Siemens SIPROTEC 7SJ61 Technical Data Manual

Siemens SIPROTEC 7SJ61 Technical Data Manual

Multifunction protection with control
Hide thumbs Also See for SIPROTEC 7SJ61:
Table of Contents

Advertisement

SIPROTEC4
Multifunction protection with
control
7SJ62 / 7SJ63
Communication module
Modbus
Revision: 1.0
Edition: April 2000
C53000-L1840-C001-01
Preface
Bus specific parameters
Supported Modbus functions
Exception responses of the Modbus
slave
Annunciations to the Modbus master
Data type definitions
Modbus register map
Technical data
Glossary
Index
Cover
1
2
3
4
5
6
7

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPROTEC 7SJ61

  • Page 1 Preface Bus specific parameters SIPROTEC4 Supported Modbus functions Exception responses of the Modbus Multifunction protection with slave control Annunciations to the Modbus master 7SJ62 / 7SJ63 Data type definitions Communication module Modbus register map Modbus Technical data Glossary Index Cover Revision: 1.0 Edition: April 2000 C53000-L1840-C001-01...
  • Page 2 Your suggestions are welcome. Subject to change without prior notice. SIPROTEC und DIGSI are registered trademarks of Siemens AG. Modbus and Modbus Plus are trademarks of Modicon, Inc. Other designations in this manual may be trademarks that if used by third parties for their own purposes may violate the rights of the owner.
  • Page 3 Order number Overcurrent, overload C53000-G1140-C118-2 Function, operation, assembly and motor protection with and commissioning of the control SIPROTEC device 7SJ61 SIPROTEC 7SJ61 Multifunction protection C53000-G1140-C121-2 Function, operation, assembly with control and commissioning of the SIPROTEC 7SJ62 SIPROTEC device 7SJ62 Multifunction protection...
  • Page 4 4.2 and Modbus communication module. See our catalog of courses for a list of available courses or contact our Training courses training center in Nuremberg. If you have questions to the SIPROTEC devices, contact your Siemens Questions representative. 7SJ61/62/63 6MD63 - Modbus...
  • Page 5 Revision index Modified chapters / Edition Reasons of modification pages First edition Apr 12 , 2000 7SJ61/62/63 6MD63 - Modbus C53000-L1840-C001-01...
  • Page 6 Revision index 7SJ61/62/63 6MD63 - Modbus C53000-L1840-C001-01...
  • Page 7: Table Of Contents

    Table of contents Bus specific parameters ....................1-1 Supported Modbus functions..................2-1 Exception responses of the Modbus slave..............3-1 Annunciations to the Modbus master ................4-1 Data type definitions ......................5-1 Single command (SC) / Single-point indiation (SP) ..........5-2 Double command (DC) / Double-point indication (DP) ........5-2 Measured value (signed integer) .................5-3 Metered measurand (unsigned long) ..............5-3 Modbus register map .....................6-1...
  • Page 8 Table of contents 6.4.5 Register addresses 10145 to 10188: Directional time overcurrent protection ..............6-13 6.4.6 Register addresses 10193 to 10200: Unbalanced load protection ................6-15 6.4.7 Register addresses 10209 to 10224: Frequency protection ..................6-15 6.4.8 Register addresses 10225 to 10247: Undervoltage and overvoltage protection ............6-16 6.4.9 Register addresses 10257 to 10278: Sensitive ground fault protection................6-17...
  • Page 9 Table of contents Technical data.........................7-1 Modbus slave for the SIPROTEC devices ............7-1 Hardware interface....................7-1 7.2.1 Connection via the AME module................7-2 7.2.2 Connection via the AMO module .................7-2 Glossary...........................8-1 Index..........................9-1 7SJ61/62/63 6MD63 - Modbus C53000-L1840-C001-01...
  • Page 10 Table of contents List of figures Figure 5-1 Data typ single command / single-point indication ..........5-2 Figure 5-2 Data type double command / double-point indication ..........5-2 Figure 5-3 Data type measured value (signed integer) ............5-3 Figure 5-4 Data type metered measurand (unsigned integer) ..........5-3 List of tables Table 2-1 Supported Modbus functions ................2-2...
  • Page 11: Bus Specific Parameters

