Mitsubishi Electric AJ65BTS-RPH User Manual page 38

Cc-link system spring clamp termnal block type repeater hub module
Table of Contents

Advertisement

No.
Name
Transmission
2)
rate setting
switch
Power terminal
3)
block
Communication
4)
terminal block
(Trunk line side)
Table 4.2 Names and settings of parts (2/3)
Set the transmission rate of the module (set to 0 at the time of delivery).
Ensure to set the transmission rate at a speed specified below.
Transmission rate of the trunk line side is identical with that of the
branch line side.
Setting value
0
1
2
3
4
Other than 0 to 4
Connects the module power supply (24V DC) and the ground cable
(FG: Functional Ground).
Terminals are assigned as follows:
Connects the transmission lines on the trunk line side (LINK IN/OUT).
Terminals are assigned as follows:
Application
Transmission rate (bps)
Cannot be set.
If set to other than 0 to 4, the ERR.
LED is turned on and data are not
transferred.
+24V
+24V
24G
24G
NC
NC
FG
FG
FG
FG
DA
DA
DB
DB
DG
DG
SLD
SLD
28
156k
625k
2.5M
5M
10M