  • Page 1 SIEMENS BANY Agent Compact Operating Instructions BANY Agent Compact Operating Instruction...
  • Page 2 If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. BANY Agent Compact Operating Instruction...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problem.
  • Page 4: Table Of Contents

    Introduction to the BANY Agent ..................6 Produktgruppe BANY Agent ..................7 Type designations ......................7 Safety notes .........................8 Important notes on using the BANY Agent product family ..........8 Important notes on using the device in hazardous areas..........10 Description .........................11 Unpacking and checking .....................11 BANY Agent components of the product ..............11...
  • Page 5 Power supply - general ....................26 Power supply ......................27 5.3.1 Connecting the power supply ................27 5.3.2 24 V DC – product group BANY Agent..............28 Digital In/Outputs ......................29 Connecting functional ground..................29 Technical data ........................30 Construction, installation and environmental conditions ..........30 Connectors and electrical data ..................31 Cable lengths ......................33...
  • Page 6: Introduction

    (all) added to it. Where ca I find more detailed information on the product ? A CD is supplied with the BANY Agent on which you will find a detailed description of the products in PDF format in the relevant subfolder.
  • Page 7: Produktgruppe Bany Agent

    BANY Agent without TAP 9AE4140-1BA00 1.3 Type designations Structure oft he type designation The type designation of an BANY Agent is made up of several parts that have the following meaning: 9AE4140-1BA01 BANY Agent with TAP 9AE4140-1BA02 BANY Agent without TAP...
  • Page 8: Safety Notes

    2 Safety notes 2.1 Important notes on using the BANY Agent product family Safety notices on the use of the devices The following safety notices must be adhered to when setting up and operating the device and during all associated work such as installation, connecting up, replacing devices or opening the device.
  • Page 9 Protection against transient voltage surges Provisions shall be made to prevent the rated voltage from being exceeded by transient voltage surges of more than 40%. This criterion is fulfilled, if supplies are derived from SELV (Safety Extra-Low Voltage) only. BANY Agent Compact Operating Instruction...
  • Page 10: Important Notes On Using The Device In Hazardous Areas

    This equipment is suitable for use in Class I, Division 2, Groups A, B, C and D or non- hazardous locations only. WARNING Restricted area of application This equipment is suitable for use in Class I, Zone 2, Group IIC or non-hazardous locations only. BANY Agent Compact Operating Instruction...
  • Page 11: Description

    2. Check all the parts for transport damage. WARNING Do not use any parts that show evidence of damage ! 3.2 BANY Agent components of the product Note When shipped, the slots for the media modules have a dummy cover fitted.
  • Page 12: Product Group Bany Agent

    3.3 Product group BANY Agent 3.3.1 BANY Agent with TAP Possible attachments 7 electrical Ethernet RJ45 jacks (with securing collar) for connection of end devices or other network segments 1 USB Master connector 1 plug-in terminal block 4-pin for connecting the power supply and the digital in/Outputs...
  • Page 13 Bild 1 BANY Agent mit TAP BANY Agent Compact Operating Instruction...
  • Page 14: Bany Agent Without Tap

    3.3.2 BANY Agent without TAP Possible attachments 3 electrical Ethernet RJ45 jacks (with securing collar) for connection of end devices or other network segments 1 USB Master connector 1 plug-in terminal block 4-pin for connecting the power supply and the digital In/Outputs...
  • Page 15 BANY Agent Compact Operating Instruction...
  • Page 16: Real Time Ethernet Ports Tap A, Tap B

    The ethernet frames are forwarded from one TAP port to the other without delay. This also works if the Bany Agent is powered off. It is not possible for the Bany Agent to send packets out of the TAP ports.
  • Page 17: Ethernet Ports Network N1 Und N2

    Fast Ethernet and Gigabit Ethernet is supported. 3.7 Control Port Ctrl: RJ45 Ethernet Port connect the Bany Agent to a PC via this port. 3.8 USB Host The hardware contains one USB host port. Mass storage devices can be connected here.
  • Page 18: Micro Sd Karte

    The Micro SD memory card should not be removed or inserted by the user. In the BANY Agent, the Micro SD memory card is located behind the sealing screw on the rear of the device. To remove the sealing screw, use a coin or a wide blade screwdriver.
  • Page 19: Digital I/O

    3.10 Digital I/O The hardware has 3 connectors which can be used as a digital input or a digital output. DI/DO: digitaler Eingang oder digitaler Ausgang SGND: Signal Masse BANY Agent Compact Operating Instruction...
  • Page 20: Description Of The Leds

    There is a reset button below the USB port. After a reset, the box is reset and switches to startup mode. While the startup LED is flashing, the box cannot be accessed from the Web interface or via BANY Scope. BANY Agent Compact Operating Instruction...
  • Page 21: Assembling

    80°C. CAUTION Provide suitable shade to protect the Bus Analyser against direct sunlight. This avoids unnecessary warming of the BANY Agent and prevents premature aging of the Bus Analyser and cabling. NOTICE When installing and operating the device, keep to the installation instructions and safety-related notices as described in this document and in the manual SIMATIC NET Industrial Ethernet Twisted Pair and Fiber Optic Networks.
  • Page 22: Installation Options