    Bus specific parameters Bus specific parameters The following settings for the serial communication between the Modbus master and the Modbus slave of the SIPROTEC device have to be defined when programming the device using the parameterization system DIGSI. Permissible slave addresses are in the range between 1 and 247. Slave address The Modbus slave of the SIPROTEC device supports the two serial Modbus mode...
  • Page 12 Bus specific parameters Processing of If one of the Modbus messages "Force Single Coil", "Preset Single Register", "Force Multiple Coil" or "Preset Single Regs" (ref. to chap. 2) broadcast is transmitted from the Modbus master to the Modbus slaves using slave messages address 0 all Modbus slaves recognize this message as a broadcast message and process it.
  • Page 13: Supported Modbus Functions

    Supported Modbus functions Supported Modbus functions The following Modbus functions are supported by the Modbus slave of the SIPROTEC device: Function Function Broadcast Description code name supported? Read Coil Reading one or several coil status registers of the Modbus slave. Status A maximum of 1970 registers can be read with one message.
  • Page 14: Table 2-1 Supported Modbus Functions

    Supported Modbus functions Function Function Description Broadcast code name supported? Force Writing (force to ON or OFF) one or several coil status registers (and Multiple Coils binary outputs of the SIPROTEC device assigned with these). (0X-Register) A maximum of 1970 registers can be written with one message. Preset Function presets one or several holding registers register.
  • Page 15: Exception Responses Of The Modbus Slave

    Exception responses of the Modbus slave Exception responses of the Modbus slave If the Modbus slave receives a query from the Modbus master which cannot be processed (e.g. a request to read a non-existent register), then the slave answers with an exception response message. The following exception codes are signaled in a exception response message to the Modbus master by the Modbus slave of the SIPROTEC device:...
  • Page 16 Exception responses of the Modbus slave 7SJ61/62/63 6MD63 – Modbus C53000-L1840-C001-01...
  • Page 17: Annunciations To The Modbus Master

    Annunciations to the Modbus master Annunciations to the Modbus master Note When analysing the annunciations of the SIPROTEC device in the Modbus master, it should be noted that due to the cycle period of the Modbus system (period between two following queries of the same data of the Modbus slave) temporary changes of an annunciation’s value (ON and OFF within one cycle) may eventually not be recognized.
  • Page 18 Annunciations to the Modbus master 7SJ61/62/63 6MD63 – Modbus C53000-L1840-C001-01...
  • Page 19: Data Type Definitions

    Data type definitions Data type definitions Following data types are used for storage of variables in Modbus registers: • Single-point indications • Single commands • Double-point indications • Double commands • Measured values (signed integer) • Metered measurands (unsigned long) Note The storage of variables of more complex data types in the Modbus holding registers (i.e.
  • Page 20: Single Command (Sc) / Single-Point Indiation (Sp)

    Data type definitions Single command (SC) / Single-point indiation (SP) Range of values: 0 – OFF 1 – ON Bit x Bit x+1 Bit x+2 SC/SP 1 SC/SP 2 SC/SP 3 Coil / input status register or one bit of a holding register Figure 5-1 Data typ single command / single-point indication Double command (DC) / Double-point indication (DP)
  • Page 21: Measured Value (Signed Integer)

    Data type definitions Double commands are exclusively controled using Modbus function „Force Multiple Coils“ (ref. to chap. 2). Measured value (signed integer) Range of values: -32768 to +32767 (-32768 = overflow or invalid) Measured value Byte 1 (MSB) Byte 0 (LSB) Input / holding register xxxx Figure 5-3 Data type measured value (signed integer)
  • Page 22 Data type definitions 7SJ61/62/63 6MD63 – Modbus C53000-L1840-C001-01...
  • Page 23: Modbus Register Map

    Modbus register map Modbus register map Explanation Note The examples shown in this chapter 6.1 do not necessarily correspond to the real allocation of the objects in the register mapping. Chapters 6.3 to 6.6 define the mapping of the data objects of the SIPROTEC devices 7SJ61, 7SJ62, 7SJ63 and 6MD63 to the associated Modbus registers.
  • Page 24: Notes For Parametrization In Digsi

