5.4 Wiring

5.4.1 Terminal Treatment of Cables
Follow the procedures below to treat the terminals (at the converter side) of various cables and install the
cables to the terminal block. Use appropriate cables based on the description in Section 5.1 "Cables." Crimp
a round type insulated crimp-type terminal to the end of the cables.
(1) Power cable, current output cable, digital I/O cables
The necessary cables should be ordered from the person responsible for the installation. Strip the sheath of
each conductor as shown in Figure 5.1 and attach a crimping terminal with insulated sleeve to it. The size of
the crimping terminal is as follows:
Integral type : M3.5
Separate type : M3.5
• Connect the power cable to terminal blocks L1 and L2.
• Connect the current output cable to terminal blocks + and -.
• Connect the digital I/O cable to terminal blocks D1, D01, D02 and COM, as required.
(2) Excitation cable
Strip the sheath from the end of each conductor as shown in Figure 5.2, attach an M3.5 crimping terminal
LF622F
with insulated sleeve, and connect it to the terminal blocks X and Y. Connect the red conductor to terminal
block E.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Figure 5.1 Terminal Treatment of Power Cable, Current Output Cable
and Digital I/O cable
X Black
E Red
Y White
Figure 5.2 Terminal Treatment of Excitation Cable
Integral type: M3.5
Crimping terminal
Separate type: M3.5
25~45mm
M3.5 crimping terminal
25~45mm
− 28 −
6F8A0926