Specifications - LG LV240HV4 Installation Manual

Single zone vertical air handling unit
Table of Contents

Advertisement

Table 1: Single Zone Vertical Air Handling Unit Specifications
System (Model) (Indoor Unit / Outdoor Unit)
Cooling Capacity
(Min/Rated/Max) (Btu/h)
1
Cooling Power Input
(Min/Rated/Max) (kW)
1
Heating Capacity (Min/Rated/Max) (Btu/h)
Heating Power Input
(Rated) (kW)
1
COP (OD 47°F)
Maximum Heating Capacity (Btu/h)
Outdoor 17°F (WB)/Indoor 70°F (DB)
Outdoor 5°F (WB)/Indoor 70°F (DB)
Power Input [W] @ Outdoor 5 (WB)
Outdoor -4°F (WB)/Indoor 70°F (DB)
EER (OD 95°F)
SEER
HSPF
Power Supply V, Hz, Ø
2
Outdoor Unit Operating Range
3
Cooling (°F DB)
Optional Wind Baffle - Cooling(°F DB)
Heating (°F WB)
Indoor Unit Operating Range
Cooling (°F WB)
Heating (°F DB)
Unit Data
Refrigerant Type
4
Refrigerant Control
IDU Sound Pressure Level dB(A) (H/M/L)
ODU Sound Pressure Level dB(A) (Cool/Heat)
Unit Weight (lbs.)
IDU (Net/Shipping)
ODU (Net/Shipping)
Power Wiring / Communications Cable (No. x AWG)
Compressor
Compressor (Qty.)
Compressor Oil
Dehumidification
Pints/Hour
Fan
IDU Type x Qty.
ODU Type x Qty.
Motor / Drive
Airflow Rate
IDU (H / M / L [CFM])
ODU (Max. [CFM])
Factory Set (High) External Static Pressure (in.wg)
Piping
Liquid (in.)
Vapor (in.)
IDU Condensate Drain, Primary & Secondary O.D. (in.)
Additional Refrigerant Charge (oz./ft.)
Pipe Length
(Minimum/ Maximum) (ft.)
7
Piping Length
(no add'l refrigerant, ft.)
7
Max. Elevation Difference (ft.)
Cooling capacity rating obtained with air entering the indoor unit at 80ºF dry bulb (DB) and 67ºF wet
bulb (WB) and outdoor ambient conditions of 95ºF dry bulb (DB) and 75ºF wet bulb (WB).
Heating capacity rating obtained with air entering the indoor unit at 70ºF dry bulb (DB) and 59ºF wet
bulb (WB) and outdoor ambient conditions of 47ºF dry bulb (DB) and 43ºF wet bulb (WB).
This data is rated 0 ft above sea level with 24.6 of refrigerant line per indoor unit and a 0 ft level
difference outdoor and indoor units.
This unit comes with a dry nitrogen charge.
Power Input is rated at high speed.
1
Power wiring to the ODU is field supplied, solid or stranded, and must comply with the applicable local
2
LV180HV4
(LVN180HV4/LUU188HV)
8,000 ~ 18,000 ~ 24,000
0.65 ~ 1.35 ~ 2.70
9,000 ~ 20,000 ~ 23,000
0.65 ~ 1.60 ~ 2.10
5
5
3 x 12 / 4 x 18
6
Twin Rotary (1)
Propeller x 1
640 / 580 / 480
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
LV240HV4
(LVN240HV4/LUU248HV)
9,000 ~ 24,000 ~ 28,000
0.70 ~ 1.92 ~ 3.20
10,000 ~ 27,000 ~ 30,000
0.75 ~ 2.26 ~ 2.80
3.66
18,000
22,000
16,000
20,000
2,500
11,000
15,000
13.33
19.0
9.5
208-230/60/1
5 - 118
Yes (-4)
-4 - 64
R410A
42 / 42 / 41
43 / 42 / 41
48 / 52
48 / 52
129 / 140
129 / 140
129 / 141
129 / 141
3 x 12 / 4 x 18
Twin Rotary (1)
PVE
2
Sirocco x 1
Propeller x 1
Brushless Digitally Controlled/Direct
710 / 640 / 480
2,048
0.3
3/8
5/8
3/4 FPT
3/4 FPT
0.43
6.6/164
6.6/164
24.6
98.4
and national codes.
Low Ambient Wind Baffle Kit allows operation down to 0°F in cooling mode.
3
Take appropriate actions at the end of HVAC equipment life to recover, recycle, reclaim or destroy R410A
4
refrigerant according to applicable regulations (40 CFR Part 82, Subpart F) under section 608 of CAA.
Sound pressure levels are tested in an anechoic chamber under ISO Standard 3745.
5
All power/communication cables from the ODU to the IDU to be minimum 18 AWG, 4-conductor,
6
stranded, shielded or unshielded (if shielded, must be grounded to the chassis at the ODU only), and
must comply with applicable and national code.
Piping lengths are equivalent.
7
GENERAL DATA

Specifications

LV360HV4
(LVN360HV4/LUU368HV)
14,000 ~ 36,000 ~ 44,000
1.25 ~ 2.88 ~ 4.80
15,000 ~ 40,000 ~ 47,000
1.35 ~ 3.39 ~ 5.05
3.50
3.46
32,000
30,000
3,200
4,400
22,000
12.50
12.50
18.0
18.0
10.0
10.0
57-77
59-81
EEV
45 / 44 / 43
52 / 54
165 / 188
203 / 232
3 x 10 / 4 x 18
Twin Rotary (1)
PVE
PVE
2.5
3.4
Propeller x 2
1,100 / 1,000 / 900
2,048
1,942 x 2
0.3
0.3
3/8
3/8
5/8
5/8
3/4 FPT
0.43
0.43
6.6/246
24.6
24.6
98.4
98.4
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lv180hv4Lv420hvLv360hv4Lv480hv

Table of Contents