Led Indicators (Depending On The Type); Product Documentation; Service Pins; Action Description - Siemens PXC3.E16A100A Datasheet

Pxc3.e series; room automation stations
Table of Contents

Advertisement

Island bus supply

LED indicators (depending on the type)

RUN
FLT
IB
PL
DALI
SRV
1)
2)
1) Service pin
2) Service pin DALI
8 7 6 5 4 3 2 1

Service pins

(depending on the type)

Product documentation

Siemens
Building Technologies
The internal bus supplies can be reinforced by external power supply modules.
An additional TXS1.12F10 supply module must be switched on and off at the same
time as the room automation station. Otherwise, DC 24 V island bus supply may
sag, resulting in alarms.
LED
Color
Activity
RUN
Green
Continuously ON
Continuously OFF
Flashing
FLT
Red
Continuously OFF
Continuously ON
Rapid flashing
IB
Yellow
Continuously ON
Flashing
Continuously OFF
PL
Yellow
Continuously ON
Flashing
Continuously OFF
DALI
Yellow
Continuously ON
Flashing
Continuously OFF
SVC
Red
Continuously OFF
Blinking
Blinking per wink
command*)
Ether-
Green
Continuously ON
net
Continuously OFF
1 / 2
Flashing
Yellow
Continuously ON
Continuously OFF
*)
Wink command
pattern:
Pin
Action
1)
Short press
2)
Short press
Long press
• Engineering and commissioning: See ABT online help.
• Installation manual Desigo TRA, CM111043.
• TX-I/O planning and installation manual, CM110562.
• Application Guide for IP Networks in Building Automation Systems, CM110668.
• Desigo Technical principles CM110664, chapters 18 and 26.
PXC3.E...
Room automation stations
Function
Device ready to operate.
No supply for device.
Start-up or program halted
OK
HW or SW error.
Wrong or corrupted application.
OK.
Island bus communication.
No modules connected
TX-I/O modules not configured or
communication fault.
OK.
KNX PL-Link communication.
KNX PL-Link not used or communication
fault.
OK
DALI bus communication
DALI not used or communication fault.
OK.
No application loaded.
Physical identification of the room
automation station.
Link active
Link inactive
Network activity
Link 100 Mbps
Link 10 Mbps
2s
Description
Ethernet
Physical identification of the room automation
station in the network.
DALI test: All ballasts On or Off.
DALI test: Start / stop the following function:
"All ballasts blink (2 s On, 2 s Off)".
21s
5 Hz
5 Hz
1s
1s
2s
CM1N9203en_05
9222z02
5 / 12
2015-11-23

Hide quick links: