Siemens SINAMICS Configuration Manual page 157

Industrial security, medium-voltage converter
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

Preconditions for PN Gate
Hardware
● SINAMICS CU320-2 PN with firmware version as of 4.5
● Communication Board Ethernet 20 (CBE20)
● Short Ethernet cable to connect CBE20 and CU320-2 PN (X150)
Recommendation: Ethernet cable with the article number: 6SL3060-4AB00-0AA0
● Control hardware with standard Ethernet interface (100 Mbit/s or higher),
for example, the SIMATIC Box IPC 427C.
Note
The Gate PC must guarantee the short latency times required for operating the PN Gate.
Influencing variables are the CPU performance, mainboard hardware (Ethernet chipset and
its connection), and the BIOS and the software components involved (operating system
components such as memory mapping, Ethernet driver, interrupt link, configuration).
Software
● STARTER as of V4.3
or
● Drive ES as of V5.5
or
● SIMATIC STEP 7 as of V5.5 SP2
● Development kit for the development and configuration:
– SINAMICS PN Gate DevKit (Article No. 6SL3071-0CA00-0XA0)
● Licenses
– The PN Gate CU requires a runtime license with Article No. 6SL3074-0AA03-0AA0 or
PROFINET version
● SINAMICS PN Gate V2 is compatible with PROFINET V2.2
Industrial Security
Configuration Manual, 08/2017, A5E36912609A
the Z option G01 for CFC.
Communication
A.1 Communication
157

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents