SIMATIC 505/500 PROFIBUS DP RBC User Manual Manual Assembly Number: 2806091-0002 Second Edition...
Page 2
All Rights Reserved — Printed in USA Reproduction, transmission, or use of this document or contents is not permitted without express consent of Siemens Energy & Automation, Inc. All rights, including rights created by patent grant or registration of a utility model or design, are reserved.
Page 3
MANUAL PUBLICATION HISTORY SIMATIC 505/500 PROFIBUS-DP RBC User Manual Order Manual Number: Not applicable; manual ships with RBC. Refer to this history in all correspondence and/or discussion about this manual. Event Date Description Original Issue 03/96 Original Issue (2806091–0001) Second Edition 06/99 Second Edition (2806091–0002)
Page 4
LIST OF EFFECTIVE PAGES Pages Description Pages Description Cover/Copyright Second Edition History/Effective Pages Second Edition 1 — 28 Second Edition Registration Second Edition...
DP I/O channel that complies with the PROFIBUS standard. The 505 and 500 PROFIBUS-DP RBCs offer the following features: The RBC is compatible with Siemens S5t and S7t, as well as Series 505, masters. The 505 RBC can be used in all currently-available Series 505 bases (4-, 8-, 11-, and 16-slot models).
Page 7
Festo Limit SW P/B Solenoid PE Cell Metlore-Toledo Third Party Data Logic Products AEG-Modicon Siemens AC/DC Bosch Motors and Drives Turk etc. Notes: The Series 505 remote I/O channel supports up to 15 Series 505/Series 500 remote bases. The PROFIBUS-DP I/O channel supports up to 112 SIMATIC and third-party DP I/O slaves.
Setup and Installation RBC Placement in The 505 PROFIBUS-DP RBC resides in a Series 505 base. Install it in the Base second slot from the left, adjacent to the power supply module. See Figure 2. Figure 2 Location of RBC in a Series 505 Base The 500 PROFIBUS-DP RBC resides in a Series 500 base.
Installing and Use the following steps to install the 505–6870 RBC in a Series 505 base or Removing the RBC to install the 500–6870 RBC in a Series 500 base. WARNING Installing or removing an RBC from a powered-up base disrupts your process and can damage the RBC.
To connect your RBC to a programming device/modem, use a standard 9-pin RS-232 serial cable that conforms at a minimum to the pinouts shown in Figure 4. A standard cable that conforms to the minimum requirements is available through Siemens; specify part number 2601094–8001. Programming Device/Modem RBC RS-232/423...
BIAS SUPPLY +5V NO CONNECT TX/RX– BIAS SUPPLY GND * For Pin 3: Terminal B on Siemens connector. * For Pin 8: Terminal A on Siemens connector. Figure 6 PROFIBUS-DP I/O Port Pinouts CAUTION Pin 5 (BIAS SUPPLY +5V) and Pin 6 (BIAS SUPPLY GND) on the PROFIBUS-DP connector are designed to support the PROFIBUS-DP I/O channel only.
The jumpers on the 505 RBC headers E2 and E3 are for factory use only. Header E4 is shipped without a jumper. Do not alter the default settings unless instructed to do so by a Siemens Technical Support technician. Freeze...
500 RBC Off/Freeze toggle on the 500 RBC switch. See Figure 8. Header E4 is shipped without a jumper. Do not alter the default setting unless instructed to do so by a Siemens Technical Support technician. (factory set) FREEZE Output state (Off/Freeze) switch...
Output State Selection on the RBC (continued) Determining For discrete output modules, the state of the outputs is determined solely by Discrete Output the position of the Off/Freeze jumper E1 on the 505 RBC or the Off/Freeze State switch on the 500 RBC. Determining For analog/word output modules, the state of the outputs is influenced not Analog Output...
Set RBC Station Address cover See Table 3 RESET pushbutton Set Status Display Mode (recessed) Spare RESET Dipswitch block (located behind door) Siemens PROFIBUS REMOTE BASE CONTROLLER Figure 9 500 PROFIBUS-DP Remote Base Controller SIMATIC 505/500 PROFIBUS-DP RBC User Manual...
Page 16
Dipswitch Options (continued) Figure 10 shows the location of the dipswitch and dipswitch cover on the bezel of the 505 RBC. 505 PROFIBUS-DP REMOTE BASE CONTROLLER Status display STATUS 0–MODULE READY 1–DIAGNOSTIC FAILURE Set RS-232/423 2–MODULE MISMATCH Serial Port Baud Rate 3–NO COMMUNICATIONS 4–NO OPERATIONAL FIRMWARE See Table 2...
Baud Rate for the Switches 1 through 3 on the dipswitch control the baud rate of the RS-232 Port RS-232/423 port. Table 2 lists the baud rates available. Invalid selections cause the RBC to report an error on the Status Display and cause the RS-232/423 port to default to 9600 baud.
Page 18
Dipswitch Options (continued) Table 3 Setting the RBC Station Address Switch Number/State Switch Number/State Station Station Station Station Address Address Sta. 0* Sta. 33 Sta. 1 Sta. 34 Sta. 2 Sta. 35 Sta. 3 Sta. 36 Sta. 4 Sta. 37 Sta.
