Mitsubishi Electric PLA-RP35EA Service Manual page 43

Mr.slim split-type, heat pump air conditioners
Hide thumbs Also See for PLA-RP35EA:
Table of Contents

Advertisement

OPERATING PROCEDURE
13. Removing the float switch (FS)
(1) Remove the drain pan. (Refer to procedure 10)
(2) Loosen the clamp of the drain pump. (See Photo 14)
(3) Remove the float switch (tapping screw 4×10: 1 screw/1
hook). (See Photo 14)
(4) Remove the float switch base and the lead wire fixing band.
(See Photo 15)
(5) Remove the lead wire from the U shaped portion of the
float switch base. (See Photo 15)
(6) Slide the float switch towards the arrow to remove from the
float switch base.
14. Removing the heat exchanger
(1) Remove the drain pan. (Refer to procedure 10)
(2) Remove the piping cover (tapping screw 4×10: 3
screws).
(3) Remove the coil plate (tapping screw 4×10: 2
screws).
(4) Remove the heat exchanger fixing screws (tapping
screw 4×10: 2 screws).
(5) Remove the coil support (tapping screw 4×10: 1
screw each)
■ RP35–60:
1 coil support (See photo 16)
■ RP71–140:
3 coil supports (See photo 17)
(6) Remove the heat exchanger.
Photo 17
Heat exchanger fixing screws
Piping cover
Coil plate
OCH626A
Coil supports
Coil support
fixing screws
Heat exchanger
Photo 15
Photo 16
Heat exchanger fixing screws
Piping cover
43
PHOTOS
Do not hold this floating part
when lifting; Doing so will cause
malfunction.
Float switch
Float switch base
Float switch base
and lead wire fixing
band
U shaped portion of the
float switch base
Coil support fixing screw
Coil support
Coil plate
Heat exchanger

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents