Electrical Connection - Siemens sitrans LR 400 Instruction Manual

Hide thumbs Also See for sitrans LR 400:
Table of Contents

Advertisement

Electrical Connection

ac version:
Hart Wiring
cable clamp
3
4 5
6
7 8
Rated temperature of
connection cables must
mA
exceed maximum ambient
temperature by at least 15 K
The equipment must be protected by a 15A fuse or circuit breaker in the building
installation.
A circuit breaker or switch in the building installation, marked as the disconnect
switch, shall be in close proximity to the equipment and within easy reach of the
operator.
All field wiring must have insulation suitable for at least 250 V.
dc version:
Hart Wiring
cable clamp
3
4 5
6
7 8
Rated temperature of
connection cables must
mA
exceed maximum ambient
temperature by at least 15 K
DC input terminals shall be supplied from an SELV source in accordance with IEC
1010-1 Annex H.
Notes (AC and DC versions):
4-20 mA, Profibus-PA, DC input circuits, 14 - 20 AWG, shielded copper wire
AC input circuit, min 14 AWG copper wire
Recommended torque on terminal clamping screws, 0.5 - 0.6 Nm
Page 18
earth
terminal
1 2
L
L
1
2
N
earth
terminal
1 2
19-30 V
SITRANS LR 400 – INSTRUCTION MANUAL
Profibus Wiring
cable clamp
3
4 5
6
7 8
Rated temperature of
connection cables must
PROFI-
exceed maximum ambient
BUS PA
temperature by at least 15 K
Profibus Wiring
cable clamp
3
4 5
6
7 8
Rated temperature of
connection cables must
PROFI-
exceed maximum ambient
BUS PA
temperature by at least 15 K
earth
terminal
1 2
L
L
1
2
N
earth
terminal
1 2
19-30 V
7ML19985FH03

Advertisement

Table of Contents
loading

Table of Contents