ABB PQFM Instruction Manual page 78

Power quality filter
Table of Contents

Advertisement

Filter (auxiliaries)
connected to the supply,
error appears
Filter (auxiliaries)
connected to the supply,
error disappears
Figure 60
shows an example of an alarm contact cabling scheme using the NC alarm
contact. Using this scheme the bulb B will be on when the power supply to the filter is
interrupted or the filter trips due to an error. Otherwise the bulb will be off.
Figure 60: Alarm bulb cabling scheme using the NC alarm contact on
When the filter system consists of multiple master-units and an alarm contact is needed
to signal when the complete system is off, then the NC alarm contacts of all the master
units have to be cabled in series. An example is given in
Figure 61: Cabling of the alarm status of a multi-unit filter consisting of masters only, using the
In the
Figure
61, the alarm bulb will be activated when both master units are in alarm.
78 Electrical design and installation ç Manual Power Quality Filter PQFM
Opens when error
present for 3 minutes
Otherwise, remains
closed
When open before,
closes when error
disappears
When closed before,
remains closed
PQF-Manager
NO
15
Alarm
(a)
outputs
16
NC
(a)
17
Remark:
(a)
Right hand terminal block when looking from rear, counting from top to
bottom
the PQF-Manager
NC Alarm
contact of
master 1
230 Vac
external
power
supply
Note: Contacts drawn in non-alarm position
NC alarm contact on each filter.
Closes when error present for 3
minutes
Otherwise, remains open
When closed before, opens when error
disappears
When open before, remains open
230 Vac
external
power
supply
External bulb
alarm indicator
B
Figure 61
for 2 master filters.
NC Alarm
contact of
Alarm bulb
master 2
B