Alarms / Errors; Definition; Alarms; Error - ABB EBN853 Operating Instructions Manual

Power electronic unit for control of contrac actuators in the explosion protection area
Hide thumbs Also See for EBN853:
Table of Contents

Advertisement

Pos: 17.1 /Überschriften/1/A - C/Alarme / Fehler @ 13\mod_1191918058984_3101.doc @ 128661
8

Alarms / Errors

Pos: 17.2 /Überschriften/1.1/1-spaltig/D - F/Definition @ 13\mod_1191918133734_3101.doc @ 128707
8.1

Definition

Pos: 17.3 /Fehlermeldungen/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Alarme @ 13\mod_1191907921656_3101.doc @ 128299
8.1.1

Alarms

The actuator or electronic unit is in a critical state (e.g., high temperature), which currently does
not affect the actuator, electronic unit, process or persons. The actuator functions are available.
Previous alarms are stored in the "Saved Alarms" area in the electronic unit. Use the graphic
user interface to output the stored alarms.
Pos: 17.4 /Fehlermeldungen/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Fehler @ 13\mod_1191908411312_3101.doc @ 128322
8.1.2

Error

The actuator or electronic unit is in a critical state, e.g., positioning time-out, which currently is
impairing the actuator, electronic unit, process or persons. The actuator is switched off and the
actuator functions are no longer available. Previous error messages are stored in the "Saved
Errors" area in the electronic unit. Use the graphic user interface to output the stored errors.
Error messages cannot be reset until the cause of the error has been eliminated.
Pos: 17.5 /Überschriften/1.1/1-spaltig/A - C/Alarm Schema @ 13\mod_1191918181968_3101.doc @ 128730
8.2

Alarm diagram

Pos: 17.6 /Fehlermeldungen/Aktorik/Antriebe/Leistungselektroniken/Allgemein/Alarm Schema @ 13\mod_1191909106750_3101.doc @ 128345
Setpoint time-out
upper limit/ lower limit
Monitoring ON
&
Actuator Stop
Safety pos. last
setpoint
Pos: 17.7 /Überschriften/1.1/1-spaltig/D - F/Fehler Schema @ 13\mod_1191918225828_3101.doc @ 128753
42/68-830-EN
Transmitter
Maintenance
monitoring
upper limit/ lower
Lubricant /
limit
Elastom.
Motor / Gear
Integr.
controller
ON
&
Alarm Signal
General Alarm
Display ON
EBN853, EBN861 (Contrac)
Alarms / Errors
Actuator
Temperature of
temperature
Electronic Unit
(high / low)
(high / low)
Behavior at critical
temp. MAN AUT
&
&
Actuator
moves in
desired
operating
mode
Saved Alarms (Reset
Option)
29