    Modbus register map Notes for parametrization in DIGSI Only those SIPROTEC objects can be transmitted or controlled by Modbus which are listed in the column “Designation of the SIPROTEC objects“. All these objects are already contained in the standard parameter set and they can be identified by their name or their "Internal object no."...
  • Page 25: Coil Status Registers (0X References)

    Modbus register map Coil status registers (0X references) The coil status register block allows the Modbus master: • command outputs through the output relays of the SIPROTEC device (external commands), • manipulation of taggings (internal commands), which can be changed by Modbus, •...
  • Page 26: Register Addresses 00033 To 00054: Single Commands

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 00017 Switching device D4 (UsrDC4) Impulse output, – 2 relays, 1-pole 00018 Switching device D4 (UsrDC4) 00019 – reserved – 00032 6.3.2 Register addresses 00033 to 00054: Single commands •...
  • Page 27: Register Addresses 00065 To 00071: Internal Commands

    Modbus register map Note • The command output mode (pulse output, continuous output) is changeable for the single commands using parametrization software DIGSI. The command output modes indicated in above table are predefined. • The switching direction OFF for single commands with pulse output is not permitted and is rejected in the SIPROTEC device.
  • Page 28: Register Addresses 00081 To 0096: Application Logic Cfc

    Modbus register map Control mode REMOTE Control mode with control authority is REMOTE, option of unlocked control with Modbus. • Changing the “Control mode REMOTE“ to UNLOCKED permits one unlocked control operation via Modbus. After execution of the command, the tagging “Control mode REMOTE“ in the SIPROTEC device will automatically be reset to LOCKED.
  • Page 29 Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 00092 CFC-Incoming annunciation 12 Tagging ON/OFF, – (UsCfcSpI12) released as CFC input 00093 CFC-Incoming annunciation 13 Tagging ON/OFF, – (UsCfcSpI13) released as CFC input 00094 CFC-Incoming annunciation 14 Tagging ON/OFF, –...
  • Page 30: Register Addresses 00257 To 00264: Exception Flags

    Modbus register map 6.3.5 Register addresses 00257 to 00264: Exception flags • Registers are write-protected • The contents of these registers are also readable using function "Read Exception Status" (function code 7). Register Designation of the Internal Comments address SIPROTEC objects object no.
  • Page 31: Input Status Registers (1X References)

    Modbus register map Input status registers (1X references) The input status register block allows the Modbus master to scan the current status of the input channels as well as the annunciations generated in the SIPROTEC device (e.g. protection annunciations, status annunciations). Note The allocation of the input channels to the binary inputs is defined during parameterization of the devices.
  • Page 32: Register Addresses 10049 To 10064: Application Logic Cfc

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10019 Input channel 19 (UsrSpO/O19) Single-point indication ON/OFF – 10020 Input channel 20 (UsrSpO/O20) Single-point indication ON/OFF – 10021 Input channel 21 (UsrSpO/O21) Single-point indication ON/OFF –...
  • Page 33: Register Addresses 10065 To 10089: Automatic Recloser Status

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10057 CFC-Output indication 9 Single-point indication ON/OFF, – (UsCfcSpO9) released as CFC output 10058 CFC-Output indication 10 Single-point indication ON/OFF, – (UsCfcSpO10) released as CFC output 10059 CFC-Output indication 11 Single-point indication ON/OFF,...
  • Page 34: Register Addresses 10097 To 10137: Time Overcurrent Protection

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10082 79 L-L Sequence 1 = 79-A/R multi-phase reclosing sequence 2879 10083 >ZSC ON 1 = >Switch zone sequence coordination ON 2722 10084 >ZSC OFF 1 = >Switch zone sequence coordination OFF 2723 10085 TRIP Gnd Fault...
  • Page 35: Register Addresses 10145 To 10188: Directional Time Overcurrent Protection