    4.3.1 Installation on a DIN rail CAUTION If the BANY Agent is liable to be subjected to serve vibration (> 10 g), use an S7-300 standard rail for installation. The DIN rail does not provide adequate support if vibration exceeds 10 g.
  • Page 23 Installation Install the BANY Agent on a 35 mm DIN rail complying with DIN EN 50022. 1. Hang the BANY Agent on the DIN rail and then push it in against the rail until it clips into place.. 2. Fit the connectors for the power supply.
  • Page 24: Installation On A Standard Rail

    4.3.2 Installation on a standard rail Installation on a SIMATIC S7-300 standard rail 1. Place the upper guide at the top of the BANY Agent housing in the S7 standard rail. 2. Screw the BANY Agent to the underside of the standard rail.
  • Page 25: Wall Mounting

    40 mm long). 2. Connect the electrical cable connecting cables. 3. Fit the connectors for the digital In/Outputs. 4. Insert the terminal blocks into the sockets on the BANY Agent. Note For more exact dimensions, please refer to the section „Dimension drawings“.
  • Page 26: Connecting

    Ethernet cables to incorrectly configured ports causes overload in the network and a breakdown in communication. 5.2 Power supply - general WARNING You can recognize the type of power supply on a warning on the device and the labeling of the connector to the power supply. BANY Agent Compact Operating Instruction...
  • Page 27: Power Supply

    Never operate the device with AC voltage or DC voltage higher than 32 V DC. CAUTION If the BANY Agent are supplied over long 24 V power supply lines or networks, measures are necessary to prevent interference by strong electromagnetic pulses on the supply lines. These can result, for example, due to lightning or switching of large inductive loads.
  • Page 28: Dc - Product Group Bany Agent

    To wire up the power connector, use a copper cable of category 18 - 12 AWG or cable with a cross-section of 0.75 to 2.5 mm². 5.3.2 24 V DC – product group BANY Agent 24 V safety extra-low voltage overview...
  • Page 29: Digital In/Outputs

    Please note that the BANY Agent must be grounded over one securing screw with minimum resistance. If an BANY Agent is mounted on a non-conducting base, a grounding cable must be installed. The grounding cable is not supplied with the device. Connect the paint-free surface of the BANY Agent to the nearest grounding point using the grounding cable.
  • Page 30: Technical Data

    6.1 Construction, installation and environmental conditions Construction BANY Agent with TAP BANY Agent without TAP Dimension (W x H x D) 60 x 125 x 125 mm...
  • Page 31: Connectors And Electrical Data

    90°.. 6.2 Connectors and electrical data Connection for end devices or network components (BANY Agent with TAP 24 V DC) 7 x RJ45-jacks with MDI-X-assignment 10/100/1000 Mbit/s (half-/full duplex) (BANY Agent with TAP 24 V DC)
  • Page 32 Electrical data: Current consumption and power loss Device version Current consumption Effective power (power supply) loss (BANY Agent with TAP 24 V DC) 0,50 mA 12 W (BANY Agent without TAP 24 V DC) 0,30 mA 7,2 W Electrical Data: Overcurrent protection...
  • Page 33: Cable Lengths

    + 10 m TP Cord + 10 m TP Cord IE FC Flexible Cable, with IE FC Outlet RJ45 0 … 90 m 4 x 2, AWG22 + 10 m TP Cord + 10 m TP Cord BANY Agent Compact Operating Instruction...
  • Page 34: Other Properties

    6.4 Other properties Mean Time between failure (MTBF) MTBF 40 years BANY Agent Compact Operating Instruction...
  • Page 35: Dimension Drawings

    7 Dimension drawings 7.1 BANY Agent with TAP BANY Agent Compact Operating Instruction...
  • Page 36 BANY Agent Compact Operating Instruction...
  • Page 37 BANY Agent Compact Operating Instruction...
  • Page 38: Bany Agent Without Tap

    7.2 BANY Agent without TAP BANY Agent Compact Operating Instruction...
  • Page 39 BANY Agent Compact Operating Instruction...
  • Page 40 BANY Agent Compact Operating Instruction...
  • Page 41: Approvals

    8 Approvals 8.1 BANY Agent approvals, certificates The specified approvals only when the corresponding mark is printed on the product. You can check which of the following approvals have been granted for your product by the markings on the type plate.
  • Page 42 Note for manufacturers of machines This product is not a machine in the sense of the EC Machinery Directive. There is therefore no declaration of conformity relating to the EC Machinery Directive 89/392/EEC for this product. BANY Agent Compact Operating Instruction...
  • Page 43 Approval of SIMATIC/SIMATIC NET Products for Direct Installation in Ex-Zone 2“ You will find this on the Internet on the pages of Siemens Industry Automation Customer Support under the following entry ID: 33118441 (http://support.automation.siemens.com/WW/view/de/33118441)
  • Page 44: Bany Agent Conformity Certificates

    CI. 1, Div. 2, GP. A, B, C, D, T4 CI. 1, Zone 2, GP. IIC T4 8.2 BANY Agent Conformity certificates Declaration of Conformity You will find the EC Declaration of Conformity for these products on the Internet at the following address: http://support.automation.siemens.com/WW/view/de/33118441...
  • Page 45: Overview Of Bany Agent Approvals

    For temperature information “T..” or the maximum ambient temperature “Ta:..”), refer to the type plate. Note Shipbuilding approval No applications for shipbuilding approvals will be made for the BANY Agent 8.4 Mechanical stability (in operation) BANY Agent Device: (Variant) IEC 60068-2-6 vibration IEC 60068-2-27 shock 5 –...
  • Page 46 BANY Agent Compact Operating Instruction...

Table of Contents