind that the flap starts swinging after the heating standby mode is released, but the display on the remote controller indicates Auto Flap during standby heating as well.
  • Page 237: Using The Remote Controller

    8-8. Using the Remote Controller Point the transmitter of the remote controller at the receiver. When the signal is received correctly it will beep once. (It beeps twice only when the unit starts operating.) The signal can be received at a distance of about 6 meters. This distance should be used only as a guide. It depends on battery strength.
  • Page 238 Control of 2WAY SYSTEM 2. Wireless Remote Controller Matching up Addresses Setting Remote Controller Addresses 1. If you press at the same time, “ ” will blink. 2. While holding down, every time you press , it cycles from ALL 3…...
  • Page 239: Emergency Operation

    Control of 2WAY SYSTEM 2. Wireless Remote Controller 8-11. Emergency Operation Use [Emergency Operation] in the following situations when there is an urgent need. When the remote controller’s batteries have failed. When the remote controller is broken. When the remote controller is lost. CZ-RWSU3 Start : press [Emergency Operation] of the receiver.
  • Page 240: Miscellaneous Settings

    8-12. Miscellaneous Settings A variety of changes can be made to settings, depending on the indoor unit being used. Operation mode indicator, time display (24 hour, AM/PM), Heat Max Temp • (These settings are saved in nonvolatile memory in the remote controller, so even when its batteries are changed, the settings do not have to be made again.) •...
  • Page 241: Before Requesting Service

    2. Wireless Remote Controller 8-13. Before Requesting Service Before requesting service, please check the followings. Solution The power to the indoor unit is not ON. Make sure the power to the indoor unit is ON. The unit doesn’t work even when is pressed on the Are the remote controller’s batteries dead?
  • Page 242: How To Install The Wireless Remote Controller Receiver

    How to Install the Wireless Remote Controller Receiver 8-14. Common to All Models 1. Warnings about Installation of Receivers The wireless remote controller uses a very weak infrared light for its signal, which can result in the signal not being received because of the following influences, so take care in where the unit is installed.
  • Page 243 Control of 2WAY SYSTEM 2. Wireless Remote Controller CZ-RWSU3 All set at OFF when shipped PCB cover Screw from the factory. Receiver PCB Main/Sub selector 1 2 3 switch for remote controllers (4) OFF: Main ON: Sub Set its address (1) to (3) CZ-RWSC3 ADDRESS 1...
  • Page 244: Cz-Rwsc3

    Control of 2WAY SYSTEM 2. Wireless Remote Controller 8-15. CZ-RWSC3 Dimensions Installation Instructions Wireless Receiver for ALL Part Names Unit: mm (1) Light receiving section Receives signals. (2) Emergency operation button Starts/Stops emergency operation. OPERATION TIMER STANDBY (3) Indication lamp FILTER Indicates operation status.
  • Page 245 Control of 2WAY SYSTEM 2. Wireless Remote Controller 2. Installing the Receiver Remove the bottom case. Attention Mounting the bottom case  Tighten the screws securely until the screw heads touch the bottom case. (Otherwise, loose screw heads may hit the PCB and cause malfunction when mounting the top case.) ...
  • Page 246: Specifications

    Control of 2WAY SYSTEM 2. Wireless Remote Controller 3. Wiring the Receiver Wiring for the receiver  Wiring diagram  Type of wiring Receiver Indoor unit Use cables of 0.5 to 1.25 mm  Total wire length: 400 m or less RC wiring (fi eld supply) (The wire length between indoor •...
  • Page 247: Test Operation

    Control of 2WAY SYSTEM 2. Wireless Remote Controller 4. Setting Address Switches  Main/Sub setting  Address setting Remove the top case of the receiver for setting. Main/Sub setting  Use this to set Main/Sub for the remote controller and the receiver. Switch ...
  • Page 248: Cz-Rwsu3

    8-16. CZ-RWSU3 1. Accessories Supplied accessories Receiver Wireless Remote Remote Controller LR03 Size Operating Quick Wood Screw Clamper Controller Holder Battery Instructions Reference M4 × 16 2. Installing the Receiver  The receiver can be installed only on the corner shown in Wire the receiver.
  • Page 249 3. Wiring the Receiver Wiring Diagram Indoor Unit Receiver PCB Terminal Strip for White Wiring Remote Black Controllers Connections Connect the wires from the receiver to the remote controller terminal strip on the indoor unit. (Polarity does not matter) 4. Setting for Receiver All set at OFF Check the settings of the [S003] DIP switch on the when shipped...
  • Page 250: Common To All Models

    8-17. Common to All Models 1. The Self-Diagnosis Function Display and What is Detected Alarm Display in the table below indicates the content of alarms that are displayed when a wired remote controller is connected. For information on how to deal with the alarms, refer to the Mounting Instructions for the indoor unit or to Test Run or servicing materials.
  • Page 251 3. Setting Up Remote Controller Functions The functions of the wireless remote controller can be set on site. (These settings are saved in nonvolatile memory in the remote controller, so even when its batteries are changed, the settings do not revert to the defaults.) NOTE The operation of the air conditioner can be impacted, depending on the settings made, so only service personnel should make the settings.
  • Page 252 201610 AMP Air Conditioning www.ampair.co.uk | sales@ampair.co.uk...