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10116 50-2 picked up 1 = 50-2 picked up 1800 10117 50-2 TimeOut 1 = 50-2 Time Out 1804 10118 50-2 TRIP 1 = 50-2 TRIP 1805 10119 50-1 picked up...
  • Page 36 Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10150 >BLOCK 67N-TOC 1 = >BLOCK 67N-TOC 2624 10151 Phase A forward 1 = Phase A forward 2628 10152 Phase B forward 1 = Phase B forward 2629 10153 Phase C forward...
  • Page 37: Register Addresses 10193 To 10200: Unbalanced Load Protection

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10183 67/67N pickedup 1 = 67/67N picked up 2691 10184 67 A picked up 1 = 67/67-TOC Phase A picked up 2692 10185 67 B picked up 1 = 67/67-TOC Phase B picked up 2693 10186...
  • Page 38: Register Addresses 10225 To 10247: Undervoltage And Overvoltage Protection

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10218 81-2 picked up 1 = 81-2 picked up 5233 10219 81-3 picked up 1 = 81-3 picked up 5234 10220 81-4 picked up 1 = 81-4 picked up 5235 10221 81-1 TRIP...
  • Page 39: Register Addresses 10257 To 10278: Sensitive Ground Fault Protection

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10247 59-1 TRIP 1 = 59 TRIP 6570 10248 reserved – 10256 6.4.9 Register addresses 10257 to 10278: Sensitive ground fault protection Register Designation of the Internal Comments address...
  • Page 40: Register Addresses 10289 To 10298: Circuit Breaker Failure Protection

    Modbus register map 6.4.10 Register addresses 10289 to 10298: Circuit breaker failure protection Register Designation of the Internal Comments address SIPROTEC objects object no. 10289 >BLOCK 50BF 1 = >BLOCK 50BF 1403 10290 >50BF ext SRC 1 = >50BF initiated externally 1431 10291 50BF OFF...
  • Page 41: Register Addresses 10337 To 10342: Startup Supervision

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10324 66 ACTIVE 1 = 66 Motor start protection is ACTIVE 4826 10325 66 TRIP 1 = 66 Motor start protection TRIP 4827 10326 reserved – 10336 6.4.13 Register addresses 10337 to 10342: Startup supervision Register...
  • Page 42: Register Address 10385: Fault Locator

    Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10372 51N InRushPU 1 = 51N InRush picked up 7554 10373 InRush OFF 1 = InRush is switched OFF 7556 10374 InRushPhBLOCKED 1 = InRush Phase is BLOCKED 7557 10375 InRush Gnd BLK...
  • Page 43: Register Addresses 10401 To 10408: Measurement Supervision

    Modbus register map 6.4.18 Register addresses 10401 to 10408: Measurement supervision Register Designation of the Internal Comments address SIPROTEC objects object no. 10401 Fail I Superv. 1 = Failure: general Current Supervision 10402 Failure <sum> I 1 = Failure: Current Summation 10403 Fail I balance 1 = Failure: Current Balance...
  • Page 44 Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 10437 >Manual Close 1 = >Manual close signal 10438 >DataStop 1 = >Stop data transmission 10439 >Test mode 1 = >Test mode 10440 >Door open 1 = >Cabinet door open –...
  • Page 45: Input Registers (3X References)

    Modbus register map Input registers (3X references) The input register block allows the Modbus master to read the values of the the analog inputs of the SIPROTEC device (recorded measured values). Note Depending on the device composition not all of the indicated analog inputs (and corresponding Modbus registers) may be available in the SIPROTEC device.
  • Page 46: Recorded Measured Values

    Modbus register map 6.5.2 Recorded measured values Register Designation of the Scaling Internal Comments address SIPROTEC objects (32767 corresponds to ...) object no. 30001 Ia = 1: 3276.7 A 2: 32.767 kA 3: 3276.7 A 30002 Ib = 1: 3276.7 A 2: 32.767 kA 3: 3276.7 A 30003...
  • Page 47 Modbus register map Register Designation of the Scaling Internal Comments address SIPROTEC objects (32767 corresponds to ...) object no. 30023 V2 = V2 (negative sequence) 1: 327.67 kV 2: 32.767 kV 3: 32.767 kV 30024 3Vo = 3Vo (zero sequence) 1: 327.67 kV 2: 32.767 kV 3: 32.767 kV...
  • Page 48: Holding Registers (4X References)