Page 19
Table 3 Setting the RBC Station Address (continued) Switch Number/State Switch Number/State Station Station Station Station Address Address Sta. 66 Sta. 96 Sta. 67 Sta. 97 Sta. 68 Sta. 98 Sta. 69 Sta. 99 Sta. 70 Sta. 100 Sta. 71 Sta.
Dipswitch Options (continued) Reset Pushbutton The RESET pushbutton on the front of the RBC is deliberately recessed to prevent accidental activation. When you press this button, a global reset is immediately performed on the RBC. After completing reset, the RBC assumes the RS-232 baud rate stipulated by the setting of switches 1 through 3 on the dipswitch, and the station address indicated by switches 4 through 10.
Page 21
When the CPU logs an RBC off the system, it sets a corresponding bit in one of the status words that are available to your RLL program. Your RLL program can use these bits to detect the loss of the RBC and control the outputs of other bases as appropriate for your application.
Action: None. Serious malfunction. Action: Place the system in a safe state and Diagnostic Failure None consult Siemens Technical Support. (In the U.S.A., call 423–461–2522.) I/O modules installed in this base do not match the expected configuration in the PROFIBUS-DP master.
Page 23
Hardware watchdog timeout that immediately resets the RBC. Action: Serious malfunction. Place the Watchdog Timer Expired None system in a safe state and consult Siemens Technical Support. (In the U.S.A., call 423–461–2522.) Serious malfunction. Consult Siemens Technical Action: Place the system in a safe state and...
Parameters Set by Software Setting User The PROFIBUS-DP RBC has parameters that are specified using the Parameters for the COM PROFIBUS configuration utility software. Refer to the SIMATIC 505 PROFIBUS-DP RBC TISOFT2 User Manual and the SIMATIC S5 ET 200 Distributed I/O System Manual for information about using COM PROFIBUS.
Diagnostic Data Reported by the RBC PROFIBUS-DP The standard for PROFIBUS-DP I/O, DIN 19245, Part 3, stipulates the Diagnostic Bytes format that each DP slave shall use to report specific diagnostics to the DP master. The diagnostics used by the 505/500 PROFIBUS-DP RBCs are described below.
Page 26
Diagnostic Data Reported by the RBC (continued) Byte 2: Station_Status_2 RBC is configured but not active (RBC can only set this to 0) Reserved RBC is operating in SYNCHRONOUS mode RBC is operating in FREEZE mode RBC’s watchdog timer has been activated Always set to 1 Static diagnostics (always set to 0) RBC waiting for parameterization...
Page 27
Byte 8: Ext_Diag_Data Reserved Remote port request pending Bytes 9–10: Reserved. Ext_Diag_Data Byte 11: Ext_Diag_Data Slot 8 is mismatched type Slot 7 is mismatched type Slot 6 is mismatched type Slot 5 is mismatched type Slot 4 is mismatched type Slot 3 is mismatched type Slot 2 is mismatched type Slot 1 is mismatched type...
Page 28
Diagnostic Data Reported by the RBC (continued) Byte 12: Ext_Diag_Data Slot 16 is mismatched type Slot 15 is mismatched type Slot 14 is mismatched type Slot 13 is mismatched type Slot 12 is mismatched type Slot 11 is mismatched type Slot 10 is mismatched type Slot 9 is mismatched type Byte 13:...
Page 29
Byte 14: Ext_Diag_Data Slot 8 contains failed module or is mismatched type Slot 7 contains failed module or is mismatched type Slot 6 contains failed module or is mismatched type Slot 5 contains failed module or is mismatched type Slot 4 contains failed module or is mismatched type Slot 3 contains failed module or is mismatched type Slot 2 contains failed module or is mismatched type Slot 1 contains failed module or is mismatched type...
Upgrading the Operating System Overview The operating system of the 505/500 PROFIBUS-DP RBC is contained in user-programmable non-volatile memory. An RBC with a previous release of the operating system can be reprogrammed with the latest release. You need a PC and a standard cable in order to reprogram the RBC. Contact the Technical Services Group for the appropriate upgrade files if you need to upgrade your RBC.
Connect your computer to the RBC with a standard 9-pin RS-232/423 null modem serial cable. This cable is available through your Siemens Energy & Automation, Inc., distributor: ask for SIMATIC 545/555 Programming Cable, part number 2601094–8001.
Group in Johnson City, Tennessee at 423-461-2522, or contact them by e-mail at simatic.hotline@sea.siemens.com. For technical assistance outside the United States, call 49-911-895-7000. You can also find information about Siemens automation products at our website at http://www.aut.sea.siemens.com. SIMATIC 505/500 PROFIBUS-DP RBC User Manual...
Page 33
SIMATIC is a registered trademark of Siemens AG. S5 and S7 are trademarks of Siemens AG. Series 505, Series 500, and TISOFT2 are trademarks of Siemens Energy & Automation, Incorporated. MS-DOS is a registered trademark of Microsoft Corporation.