Download Print this page
Siemens MICROMASTER Vector 6SE32 Getting Started

Siemens MICROMASTER Vector 6SE32 Getting Started

Advertisement

Quick Links

MICROMASTER Vector 6SE32
MIDIMASTER Vector 6SE32
Getting Started
Caution: Before installing and
putting this equipment into
operation, please read the
Operating Instructions Manual for
Safety Precautions and Warnings
SIEMENS MICROMASTER
The MICROMASTER Vector (MMV) and the
MIDIMASTER Vector (MDV) are a range of frequency
inverters for controlling the speed of three phase AC
induction motors.
Step 1
Connecting up the MMV and MDV
230V Single Phase
400V Three Phase
Delta connection for
Star connection for
230V 3 phase
400V 3 phase
Note: Motors above 11kW are usually configured
400V Delta / 690V Star.
In this case the motor should be connected in Delta.
MIDIMASTER Vector (MDV)
The MDV electrical installation section of the
Operator Instructions Manual shows the position of
the terminals used to connect the power and the
motor.
While the motor is
turning, press this UP
'
STOP
'
button and watch as
Press this
the motor turns faster
green button
and the value in the
(RUN button)
display increases. It
to start the
Jog
will keep increasing
motor.
until it reaches 50 Hz.
Hz
Forward/
When the inverter
P
reverse
reaches 50Hz output,
press this DOWN button
'DOWN' button
and watch the motor
This is the
This is the
speed and display value
'
STOP button.
STOP button
'
decrease.
At any time, press the 'STOP' button and watch the
motor stop.
Step 3
Changing the speed of the motor
The default output frequency of the drive is 5Hz (see
Hints and Tips to convert this to RPM). This speed will
probably be too low for most applications and a speed
change may be required. The following steps will allow
you to change the preset value of the inverter output to
the required speed.
Step / Action
Display
Press the 'P' button to access the parameter settings.
P000
Press the
button 5 times until the display reads P005.
P005
005.0
Press the 'P' button to display the current parameter value.
Press the
button to change the value to 35Hz. (This
035.0
number can be any number between 0 and 50Hz - default.)
P005
Press the 'P' button to store the new value.
P000
Press the
button until the display reads P000.
Press the 'P' button to exit the parameterisation procedure.
000.0
The display will alternate between the output frequency and
the frequency set point.
035.0
The required speed has now been stored.
This method is used to access all parameters.
The drive can now be started by pressing the 'RUN'
button. It will ramp up to the frequency held in parameter
P005 and remain there. To stop the drive press the
'STOP' button, the drive will then ramp down to 0Hz
output.
Default Parameters:
Digital input
Terminal
Parameter
Default
1
5
P051 = 1
ON right
ON left
2
6
P052 = 2
3
7
P053 = 6
Fixed frequency 3
4
8
P054 = 6
Fixed frequency 2
5
16
P055 = 6
Fixed frequency 1
6
17
P356 = 6
Fixed frequency 6
Output
Relays
1
18/19/20
P061 = 6
Fault identification
2
21/22
P062 = 8
Warning active
Fault Codes:
F001
Overvoltage
F002
Overcurrent
F003
Overload
F004
Overheating of motor (PTC)
F005
Inverter overtemperature
(internal PTC)
F074
Motor overtemperature by I²t
calculation
Other faults, see manual
For further Technical Support
Information, and to submit your
suggestions for improvements,
see our Web Site:
http://www.con.siemens.co.uk
Siemens plc
Automation and Drives
Varey Road
Congleton
Cheshire CW12 1PH
Great Britain
G85139-H1751-U568-D1
May 1999
English
Order Number: 6SE3286-4BA86

Advertisement

loading

Summary of Contents for Siemens MICROMASTER Vector 6SE32

  • Page 1 MIDIMASTER Vector (MDV) are a range of frequency button and watch as Press this inverters for controlling the speed of three phase AC the motor turns faster MICROMASTER Vector 6SE32 green button induction motors. and the value in the (RUN button)
  • Page 2 Step 4 Controlling the motor speed with Hints and Tips Commissioning MICROMASTER Vector / MIDIMASTER Vector a potentiometer The direction of rotation of the motor can be reversed during commissioning by changing A potentiometer can be used to control the running Frequently used parameters Display parameters Basic parameters...

This manual is also suitable for:

Midimaster vector 6se32