1MRS756705
3.12.
3.12.1.
Station Automation COM600
Operator's Manual
IEC 61850 setting groups and parameters
Certain IEC 61850 parameters are assigned to setting groups. These parameters can have
different values in different groups. Parameters belonging to setting group have # char-
acter as a prefix in the name. You can view the parameters of each group by selecting
the Setting group number from the drop-down menu. The currently active Setting group
number in the IED is indicated with an asterisk (*) in the Setting Group drop-down list.
To change the parameter values in a setting group:
1. Select the Setting Group to be edited.
2. Click Enable Write on the top of the Parameter Setting view.
3. Enter the new values for the parameters.
4. Write the changed parameter values to IED by clicking Write to IED.
5. Store the parameter changes permanently to IED by clicking disable write or closing
the tool. Pop-up dialog prompts for store or cancel.
The active setting group in the IED is changed with Active Setting Group parameter. To
change the parameter follow the steps 2 - 5.
Figure 3.11.1-2 Selecting a parameter group
Measurements
Viewing measurements
To view measurement information, click Measurements below the desired IED in the
substation structure. HMI updates the measurement information automatically.
COM600 3.3
parameters3.png
33