5.1.4

Setting the AC Power Fault Reporting Delay

Normal selection for reporting loss of AC is 60 minutes.
The OFF position is for test purposes only and the normal position for switch 9 is ON. For testing the Low
AC reporting, you can temporarily turn switch 4 OFF without removing power.
Remember to turn the switch ON when testing is complete.
ON
OFF
6
7
8
6
7
8
6
7
8
6
7
8
Figure 5-5. Setting DIP Switch 9 and 10
Switch 9 OFF & Switch 10 OFF:
AC power fault reporting will not be delayed.
9
10
Switch 9 ON & Switch 10 OFF:
AC power fault reporting will be delayed 60 minutes.
9
10
Switch 9 OFF & Switch 10 ON:
AC power fault reporting will be delayed 120 minutes.
9
10
Switch 9 ON & Switch 10 ON:
AC power fault reporting will be delayed 180 minutes.
9
10