Model SIM-16
Supervised Input Module
INTRODUCTION
OPERATION
PRE-INSTALLATION
INSTALLATION
P/N 315-034060-3
The SIEMENS Model SIM-16 Supervised Input Module
is a remotely located, general purpose input module. It
provides sixteen input circuits for remote system
monitoring. Each input can be individually programmed
as supervised (dry contacts only) or unsupervised
(general-purpose input). The SIM-16 has two Form C
relays. The relays and the inputs are programmable using
the Zeus Programming Tool.
The SIM-16 is mounted in an enclosure that is remotely
located from the Main Panel. Communication between
the SIM-16 and the NIC-C (Network Interface Card) is
through the Control Area Network (CAN) bus. Up to 99
SIM-16s can be used with a single NIC-C.
Each SIM-16 has two 10-position rotary switches that are
used to set the board address on the CAN which is a
sub-address of the NIC-C.
Every time a change of state of the input is detected, a
unique CAN message is sent to the NIC-C. A CAN
message from the NIC-C directed to the SIM-16 controls
the Form C relays.
Rotary Address Switches - Set the board address for
each SIM-16 using both of the ten-position rotary
switches located on the board (See Figure 1). Each of
these addresses must be a sub-address of the NIC-C
and must be the same as the addresses assigned in the
Zeus Programming Tool.
A SIM-16 may be installed in a REMBOX. When using REMBOX 2 or 4, mount the
SIM-16 in one module space on a REMBOX2-MP , P/N 500-634211 or REMBOX4-MP ,
P/N 500-634212 using the four screws provided. (Refer to REMBOX2-MP/REMBOX4-
MP Installation Instructions, P/N 315-034211.) Up to 4 SIM-16s will fit in a REMBOX2;
up to 8 SIM-16s will fit in a REMBOX4.
TB1
1
2
9
10
P2
TB3
6
1
TB2
Figure 1
SIM-16 Supervised Input
Module
Siemens Building Technologies
SIM-16
3
4
5
6
7
8
11
12
13
14
15
16
P3
S1
S2
TB4
6
1
Fire Safety

Advertisement

loading

Summary of Contents for Siemens SIM-16

  • Page 1 Module INSTALLATION A SIM-16 may be installed in a REMBOX. When using REMBOX 2 or 4, mount the SIM-16 in one module space on a REMBOX2-MP , P/N 500-634211 or REMBOX4-MP , P/N 500-634212 using the four screws provided. (Refer to REMBOX2-MP/REMBOX4- MP Installation Instructions, P/N 315-034211.) Up to 4 SIM-16s will fit in a REMBOX2;...
  • Page 2 • Each SIM-16 module is a node in the CAN bus. • The SIM-16 can be installed with or without an RNI. Connect the CAN bus and 24V as shown in Figures 2 and 3. • Up to 99 CAN modules, in any combination, can be connected to the CAN bus of each NIC-C.
  • Page 3 TO PSC-12, TB1 SEE NIC-C INSTALLATION INSTRUCTIONS, P/N 315-033240 FOR WIRING DETAILS Figure 3 SIM-16 Wiring Without An RNI NOTES 1. Contacts are unsupervised. 2. 1A max @ 24VDC resistive. SIM-16 3. All wiring must remain inside the enclosure or...
  • Page 4 3. Wiring for TB1 and TB2 is 18 *SUPPLIED WITH THE SIM-16 AWG min., 12 AWG max. 4. Maximum distance 500 feet from SIM-16 to supervised input. 5. In the Zeus Programming Tool, select supervised for each supervised input. 6. Supervised and unsuper-...