    Modbus register map Holding registers (4X references) The holding register block allows the Modbus master to read system information, measured values – mean values, metered measurands as well as fault locations. Note Depending on the device composition not all of the indicated measured values/metered measurands (and corresponding Modbus registers) may be available in the SIPROTEC device.
  • Page 49 Modbus register map Register Designation of the Internal Comments address SIPROTEC objects object no. 40129 / 2 Alarm Sum Event 1 = Alarm Summary Event ON 40129 / 2 Relay PICKUP 1 = Relay PICKUP (protection, summary alarm) 40129 / 2 Relay TRIP 1 = Relay GENERAL TRIP command (common, summary alarm)
  • Page 50: Register Addresses 40201 To 40215: Metered Measurands

    Modbus register map 6.6.3 Register addresses 40201 to 40215: Metered measurands • Data type definition ref. to chap. 5.4, • Registers are write-protected The scaling of the metered measurands, which are derived from Scaling measured values, refers to: 60000 impulses per hour for V = V and I = I prim prim...
  • Page 51: Register Addresses 40251 To 40257: Measured Values - Mean Values

    Modbus register map Note • The scaling of the metered measurands at binary inputs ("Wp(puls)" and "Wq(puls)") depends on the externally connected pulse generator. • The error status bit of the metered measurands (except of the operating hours meter) is set after a initial start or restart of the SIPROTEC device until the second update cycle of the metered measurands after the reset.
  • Page 52: Register Addresses 40301 To 40305: Fault Locator And Fault Currents

    Modbus register map 6.6.5 Register addresses 40301 to 40305: Fault locator and fault currents • Data type definitions ref. to chap. 5.3, • Registers are write-protected Note Always the latest fault location and fault currents are stored in the Modbus registers. In the event of a fault, reading out of the fault record protocol from the SIPROTEC device is necessary for an exact diagnosis.
  • Page 53: Technical Data

    Technical data Technical data Modbus slave for the SIPROTEC devices Modbus slave Slave addresses 1 – 247 Modbus modes RTU, ASCII • Modbus functions Read Coil Status • Read Input Status • Read Holding Register • Read Input Register • Force Single Coil •...
  • Page 54: Connection Via The Ame Module

    Technical data 7.2.1 Connection via the AME module Connections 9pole D-SUB outlet (ref. to Table 7-2) Protocol semi-duplex Max. line length 1000 m / 3300 ft Insulation level 500 V Bus termination Integrated, connectable terminating resistors 221 Ohm between A and B 392 Ohm between B and VCC1 as well as A and GND1 Input resistor not terminated ≥...
  • Page 55: Glossary

    Glossary Glossary Universal asynchronous communication module with (electrical) isolated RS485 interface for the SIPROTEC devices from Siemens. Universal asynchronous communication module with fibre-optical interface for the SIPROTEC devices from Siemens. Automatic Recloser Continuous Function Chart Cyclical Redundancy Check Double Command...
  • Page 56 Glossary 7SJ61/62/63 6MD63 - Modbus C53000-L1840-C001-01...
  • Page 57: Index

    Index Index Numerics 27............6-16 Error with a summary alarm ....6-27 37............6-21 46............6-15 49............6-18 fault currents........... 6-30 50/51............6-12 Fault locator........6-20, 6-30 50BF ............6-18 fibre-optical interface ........ 7-2 50Ns/51Ns..........6-17 Frequency protection......6-15 55............6-21 59............
  • Page 58 Index Sensitive ground fault protection .... 6-17 Set point alarms........6-21 setting group ..........6-6 single command ........5-2, 6-4 single-point indication ....... 5-2 Slave address ........... 1-1 standard mapping........6-23 standard parameter set ......6-2 Startup supervision ......... 6-19 Stop data transmission ......6-27 System information.........

This manual is also suitable for:

Siprotec 7sj62Siprotec 7sj63Siprotec 6md63

Table of Contents