HP FlexNetwork MSR3064 Installation Manual page 18

Flexnetwork msr3000 series.
Hide thumbs Also See for FlexNetwork MSR3064:
Table of Contents

Advertisement

Model
3064
IMPORTANT:
• For the MSR3012/3024 router, use a rack with a depth of more than 0.68 m (2.23 ft) as a best
practice.
• For the MSR3044/3064 router, use a rack shelf and a rack with a depth of more than 0.68 m (2.23
ft) as a best practice.
Mounting the router in the rack
WARNING!
The mounting brackets can only support the weight of the router. To avoid damage to the router, do
not place any objects on the router.
To mount the router in a rack:
Use a front mounting bracket to mark the positions of cage nuts, making sure they are at the
1.
same level.
Use a rear mounting bracket to mark the positions of cage nuts, making sure the front and rear
2.
mounting brackets are at the same level.
Router dimensions
Width—440 mm (17.32 in)
Height—130.5 mm (5.14 in) (3 RU)
Total depth—600 mm (23.62 in)
480 mm (18.90 in) for the
chassis
60 mm (2.36 in) for connecting
an RPS power cord at the front
of the chassis
60 mm (2.36 in) for connecting
an E1 cable at the rear of the
chassis
Rack clearance requirements
The rack must meet all the following
requirements:
A minimum of 80 mm (3.15 in) between
the front rack post and the front door.
A minimum of 550 mm (21.65 in)
between the front rack post and the rear
door.
310 mm (12.20 in) to 440 mm (17.32 in)
between the front and rear rack posts,
with a clearance of 160 mm (6.30 in)
between the rear rack post and the rear
door, or 465 mm (18.31 in) to 595 mm
(23.43 in) between the front and rear
rack posts.
13